PROPER INSTALLATION
CONFIGURATION SETTINGS
---
Start Configuration position
Interface Usage
0*
Unit is only controlled by the PTAC touchpad.
rE
Unit is both controlled by a wireless thermostat and/or the touchpad.
L5
Unit is controlled by a wired thermostat via the low voltage terminals only.
Au*
The fan only runs with the call for heating or cooling.
On
The fan runs continuously except in the OFF position.
C
The fan runs continuously in cooling and cycles with call for heating.
bP
Unit is equipped with fan operation button for guest selection of fan cycling.
bA
Unit is equipped with fan operation button, but self reverts to cyclic fan.
bC
Unit is equipped with fan operation button, but self reverts to continuous fan.
A
The fan always runs even in OFF mode
C
Cooler only with or without electric heat.
H*
Heat Pump.
0
Service no Operation "Eo"
C4
Room Identification first two digits
00-99
Set first two digits of room identification
C5
Room Identification last two digits
00-99
Set last two digits of room identification
0*
"No Occupancy" detection devices
1
Wired Door Switch and Motion Sensor present
18
Enter "No Occupancy" routine 18 hours after last control selection
0*
Normally Closed Device (Open when sensing motion)
1
Normally Open Device (Closed when sensing motion)
C8
Cooling Temperature Limiting
60*-72
Select temperature between 60 and 72 for minimum cooling set point
C9
Heating Temperature Limiting
68-90, 80*
Select temperature between 68 and 90 for maximum heating set point
8*
Mating thermostat has a "B" terminal
0
Mating thermostat has an "O" terminal
0*
Not Active
A
Active
c3
Unrented Cooling Temperature
45-95, 79*
Select temperature between 45 and 95 minimum unrented cooling set point.
c4
Unrented Heating Temperature
45-95, 63*
Select temperature between 45 and 95 minimum unrented heating set point.
0*
Not Active
1
Active
U
Active in No occupancy / Unrented State
CC
Dehumidistat call for a drop in temperature
3-8
3-8
F*
Fahrenheit Scale
C
Celsius Scale
L*
On, low fan*
H
On, high fan
0
Off
CF
Hi. Speed Cooling Smart Temperature
5*-9
5-9
CH
Hi Speed Heating Smart Temperature
6-8*
6-8
CJ
2nd Stage Heat. Dif.
4*-8
4-8
--
No electric heat
d1
Room Air Mix Cooling
1*
On
0
Off
d2
Room Air Mix Heating
0*
Off
1
On
d3
Air Mix Fan Speed
L*
Low
H
High
d4
Heating Smart Speed
0
Not Available
1*
Available
d5
Warnings,
1*
Enabled
OCT Lock & LED
0
Dis-enabled
d6
Sensorless Un-Occ. Time and Fan Revert Time
1-32
1- 32, 18*
d7
1st Un-Occ. Set Back Temperature
1-16
1-16, 2*
d8
1st Un-Occ. Set Back Time
.1, .5, 1-24
.1, .5, 1-24, .5*
d9
2nd Un-Occ. Set Back Temperature
1-16
1-16, 3*
dA
2nd Un-Occ. Set Back Time
.1, .5, 1-24
(d8)-24, 1*
dB
3rd Un-Occ. Set Back Temperature
1-16
1-16, 6*
dC
3rd Un-Occ. Set Back Time
.1, .5, 1-24
(dA)-24, 3*
dH
Electric Heater Size
00*, 15, 20,
25, 35, 50
00*, 15, 20, 25, 35 & 50
r4
Room Prefix
00* - 99
00* - 99
r5
Room Suffix
00* - 99
00* - 99
*Indicates factory default.
Reverse Cycle "B" or "O"
selection for thermostat
Description
C1
C2
Fan Operation
Wired Unrented Set Back
c2
Option Code
Feature Code
C0
Dehumidification
Cb
Description
C6
Wired Occupancy
C7
Wired Motion Sensor Type
C3
Reverse Cycle Operation
Cd
English/Metric Temperature
CE
Freeze Protection