INSTALLATION

>

WALL MOUNT) 

 Always verify the input voltage source.  Open front cover as shown above.  Route the required transformer input wires (BLACK=120V, 

WHITE=common, RED=277V) out though the center K/O and make input connection in the box.   Simply use the Box pattern K/O’s in the back panel as needed 
to mount to wall box and secure unit to the wall.  If the unit is shipped with the battery disconnected, connect/verify at this time the battery is connected to the 
BAT location on the main PCA. Connect the small transformer cable to the PCA at the XFMR location and replace/snap covers, then proceed to Power-Up 
Sequence...

>

CEILING MOUNT) 

 CAUTION: (2) SCREWS MUST BE USED TO MOUNT THE BACK-PLATE TO THE CEILING SURFACE WITH SUITABLE HARDWARE( to 

prevent sag and/or the unit falling).  Route the proper two transformer input wires  (BLACK=120V, WHITE=common, RED=277V) out through the hole in the 
back-plate, make input connection, and secure back-plate to the ceiling surface/box.  Verify the battery is connected to the main PCA, and connect the small 
transformer cable.  Replace/snap the unit closed and check security, then proceed to Power-Up Sequence...

WALL / CEILING INSTALLATION:

TO OPEN COVER

TO OPEN LAMP

Transformer Inputs:

=================

BLACK - 120V
WHITE - Common
RED - 277V

REMOVE THE INPUT POWER IMMEDIATELY IF ALL 

RED LED’S ON THE OP-PANEL FLASH:

   This 

indicates that the input power is incorrectly wired, and 
needs to be corrected.  IF 277 is applied to the 120 tap 
for more than 7/sec, then the fusable-link may open 
requiring the transformer to be replaced.  Note that this 
condition is not covered by warranty.    

IMPORTANT NOTE:

Содержание CTX Series

Страница 1: ...ere it will not readily be subjected to tampering by unauthorized personnel The use of accessory equipment not authorized by the manufacturer may cause an unsafe condition Do not use this equipment for other than its intended purpose Service of this equipment should be performed by qualified service personnel No rigid conduit Flexible conduit only No rigid conduit THERMOPLASTIC EMERGENCY LIGHTING ...

Страница 2: ...THE CEILING SURFACE WITH SUITABLE HARDWARE to prevent sag and or the unit falling Route the proper two transformer input wires BLACK 120V WHITE common RED 277V out through the hole in the back plate make input connection and secure back plate to the ceiling surface box Verify the battery is connected to the main PCA and connect the small transformer cable Replace snap the unit closed and check sec...

Страница 3: ... Sequence The unit automatically performs diag testing at all power up and initializes itself The system is capable of instantaneously detecting lamp failures and is indicated by a flashing LAMP LED The system also constantly monitors and controls all functions the charging circuit the battery the input power level the EXIT LED s and operator manual tests The charge circuit is computer controlled ...

Страница 4: ...test 1 Press performs a 5 sec brief test all lamps operating from battery only 2 Presses performs a 1 min test all lamps operating from battery only 3 Presses performs a 30 min discharge test all lamps operating from battery only The system allows only one 30 min test each 24 hr period CONTINUOS MONITORING The system monitors the battery for proper levels and performs periodic low level charger an...

Отзывы: