(Heat pump units for Heat pump series 10CR~25CR with wire remote control & PCB)
IMPORTANT:
These values are for information only, they should be checked and selected to comply with the local and/or
national codes and regulations. They are also subjected to the type of installation and size of
conductors.
INDOOR UNIT
CC 10CR
CC 15CR
CC 20CR
CC 25CR
OUTDOOR UNIT
SL 10BR
SL 15BR
SL 20BR
SL 25BR
Voltage range
220V – 240V /1Ph/ 50Hz +
!
Recommended fuse
A
6
10
16
20
Power Supply Cable size
mm
2
1.5
1.5
2.5
2.5
Number of conductors
3
3
3
3
Interconnection Cable size
mm
2
1.5
1.5
2.5
2.5
Number of conductors
3
3
3
3
The electrical power must be provided with protection
devices (circuit breaker or fuse) with double pole
separation system (phase + neutral) with minimum
contact gap of 3mm.
!
TERMINAL STRIP
INDOOR UNIT
INTERCONNECTION
CABLE
TERMINAL STRIP
OUTDOOR UNIT
Heat pump units for Heat pump series 10CR~25CR with wire remote control & PCB
Indoor unit
CC 30C
Outdoor unit
SL 30C
Voltage range
220V – 240V/ 1Ph/ 50Hz +
!
Recommended fuse
A
25
Power Supply Cable size
mm
2
4
Number of conductors
3
Interconnection Cable size
mm
2
2.5
Number of conductors
7
IMPORTANT:
These values are for information only, they should be checked and selected to comply with the local and/or
national codes and regulations. They are also subjected to the type of installation and size of
conductors used.
(Cooling only units for series 30C with wire remote control & PCB)
Cooling only units for series 30C with wire remote control & PCB
N
COMP
4WV
OF
N
L
COMP
4WV
OF
N
N
L
COMP
L
N
S
R
TH
L
N
The electrical power must be provided with protection
devices (circuit breaker or fuse) with double pole
separation system (phase + neutral) with minimum
contact gap of 3mm.
!
TERMINAL STRIP
OUTDOOR UNIT
INTERCONNECTION
CABLE
TERMINAL STRIP
INDOOR UNIT
OUTDOOR COIL SENSOR
CCC-0700 (01~16) ENG*