CHARGER

BATTERY
LAMPS

CHG - TEST

SELF-TEST / DIAGNOSTIC

REMOTE SENSOR

(IF EQUIPPED)

>

GREEN - Status: Solid indicates system normal and flashes during any manual/auto 
test cycle.

>

RED - CHARGER FLASHING:  a charger failure requires the main system PCA to be 
replaced.

>

RED - BATTERY FLASHING:  battery may be disconnected or if it is connected 
replacement is needed.

>

RED - LAMPS FLASHING:  indicates that a Lamp(s) has failed.

OP-PANEL  INDICATORS:

TRANSFORMER

Cable

LAMP Cable

BATTERY

Cable

LAMP Cable

REMOTE Lamp

(IF EQUIPPED)

Factory Cable:
YELLOW - Signal from system
BLACK - Return line from system

PCA Configuration CODE  (see front page for the table of codes)

TROUBLE INDICATIONS / TROUBLESHOOTING

WIRING INFORMATION

Transformer Inputs:

=================

BLACK - 120V
WHITE - Common
RED - 277V

mcPhilben

 / 

Day-Brite

776 S.Green Street - Tupelo, Ms 38804 - ph: 662.842.7212 - fx: 662.680.6619

NORMAL OPERATION / MANUAL TESTS

>

GREEN - Status:

 Solid indicates system normal and charging current from the input source is available.

>

NOTE:

  To reset/cancel a test, simply press the button once during any test.

>

1 Press:

  performs a 5/sec brief test, all lamps operating from battery only.

>

2 Presses:

  performs a 1/min test, all lamps operating from battery only.

>

3 Presses:

  performs a 30/min discharge test, all lamps operating from battery only.  The system allows only one 30/min test each 24/hr period.

>

CONTINUOS MONITORING:  

The system monitors the battery for proper levels and performs periodic low-level charger and battery exercising.  Constant 

LAMP checking, should a LAMP fail, the system will flash the LAMPS indicator until repaired .  The charger is fully checked once per day by a internally 
disconnected/isolated integrity check, at this time the battery is also completely isolated and then check for proper capacity levels.

>

OPTIONAL FACTORY EQUIPPED ITEMS:

>

Remote-A:

  Unit will be supplied with a circuitry and pigtail connector cable require to control and operate a remote of up to 6/w (per wiring diagram).

>

Re-strike Time Delay:

   After a power failure and power is restored, the units lamps will remain lighted for a 15/min period (provided battery capacity remains) .

>

Remote Control:

  To operate, use a laser pen passing the laser over the remote sensor; simply duplicate the manual button (1, 2, 3) pushes.

OP-PANEL  INDICATORS / OPERATION:

TEST

Button

Содержание CTX Series

Страница 1: ...ere it will not readily be subjected to tampering by unauthorized personnel The use of accessory equipment not authorized by the manufacturer may cause an unsafe condition Do not use this equipment for other than its intended purpose Service of this equipment should be performed by qualified service personnel No rigid conduit Flexible conduit only No rigid conduit THERMOPLASTIC EMERGENCY LIGHTING ...

Страница 2: ...THE CEILING SURFACE WITH SUITABLE HARDWARE to prevent sag and or the unit falling Route the proper two transformer input wires BLACK 120V WHITE common RED 277V out through the hole in the back plate make input connection and secure back plate to the ceiling surface box Verify the battery is connected to the main PCA and connect the small transformer cable Replace snap the unit closed and check sec...

Страница 3: ... Sequence The unit automatically performs diag testing at all power up and initializes itself The system is capable of instantaneously detecting lamp failures and is indicated by a flashing LAMP LED The system also constantly monitors and controls all functions the charging circuit the battery the input power level the EXIT LED s and operator manual tests The charge circuit is computer controlled ...

Страница 4: ...test 1 Press performs a 5 sec brief test all lamps operating from battery only 2 Presses performs a 1 min test all lamps operating from battery only 3 Presses performs a 30 min discharge test all lamps operating from battery only The system allows only one 30 min test each 24 hr period CONTINUOS MONITORING The system monitors the battery for proper levels and performs periodic low level charger an...

Отзывы: