background image

-2-

4

3

2

1

“A”

FIGURE 1

MOBILE HOMES

The installation of a range designed for mobile home
installation must conform with the Manufactured Home
Construction and Safety Standard, Title 24 CFR, Part
3280 (formerly the Federal Standard for Mobile Home
Construction and Safety, Title 24 HUD, Part 280) or, when
such standard is not applicable, the Standard for
Manufactured Home Installations 1982 (Manufactured
Home Sites, Communities and Set-Ups), ANSI
A225.1-latest edition, or with local codes.

LOCATING THE RANGE

Place range in a well lit area. Do not set range over holes
in the floor or other locations where it may be subject to
strong drafts. Any opening in the wall behind the range
and in the floor under the range should be sealed. Make
sure the flow of combustion or ventilation air is not
obstructed.

INSTALLATION DRAWINGS

IMPORTANT

PLEASE KEEP FOR THE USE OF THE
LOCAL ELECTRICAL INSPECTOR.

“A” = 30 inches minimum clearance between the top of
the cooking surface and the bottom of an unprotected
wood or metal cabinet, or “A” = 24 inches minimum
when bottom of wood or metal cabinet is protected by
not less than 1/4-inch thick flame-retardant millboard
covered with not less than No. 28 MSG sheet steel,
0.015-inch thick stainless steel, 0.024-inch thick
aluminum, or 0.020-inch thick copper.

To eliminate the risk of burns or fire by reaching over
heated surface units, cabinet storage space located
above the surface units should be avoided. If cabinet
storage is to be provided, the risk can be reduced by
installing a range hood that projects horizontally a
minimum of 5 inches beyond the bottom of the cabinets.

FIGURE 1

1, 2, 3 - COMBUSTIBLE BUILDING WALLS.

4 - COMBUSTIBLE WALL CABINET.

A free-standing range may be installed adjacent to (0

²

from) combustible walls 1, 2 & 3.

A slide-in and drop-in range may be installed adjacent to
(0

²

from) combustible walls 2 & 3. The rear wall

clearance will be determined by cabinet cut-out depth
shown in illustrations on pages 3 and 4.

Содержание PER5715BAW

Страница 1: ...e of range can result in serious injury or property damage CLEARANCE DIMENSIONS For complete information in regard to installation of free standing drop in and slide in ranges see figures 1 through 4...

Страница 2: ...L INSPECTOR A 30 inches minimum clearance between the top of the cooking surface and the bottom of an unprotected wood or metal cabinet or A 24 inches minimum when bottom of wood or metal cabinet is p...

Страница 3: ...SELF CLEAN RANGE DISCOLORATION OR DELAMINATION MAY OCCUR TO AVOID POSSIBLE DAMAGE WE RECOMMEND INCREASING THE 30 CABINET OPENING TO 31 1 4 MINIMUM AND USING HEAT SHIELD KIT CABKIT V THE COUNTERTOP CU...

Страница 4: ...23 1 4 CUT DEPTH PROVIDE FOR 120 208 120 240 VOLT JUNCTION BOX FOR RANGE CONDUIT BELOW UNIT 1 1 4 27 1 2 FROM TOP OF COUNTER 30 CABINET OPENING RECOMMEND THE USE OF 3 1 2 WIDE SLATS ON EACH SIDE 24 C...

Страница 5: ...l C Use the bracket as a template and mark the required holes as shown in figure 5 for the type of construction you will be using D Free standing and slide in ranges may be secured to either floor or...

Страница 6: ...are equipped with a non lift up top All free standing ranges with a glass top are non lift up Coil tops are lift up D For SAFETY CONSIDERATIONS as well as optimum performance adjust the range so that...

Страница 7: ...ire plug in outlet placed at a convenient point near the back of the range The range is then connected to this outlet through an approved range connector pigtail fastened securely to the terminal bloc...

Страница 8: ...d Only a 4 wire cord or conduit should be used 2 The ground wire from the service cord or conduit must connect to the range chassis using the green ground screw 3 The white wire of the service cord or...

Отзывы: