EXAMPLE:  For a bank of four  dryers, 2 unrestricted openings  measuring
12-inches by 24-inches (30.48 cm by 60.96 cm) are acceptable.

To compensate for the use of registers or louvers used over
the openings, this area must be increased by approximately
33%.  Make-up air openings  should not be located  in an
area directly near where exhaust vents exit the building.
Allowances  must be made for  remote or  constricting
passageways  or  where dryers  are  located at high altitudes
or  predominantly  low  pressure areas.

IMPORTANT: Make-up air must be free of dry cleaning
solvent fumes.  Make-up air that is contaminated by dry
cleaning  solvent fumes  will  result  in  irreparable damage to
the  motors and other  dryer  components.

NOTE:

 

Component failure due to dry cleaning solvent

fumes will void the warranty.

Exhaust Requirements ________________

Exhaust ductwork  should be designed and installed by  a
qualified professional.  Improperly sized ductwork will create
excessive back  pressure,  which  results  in  slow  drying,
increased use of energy, and shutdown of the burner by the
airflow  (sail)  switch, burner  hi-limits, or  lint  chamber  hi-limit
protector thermostat.  The dryer must be installed with a proper
exhaust duct connection to the outside.

IMPORTANT: The dryer should be located where a
minimum  amount of exhaust ducting  will be necessary.

The dryer must be installed with adequate clearance for air
openings  into the combustion  chamber.

IMPORTANT: The dryer must be installed in a location/
environment,  which the ambient temperature  remains
between 40° F (4.44° C) and 130° F (54.44° C).

Dryer Enclosure Requirements _______

Bulkheads and partitions  should be made of non-
combustible  material.

A The  requirement to allow the dryer door to open completely  is

29-inches  (74  cm).

B A  minimum  overhead  clearance of 12-inches  (30.48  cm)  is

required.

C Dryer should be positioned a minimum of 12-inches (30.48 cm)

away  from the nearest obstruction.  24-inches  (60.96  cm)  is
recommended for ease of installation, maintenance, and service.

D 1/16” (1.5875 mm) minimum is required.

E Flooring  should be level  or below  dryer  cabinet for ease of

removing panels during maintenance.

F Dryers may be positioned sidewall to sidewall, however a 1/16”

(1.5875 mm) minimum allowance must be made for the opening
and closing of the control door, along with the removal of panels
during maintenance.

G 4-inch (10.16 cm) maximum.

Fresh Air Supply Requirements _______

When the dryer  is operating,  it draws  in  room  air, heats  it,
passes this  air through the tumbler, and exhausts  it out of
the building.  Therefore, the room  air  must be continually
replenished from the outdoors.  If the make-up air  is
inadequate, drying time and drying efficiency will be adversely
affected.  Ignition problems and sail  switch  “fluttering”
problems  may  result, as  well  as  premature  motor failure
from overheating.  The dryer must be installed with provisions
for adequate combustion and make-up air  supply.
Air supply (make-up air) must be given careful consideration
to ensure proper performance of each dryer.  Fresh air
ventilation openings shall not be blocked and/or sealed.  As
a general rule, an unrestricted air entrance from the outdoors
of 1.0 ft

2

 (0.093 m

2

) is required for each dryer.  (Based on 1

inch

2

 [6.5 cm

2

] per 1,000 Btu [252 kcal].)

It is not necessary to have a separate make-up air opening
for each dryer.  Common  make-up air openings  are
acceptable.  However, they must be set up in such a manner
that the make-up air is distributed equally to all the dryers.

Fire Hazard

Use a heavy metal vent.

Do not use a plastic vent.

Do not use a metal foil vent.

Failure to follow these instructions can result in death
or fire.

!

  WARNING

A = 12-inches (30.48 cm)
B = 24-inches (60.96 cm)

Содержание MLG-30PDA

Страница 1: ...MLG 30PDA Installation Manual Stack Dryer Part No 113543 3 RETAIN THESE INSTRUCTIONS IN A SAFE PLACE FOR FUTURE REFERENCE...

Страница 2: ......

Страница 3: ...m rubber or similarly textured rubber like materials Clean lint screen every third load to fourth Keep area around the exhaust opening and adjacent surrounding areas free from the accumulation of lint...

Страница 4: ...dryer must be used only for drying water washed fabrics The dryer must never be operated with any of the back guards or service panels removed Personal injury or fire could result The wiring diagram...

Страница 5: ...ERS PER 48 53 TRUCK 30 33 VOLTAGE AVAILABLE 120V 1 2w 60 Hz APPROXIMATE NET WEIGHT 675 lb 306 kg APPROXIMATE SHIPPING WEIGHT 710 lb 322 kg AIRFLOW PER POCKET 400 cfm 11 3 cmm HEAT INPUT PER POCKET 72...

Страница 6: ...manual refer to Exhaust Requirements section Excessive Weight Hazard Use two or more people and mechanical equipment to lift move and install dryer Failure to do so can result in back or other injury...

Страница 7: ...ely is 29 inches 74 cm B A minimum overhead clearance of 12 inches 30 48 cm is required C Dryer should be positioned a minimum of 12 inches 30 48 cm away from the nearest obstruction 24 inches 60 96 c...

Страница 8: ...tion regulations of the country of destination Outside Ductwork Protection To protect the outside end of the horizontal ductwork from the weather a 90 elbow bent downward should be installed where the...

Страница 9: ...trical Code ANSI NFPA NO 70 LATEST EDITION or in Canada the Canadian Electrical Codes Parts 1 2 CSA C22 1 1990 or LATEST EDITION IMPORTANT Failure to comply with these codes or ordinances and or the r...

Страница 10: ...nada Standards Canadian Electrical Codes Parts 1 2 CSAC22 1 1990 or LATEST EDITION The ground connection may be to a proven earth ground at the location service panel Electrical Connections A wiring d...

Страница 11: ...feet 609 6 meters for correct burner orifice size s Btu rating for both tumblers Gas Connections Inlet connection 1 2 M N P T 1 per pocket Inlet supply size 1 2 Pipe minimum 1 per pocket Combined top...

Страница 12: ...egulator must be installed in the gas supply line header if the natural gas pressure exceeds 13 0 in WC 32 34 mb pressure A minimum 1 8 N P T plugged tap accessible for a pressure gauge connection mus...

Страница 13: ...o operate the dryer Read all DANGER WARNING CAUTION and DIRECTION labels attached to the dryer Check incoming supply voltage to be sure that it is the same as indicated on the data label Be sure that...

Страница 14: ...rformed by a qualified trained technician service agency or gas supplier If service is required contact the Maytag distributor from whom the equipment was purchased If the distributor cannot be contac...

Страница 15: ...ick A back draft damper that is sticking partially closed can result in slow drying and shutdown of heat circuit safety switches or thermostats When cleaning the dryer cabinet s avoid using harsh abra...

Страница 16: ...MLG 30PDA Manuel d installation S cheuse superpos e Part No 113543 3 CONSERVER CES INSTRUCTIONS EN LIEU S R POUR R F RENCE ULT RIEURE...

Страница 17: ...minimum le risque d incendie ou d explosion ou pour viter tout dommage mat riel toute blessure ou la mort Ne pas entreposer ni utiliser d essence ni d autres vapeurs ou liquides inflammables proximit...

Страница 18: ...18 Maytag Co 113543 3...

Страница 19: ...NT La s cheuse doit tre utilis e uniquement pour s cher du linge lav l eau La s cheuse ne doit jamais fonctionner alors que les protections arri re ou les panneaux de service sont d mont s Des blessur...

Страница 20: ...MATIF 675 lb 306 kg POIDS BRUT APPROXIMATIF TRANSPORT 710 lb 322 kg D BIT D AIR PAR TAMBOUR 400 pi min 11 3 m min PUISSANCE CALORIFIQUE PAR TAMBOUR 72 000 Btu h 18 143 kcal h RACCORD D VACUATION DIAM...

Страница 21: ...eter recycler tous les mat riaux d emballage IMPORTANT Il est imp ratif d installer la s cheuse sur un plancher non combustible La s cheuse doit tre utilis e dans un lieu non combustible Avant d insta...

Страница 22: ...doit tre am nag e de fa on ce que l air d appoint soit uniform ment r parti entre toutes les s cheuses A 12 pouces 30 48 cm B 24 pouces 60 96 cm EXEMPLE Pour un ensemble de quatre s cheuses deux ouve...

Страница 23: ...par dessus Tous les raccords de conduit doivent tre couverts de ruban adh sif pour viter que l humidit et la charpie s chappent dans le local Les trappes d inspection doivent tre install es des point...

Страница 24: ...et 2 CSA C22 1 1990ouDERNI RE DITION IMPORTANT Tout manquement ces codes ou r glements et ou aux conditions stipul es dans ce manuel peut provoquer des blessures ou la panne d un organe REMARQUE La p...

Страница 25: ...e sur le tableau lectrique du local Raccordement lectrique Un sch ma de c blage contenant les informations de connexion se trouve derri re le tableau de commande Si les codes locaux le permettent l a...

Страница 26: ...rieur aliment s ensemble exigent une arriv e de 3 4 minimum Tuyauteries raccordements La s cheuse est fournie avec deux raccords d arriv e N P T de 1 2 l arri re Il est recommand de pr voir un robine...

Страница 27: ...isation g n rale d alimentation en gaz si la pression en gaz naturel d passe 13 0 po CE 32 34 mbar Un piquage N P T de 1 8 minimum avec bouchon accessible pour raccorder un manom tre doit tre install...

Страница 28: ...de mettre en marche la s cheuse contr ler les points suivants Lire toutes les tiquettes de DANGER AVERTISSEMENT MISE EN GARDE et CONSIGNE appos es la s cheuse Contr ler que la tension d alimentation...

Страница 29: ...RQUE Les intervalles recommand s portent sur une utilisation moyenne en l occurrence 6 8 heures op rationnelles en fonctionnement par jour Tous les 6 mois inspecter le conduit d vacuation et liminer t...

Страница 30: ...les trois ou quatre charges Si le filtre charpie est colmat le rendement de la s cheuse sera m diocre La trappe le tiroir du filtre charpie se trouve juste sous la porte de la s cheuse Ouvrir la trap...

Отзывы: