Piping Length & Elevation

If the pipe is too long, both the capacity and reliability of
the unit will drop. As the number of bends increases,
resistance to the flow of refrigerant system increases, thus
lowering cooling capacity. As a result, the compressor may
become defective. Always choose the shortest path and
follow the recommendations as tabulated below:

REFRIGERANT PIPING

Outdoor Unit

Indoor Unit

Ø Tube, D

A (mm)

Inch

mm

Imperial

Rigid

1/4"

6.35

1.3

0.7

3/8"

9.52

1.6

1.0

1/2"

12.70

1.9

1.3

5/8"

15.88

2.2

1.7

3/4"

19.05

2.5

2.0

Piping Connection To The Units

Align the center of the piping and tighten the flare nut
sufficiently with fingers.

Finally, tighten the flare nut with the torque wrench until
the wrench clicks.

Pipe Size mm / (in)

Torque Nm / (ft - lb)

6.35 (1/4)

18 (13.3)

9.53 (3/8)

42 (31.0)

12.7 (1/2)

55 (40.6)

15.88 (5/8)

65 (48.0)

19.05 (3/4)

78 (57.6)

Indoor Piping

Flare Nut

Flared Tube

Flare Joint

Spanar

Torque Wrench

Cutting Copper Tube

1/4t

Remove Burr Indoor

Copper Tube

Swaging Block

Piping Works

Do not use contaminated or damaged copper tubing. Do
not remove plastic, rubber plugs and brass nuts from the
valves, fittings, tubings and coils until you are ready to
connect suction or liquid line into valves or fittings.

If any brazing work is required, ensure that the nitrogen
gas is passed through coil and joints while the brazing
work is being done. This will eliminate soot formation on
the inside walls of the copper tubings.

Cut the connection pipe with a pipe cutter.

Remove burrs from cut edges of the pipes with remover.
Hold the end of the pipe downwards to prevent metal chips
from entering the pipe.

Insert the flare nuts, mounted on the connection parts of
both the indoor unit and outdoor unit onto the copper pipes.

Flare the pipe with extra length above the flaring tool as
shown in the table.

The flared edge must be even and not cracked or scratched.

Remark:

The refrigerant pre-charged in the outdoor unit
is for piping length up to 7.62 m/25 ft.

Model

Maximum length, m (ft), L

Max. elevation, m (ft), H

Max. number of (90º) bends

Liquid pipe size

Gas pipe size

10

15

20

25

12 (39)

12 (39) 15 (49)

15 (49)

5 (16.4) 5 (16.4)  8 (26.2) 8 (26.2)

10

10

10

10

1/4"

1/4"

1/4"

1/4"

3/8"

1/2"

1/2"

5/8"

Содержание 5SLX10C

Страница 1: ...INVERTER WALL MOUNTED SPLIT TYPE AIR CONDITIONER G Series INSTALLATION MANUAL Group INVERTER Part Number A08014078756 Date FEBRUARY 2005 IM WMXG 0205 McQuay 2005 McQuay International...

Страница 2: ...ND DIMENSIONS INSTALLATION PLATE Dimension A B C D E F G H I J K L M N O 10 15G GR 899 260 198 590 246 185 124 8 56 50 419 495 50 128 132 35 4 10 2 7 8 23 2 9 7 7 3 4 9 0 3 2 2 2 0 16 5 19 5 2 0 5 1 5...

Страница 3: ...ion 20 25G GR I 48 1 9 H 8 0 3 G 51 2 0 F 99 3 9 E 294 11 6 D 912 35 9 C 220 8 6 B 310 12 2 A 1060 41 7 O 160 6 3 N 138 5 4 M 160 6 3 L 403 15 9 K 354 13 9 J 43 1 7 FRONT VIEW TOP VIEW SIDE VIEW INSTA...

Страница 4: ...in mm in Dimension A B C D E F G H I J K L M N O 10 15C CR 700 521 250 485 175 36 95 93 86 68 441 130 111 15 18 27 5 20 5 9 8 19 1 6 8 1 4 3 7 3 6 3 3 2 6 17 3 5 1 4 3 0 5 0 7 3 0 1 B E F N C N K L L...

Страница 5: ...collect t t s par r r ment par un centre de collecte et de traitement sp cifique Veuillez vous r r r f f f s locales pour conna a a tre ces centres Ceci enne Questo prodotto soggetto alle disposizioni...

Страница 6: ...ture reference INSTALLATION MANUAL INVERTER WALL MOUNTED SPLIT TYPE AIR CONDITIONER COOLING ONLY R22 WMX20G MWMX020G SLV20B MLCV020B R410A 5WMX10G M5WMX010G 5SLX10C M5LCX010C 5WMX15G M5WMX015G 5SLX15C...

Страница 7: ...the drainage piping is not connected properly it may cause water leakage Do not overcharge the unit This unit is factory pre charged Overcharge will cause over current or damage to the compressor Ensu...

Страница 8: ...obstruction at the upper part of the unit please allow more space than the figure indicated in the above table Condensed Water Disposal of Outdoor Unit Heat Pump Unit Only There are 2 holes on the bas...

Страница 9: ...with vinyl tape Unit piping 50 0 mm 50 0 mm 50 0 mm Hole With Cone Drill Indoor Side Outdoor Side Mounting Installation Plate Ensure that the wall is strong enough to withstand the weight of the unit...

Страница 10: ...e Swaging Block Piping Works Do not use contaminated or damaged copper tubing Do not remove plastic rubber plugs and brass nuts from the valves fittings tubings and coils until you are ready to connec...

Страница 11: ...R410A is a new HFC refrigerant which does not damage the ozone layer The working pressure of this new refriger ant is 1 6 times higher than conventional refrigerant R22 thus proper installation servic...

Страница 12: ...e Vacuum pump Open Close Close Close Hi Low Model 10 15G 10 15GR 20G 20GR 25G 25GR 10m 32 8ft 12m 39 4ft 15m 49 2ft 35 65 50 90 35 65 110 60 110 185 90 165 280 120 220 370 Additional charge in gram Fo...

Страница 13: ...ator Lights forCooling Unit Heat Pump Unit Sleep Mode Cool Timer Ionizer NTP Inverter Unit MWMX G LED Indicator Lights Normal Operation And Fault Conditions For Cooling Heat Pump Unit Normal Operation...

Страница 14: ...d dry mode operation do not direct the air discharge louver downwards for too long If operating continues in this way condensation may occur on the louver thus resulting in water drippings Overheating...

Страница 15: ...ilter is a consumable part which you can purchase from your air conditioner dealer 4 Use the new filter immediately once it has been taken out from its sealed packing Do not unpack the new filter too...

Страница 16: ...hemicals to clean the indoor unit Period At least once every 2 weeks More frequently if necessary At least once every 2 weeks More frequently if necessary Service Parts Indoor air filter Indoor unit 1...

Страница 17: ...these verifications please contact the air conditioner unit installer The air filter is dirty The doors or windows are open The air suction and discharge are clogged The regulated temperature is not h...

Страница 18: ...hlichenAuslegung der vorliegendenAnleitung bzw einer ihrer bersetzungen gilt dieAusf hrung in Englisch nderungen von Design und technischen Merkmalen der in dieserAnleitung beschriebenen Ger te bleibe...

Отзывы: