16
SW1 (HEAT) AND SW4 (DELAY) DIP SWITCHES MUST BOTH BE ADJUSTED ACCORDING TO INPUT (NOZZLE SIZE).
NOTE:
Table A-10 ECM Blower Set-Up (POF1HD140AVFA)
DIP SWITCH ADJUSTMENT CHART
FOR INPUT 0.75 USGPH TO 1.00 USGPH
SW1 - HEAT
SW2 - COOL
DIP Switch
Position
100-10DD blower with ½ HP ECM
SW2 (COOL): 1 TON is approximately equal to 400 CFM
SW3 (ADJUST): (Heating Mode) Increase OR decrease temperature rise respectively
(Cooling Mode) Increase OR decrease CFM respectively
INPUT
DIP Switch Position
AC Size
1 2
POS.
USGPH
1
2
POS.
(TON)
OFF OFF A
1.00
OFF OFF A
3
ON OFF B
0.85
ON OFF B 2.5
OFF ON C
N/A
OFF ON C
2
ON ON D
0.75
ON ON D 1.5
SW3 - ADJUST
SW4 - DELAY
DIP Switch
Position
CFM
DIP Switch Position
INPUT
1 2
POS.
1
2
POS.
USGPH
OFF OFF A
0%
OFF OFF A 1.00
ON OFF B
(+)15%
ON OFF B 0.85
OFF ON C
(-)15%
OFF ON C N/A
ON ON D
N/A
ON ON D 0.75