CHARGER
BATTERY
LAMPS
CHG - TEST
SELF-TEST / DIAGNOSTIC
REMOTE SENSOR
(IF EQUIPPED)
>
GREEN - Status: Solid indicates system normal and flashes during any manual/auto
test cycle.
>
RED - CHARGER FLASHING: a charger failure requires the main system PCA to be
replaced.
>
RED - BATTERY FLASHING: battery may be disconnected or if it is connected
replacement is needed.
>
RED - LAMPS FLASHING: indicates that a Lamp(s) has failed.
OP-PANEL INDICATORS:
TRANSFORMER
Cable
LAMP Cable
BATTERY
Cable
LAMP Cable
REMOTE Lamp
(IF EQUIPPED)
Factory Cable:
YELLOW - Signal from system
BLACK - Return line from system
PCA Configuration CODE (see front page for the table of codes)
TROUBLE INDICATIONS / TROUBLESHOOTING
WIRING INFORMATION
Transformer Inputs:
=================
BLACK - 120V
WHITE - Common
RED - 277V
mcPhilben
/
Day-Brite
776 S.Green Street - Tupelo, Ms 38804 - ph: 662.842.7212 - fx: 662.680.6619
NORMAL OPERATION / MANUAL TESTS
>
GREEN - Status:
Solid indicates system normal and charging current from the input source is available.
>
NOTE:
To reset/cancel a test, simply press the button once during any test.
>
1 Press:
performs a 5/sec brief test, all lamps operating from battery only.
>
2 Presses:
performs a 1/min test, all lamps operating from battery only.
>
3 Presses:
performs a 30/min discharge test, all lamps operating from battery only. The system allows only one 30/min test each 24/hr period.
>
CONTINUOS MONITORING:
The system monitors the battery for proper levels and performs periodic low-level charger and battery exercising. Constant
LAMP checking, should a LAMP fail, the system will flash the LAMPS indicator until repaired . The charger is fully checked once per day by a internally
disconnected/isolated integrity check, at this time the battery is also completely isolated and then check for proper capacity levels.
>
OPTIONAL FACTORY EQUIPPED ITEMS:
>
Remote-A:
Unit will be supplied with a circuitry and pigtail connector cable require to control and operate a remote of up to 6/w (per wiring diagram).
>
Re-strike Time Delay:
After a power failure and power is restored, the units lamps will remain lighted for a 15/min period (provided battery capacity remains) .
>
Remote Control:
To operate, use a laser pen passing the laser over the remote sensor; simply duplicate the manual button (1, 2, 3) pushes.
OP-PANEL INDICATORS / OPERATION:
TEST
Button