background image

1-13

English

REFRIGERANT GAS TANK

FLEXIBLE HOSE

HIGH PRESSURE GAUGE

MANIFOLD

LOW SIDE

PRESSURE GAUGE

GAS VALVE

REFRIGERANT PIPING

INDOOR UNIT

OUTDOOR UNIT

LIQUID VALVE

ADDITIONAL CHARGE

The refrigerant is pre-charged in the outdoor unit. If the
piping length is less than 5m, additional charge after
vacuuming is not necessary. When the piping length is more
than 5m, use the table below.

Additional charge operation

This operation must be done by using gas cylinder and a
precise weighing machine obligatorily. The additional charge
is top up into the outdoor unit by suction valve via service
port.

• Remove the service valve plug.
• Connect the low pressure manifold to the suction service

port, center manifold to the cylinder tank and close the
high pressure manifold (see figure below).
Purge all the flexible hose with refrigerant gas.

• Start the air conditioner unit.
• Open the gas cylinder and low pressure manifold valve.
• When the required refrigerant quantity is pumped in the

unit, close the low pressure manifold and the gas cylinder
valve.

• Disconnect the manometer and the gas cylinder. Place back

the service port cap.

Model

7m

10m

15m

20m

CC10C

30

75

CC15C

30

75

CC20C

30

75

150

CC25C

76

190

380

CC30C

100

250

500

750

CC40C

100

250

500

750

CC50C

100

250

500

750

CC60C

100

250

500

750

Cooling only unit
Additional charge in gram

Model

7m

10m

15m

20m

CC10CR

40

100

CC15CR

40

100

CC20CR

50

125

250

CC25CR

100

250

500

CC30CR

100

250

500

750

CC40CR

100

250

500

750

CC50CR

100

250

500

750

CC60CR

100

250

500

750

Heat pump unit
Additional charge in gram

Check refrigerant leak

Check with refrigerant detector whether there is a leak on
the flare type connection of the indoor unit and outdoor unit.
Hints: After operation for sometime, check if there is oil
traces, there is a leak.

CCC-0700 (01~16) ENG*

2/1/01, 10:42 AM

13

Содержание ACC10C

Страница 1: ...020C SL20B ALC20B MLC020B CC25C ACC25C MCC025C SL25B ALC25B MLC025B CC30C ACC30C MCC030C SL30C ALC30C MLC030C CC40C ACC40C MCC040C SL40C ALC40C MLC040C CC50C ACC50C MCC050C SL50C ALC50C MLC050C CC60C...

Страница 2: ...note on the following important points when installing Do not install the unit where leakage of flammable gas may occur If gas leaks and accumulates at the surrounding of the unit it may cause fire i...

Страница 3: ...DIMENSIONS Indoor Unit CC A B C D E F G H I J K L 10 C CR 31 741 702 662 10 765 72 261 411 349 225 261 15 C CR 31 881 842 802 10 905 72 261 411 349 225 261 20 C CR 31 1041 1002 962 10 1065 72 261 411...

Страница 4: ...66 92 348 318 129 482 68 5 20B 20BR 840 646 330 297 309 626 46 90 64 177 106 408 378 124 492 78 5 25B 25BR 840 646 330 297 309 626 46 90 64 177 106 408 378 124 492 78 5 2 5 64 5 CC A B C D E F 30C 30C...

Страница 5: ...r ance see drawing C Do not put the indoor unit where there is direct sunlight on unit The location is suitable for piping and drainage and it must be have a large distance between a door and unit CEI...

Страница 6: ...must not be susceptible to highly concentrated dust oil salt or sulfide gas Outdoor unit SL series Clearance RETURN AIR OBSTACLE OBSTACLE OBSTACLE OBSTACLE SERVICE ACCESS DISCHARGE AIR INSTALLATION O...

Страница 7: ...stage by stage advancing the blade of pipe cutter slowly Extra force and deep cut will cause more distortion of pipe and therefore extra burr Remove burrs from cut edges of pipes with a remover as sh...

Страница 8: ...TANT These values are for information only they should be checked and selected to comply with the local and or national codes and regulations They are also subjected to the type of installation and si...

Страница 9: ...BLE TERMINAL STRIP OUTDOOR UNIT Heat pump units for Heat pump series 10CR 25CR with wire remote control PCB Indoor unit CC 30C Outdoor unit SL 30C Voltage range 220V 240V 1Ph 50Hz Recommended fuse A 2...

Страница 10: ...national codes and regulations They are also subjected to the type of installation and size of conductors used Heat pump units for Heat pump series 30CR with wire remote control PCB Indoor unit CC 40...

Страница 11: ...l codes and regulations They are also subjected to the type of installation and size of conductors used Heat pump units for Heat pump series 40CR with wire remote control PCB Caution Ensure that the c...

Страница 12: ...ed with service port valve for connection to a manometer Remove the caps from the valve and the service port Connect the center manifold gauge with the vacuum pump Connect the manifold gauge to the se...

Страница 13: ...hose with refrigerant gas Start the air conditioner unit Open the gas cylinder and low pressure manifold valve When the required refrigerant quantity is pumped in the unit close the low pressure manif...

Страница 14: ...hat 1 Condenser fan is running with warm air blowing off the condensing unit 2 Evaporator blower is running and discharge cool air 3 The remote controller incorporates a 3 minute delay in the circuit...

Страница 15: ...essor oil is factory precharged It is not necessary to add any oil if the circuit remains sealed 1 All motor pre lubricated and sealed at factory PERIOD At least once every 2 week More frequently if n...

Страница 16: ...perfume etc which might have adhered onto the coil This is caused by air humidity after an extended long period of operation The set temperature is too low increase the temperature setting and operat...

Отзывы: