E.  EXHAUST REQUIREMENTS

Exhaust ductwork 

should be

 designed and installed by a qualified professional.  Improperly sized ductwork will

create excessive back pressure which results in slow drying, increased use of energy, and shutdown of the
burner by the airflow (sail) switch, burner hi-limits, or lint chamber hi-limit protector thermostat.  The dryer 

must

be

 installed with a proper exhaust duct connection to the outside.

When possible, it is suggested to provide a separate (single) exhaust duct for each dryer.

CAUTION:

This dryer produces combustible lint and 

must be

 exhausted to the outdoors.

CAUTION: IMPROPERLY

 

SIZED

 

OR

 

INSTALLED

 

EXHAUST

 

DUCTWORK

 

CAN

CREATE

 

A

 

POTENTIAL

 

FIRE

 

HAZARD.

The exhaust ductwork 

should be

 laid out in such a way that the ductwork travels as directly as possible to the

outdoors with as few turns as possible.  The shape of the ductwork is not critical provided that the minimum
cross section area is maintained.  Single or independent dryer venting is recommended.

It is suggested that the use of 90° turns be avoided; use 30° or 45° angles instead.

The ductwork 

should be

 smooth inside with no projections from sheet metal screws or other obstructions,

which will collect lint.  When adding ducts, the ducts to be added should overlap the duct to which it is connected.

ALL

 ductwork joints 

must be

 taped to prevent moisture and lint from escaping into the building.  Additionally,

inspection doors

 should be

 installed at strategic points in the exhaust ductwork for periodic inspection and

cleaning.

IMPORTANT:

When connecting ductwork to the dryer exhaust duct, be sure that when screws are
used they 

DO NOT

 restrict the operation (both opening and closing) of the damper.

NOTE:

When the exhaust ductwork passes through a wall, ceiling, or roof made of combustible
materials, the opening 

must be

 2-inches (5.08 cm) larger than the duct (all the way around).

The duct 

must be

 centered within this opening.

To protect the outside end of the horizontal ductwork from the weather, a 90° elbow bent downward 

should be

installed where the exhaust exits the building.  If the ductwork travels vertically up through the roof, it 

should be

protected from the weather by using a 180° turn to point the opening downward.  In either case, allow at least
twice the diameter of the duct between the duct opening and the nearest obstruction (i.e., roof or ground level).

IMPORTANT:

DO NOT

 use screens, louvers, or caps on the outside opening of the exhaust

ductwork.

IMPORTANT:

Exhaust back pressure measured by a manometer at the dryer exhaust duct area 

must

be 

no less than 0 and 

must not exceed

 0.3 inches (0.74 mb) of water column

(W.C.).

IMPORTANT: It is recommended

 that exhaust or booster fans not be used in the exhaust ductwork

system.

NOTE:

As per the National Fuel Gas Code, “Exhaust ducts for Type 2 clothes dryers shall be
constructed of sheet metal or other noncombustible material.  Such ducts shall be equivalent in
strength and corrosion resistance to ducts made of galvanized sheet steel not less than 26
gauge (0.0195-inches [0.50 mm]) thick.”

Содержание MDG30MNV

Страница 1: ...voisin Suivez les instructions du fournisseur Si vous ne pouvez rejoindre le fournisseur de gaz appelez le service des incendies L installation et l entretien doivent tre assur s par un installateur o...

Страница 2: ...nflammables proximit decet appareil ou de tout autre appareil We have tried to make this manual as complete as possible and hope you will find it useful The manufacturer reserves the right to make cha...

Страница 3: ...IFNEARDRYERSINOPERATION CAUTION DRYERSSHOULDNEVERBELEFTUNATTENDEDWHILEINOPERATION FORYOUR SAFETY DONOTDRYMOPHEADSINTHEDRYER DONOTUSEDRYERINTHEPRESENCEOFDRYCLEANINGFUMES WARNING UNDER NO CIRCUMSTANCES...

Страница 4: ...cluded with the dryer WARNING DRYER MUST NEVER BE OPERATEDWITHOUTTHE LINTFILTER SCREEN IN PLACE EVENIFANEXTERNALLINTCOLLECTIONSYSTEMISUSED Dryer must not be installed or stored in an area where it wil...

Страница 5: ...ration for Operation Start Up 18 I Preoperational Tests 19 J Preoperational Instructions 20 K Shutdown Instructions 21 SECTIONIV SERVICE PARTSINFORMATION 22 A Service 22 B Parts 22 SECTIONV WARRANTYIN...

Страница 6: ...building or area of ALL occupants e Immediately call your gas supplier from a neighbor s phone Follow the gas supplier s instructions f If you cannot reach your gas supplier call the fire department 4...

Страница 7: ...perlywillVOIDTHEWARRANTY 9 UNDER NO CIRCUMSTANCES should the dryer door switch lint door drawer switch or heat safety circuit ever be disabled WARNING PERSONALINJURYOR FIRE COULD RESULT SHOULD THE DRY...

Страница 8: ...S A F E WATER CONNECTION 3 4 11 5 NH VOLTAGE AVAILABLE 120v 1 2w 60 Hz APPROX WEIGHT UNCRATED 534 lbs 242 kg APPROX WEIGHT CRATED 571 lbs 259 kg HEAT INPUT 100 000 Btu hr 25 200 kcal hr AIRFLOW 460 c...

Страница 9: ...113307 7 Maytag Co 5 NOTE Themanufacturerreservestherighttomakechangesinspecificationsatanytimewithout noticeorobligation Specifications...

Страница 10: ...t chamber To remove the two 2 bolts located in the lint chamber area remove the lint door drawer With the skid removed to make it easier to slide the dryer into its final position slightly lower ALL f...

Страница 11: ...st ductwill be necessary 9 The dryer must be installed with adequate clearance for air openings into the combustion chamber CAUTION This dryer produces combustible lint and must be exhausted to the ou...

Страница 12: ...he area must be increased It is not necessary to have separate make up air openings for each dryer Common make up air openings are acceptable However they must be set up in such a manner that the make...

Страница 13: ...nspection doors should be installed at strategic points in the exhaust ductwork for periodic inspection and cleaning IMPORTANT When connecting ductwork to the dryer exhaust duct be sure that when scre...

Страница 14: ...n A 30 feet 9 144 meters The minimum diameter of this ductwork must be at least Dimension B 8 inches 20 32 cm Including basket tumbler dryer elbow connections or elbows used for outside protection fro...

Страница 15: ...ctwork Dimension A must be at least 8 inches 20 32 cm IMPORTANT No more than four 4 dryers should be connected to one 1 main common duct The illustration below shows the minimum cross sectional area f...

Страница 16: ...must be connected with copper wire only DO NOT use aluminum wire it could create a fire hazard The copper conductor wire cable must be of proper ampacity and insulation in accordance with electric co...

Страница 17: ...SA C22 1 1990 or LATEST EDITION The ground connection may be to a proven earth ground at the location service panel For added personal safety when possible it is suggested that a separate ground wire...

Страница 18: ...1 gas dryers are made into the rear service box located at the upper left area of the dryer Single Phase Electrical Lead Connections Black Positive White or Red Neutral or L2 Green Ground A ground lug...

Страница 19: ...use irreparable damage to the gas valve which willVOIDTHEWARRANTY WARNING FIRE OR EXPLOSION COULD RESULT DUE TO FAILURE OF ISOLATINGOR DISCONNECTINGTHE GAS SUPPLYAS NOTED 1 Gas Supply The gas dryer in...

Страница 20: ...hr 25 200 kcal hr 1 Natural Gas Regulation is controlled by the dryer s gas valve s internal regulator Incoming supply pressure must be consistent between a minimum of 6 0 inches 14 92 mb and a maximu...

Страница 21: ...er is 1 2 diameter For ease in servicing the gas supply line of each dryer must have its own shutoff valve The size of the main gas supply line header will vary depending on the distance this line tra...

Страница 22: ...or less than 1 2 psig 3 5 kPa H PREPARATION FOR OPERATION START UP The following items should be checked before attempting to operate the dryer 1 Read ALL CAUTION WARNING and DIRECTION labels attache...

Страница 23: ...ion attempts If there is no flame after the third ignitionattemptthemodulewilllockoutuntilitismanuallyreset Toresettheignitionsystem open and close the main door and restart the dryer b A gas pressure...

Страница 24: ...he L E D display will read MANUAL DRYING CYCLE D 00 00 MIN REMAIN NOTE The dryer can be stopped at any time by pressing the STOP CLEAR key at this time the dryer will go into a cycle pause If the STOP...

Страница 25: ...ryer is to be shutdown taken out of service for a period of time the following must be performed 1 Discontinue power to the dryer either at the external disconnect switch or the circuit breaker 2 Disc...

Страница 26: ...hen contacting the Maytag Co be sure to give the correct model number and serial number so that the inquiry is handled in an expeditious manner B PARTS Replacement parts should be purchased from the d...

Страница 27: ...must be completed and returned for each individual dryer NOTE Besuretoincludetheinstallationdatewhenreturningthewarrantycard s B WARRANTY For a copy of the manufacturer s commercial warranty covering...

Страница 28: ...AND OTHER FLAMMABLE VAPORSAND LIQUIDS NOTE Suggested time intervals shown are for average usage which is considered six 6 to eight 8 operational running hoursperday IMPORTANT Dryer produces combustib...

Страница 29: ...nnections and nonpermanent gas connections unions shutoff valves and orifices Motor and drive belts should be examined Cracked or seriously frayed belts should be replaced Tighten loose V belts when n...

Страница 30: ...e manufacturer to gather information on your particular dryer 3 MANUFACTURINGCODE NUMBER The number issued by the manufacturer which describes ALL possible options on your particular model 4 TYPE OFHE...

Страница 31: ...ompleting installation of the replacement microprocessor controller computer board reestablish power to the dryer b Start the drying cycle by pressing any of the preset cycles in letters A F c Verify...

Страница 32: ...s normal operation No L E D indicator indicates a power or an internal failure has occurred 3 For Models with DSI Module Type II Theory of Operation Start the drying cycle When the gas burner ignites...

Страница 33: ...attended to the Phase 7 microprocessor controller computer will display that the system was activated BEFORE YOU START CHECK LOCAL CODES AND PERMITS Call your local water company or the proper munici...

Страница 34: ...ession system will be INOPERATIVE IMPORTANT Appliance is to be connected to the water mains using a new hose set and the old hose set should not be reused 2 Water Connections The water connection is m...

Страница 35: ...e T or three way fitting located in the outlet supply side of the water solenoid valve The use and connections of this manual bypass are at the option or discretion of the owner The water connection f...

Страница 36: ...Part No 113307 7 06 26 08 0...

Отзывы: