MCQUAY Service Guide Book
Diagnosis
56
Ceiling Cassette A/C Series Inverter-X Model
Model
Board Handset
MCKX 20/25A/AR
VA3.0
G17 / SLM3
MCKX 10/15/20C/CR
VA3.0
G17 / SLM3
POWER
(Green)
TIMER
(Orange)
SLEEP
(Red)
HEAT
(Red)
Error
Code
(SLM3)
Operation / Faulty
Indication
Action
- Cooling
mode
-
- Timer
On
-
- Sleep
mode
On
-
- Heating
mode
-
- Defrost
mode
-
E1
Indoor temperature
sensor loose / short
Check indoor coil sensor
connection / change indoor
coil sensor
E2
Outdoor temperature
sensor loose / short
Check outdoor coil sensor
connection / change
outdoor coil sensor
E3 Communication
error
Check connection wires
between indoor and
outdoor
E4
Compressor overload
protection
If running ampere highly
increase, change the
compressor
E5 Pump
fault
Clear the clogging at drain
pipe. If pump is not
working, change the pump
E6
Compressor overheat /
gas leak
Check for leakage & repair
/ Top up refrigerant
E7
IPM / PFC / Partial
switching
Check supply voltage and
compressor phase
E8
Outdoor over current
Check the input current
and discharge pressure
/
ON
ON or OFF
BLINKING
1 time
2 times
3 times
4 times
5 times
6 times