Extraction fans lower the pressure in a building which can cause spillage of
combustion products from an open-flued appliance. This can occur even if
the appliance and the fan are in different rooms. If mechanical extraction is
unavoidable in the same room as your stove, then seek specialist advice to
ensure safe operation of the appliance.
A competent installer should be aware of specific ventilation parameters.
Building control guidance for heat producing appliance ventilation can be
found at:
https://www.hetas.co.uk/19223/
For local building regulations, please see page 4.
FLUE / CHIMNEY
It is important that the flue or chimney to which this appliance is to be
connected has been checked by a competent person to ensure its suitability
and that it will work safely. The chimney or flue and installation should
comply with local and national building regulations.
Sufficient operating draft is required for the product to function optimally.
The following considerations should be considered to ensure safe operation
of the appliance.
The flue must be:
•
Suitable for use with solid fuel burning appliances (Min. rating of
T400).
•
In good condition and provide a draft of 10-20 Pa.
•
Free from any internal obstructions.
•
At least 4.5 metres from the top of the stove outlet to the top of the
chimney.
•
Independent from a shared flue system of any type.
•
Larger or equal in diameter than the appliance flue collar size.