background image

9

9 Ductwork

This air handler is designed for a complete supply and return 

ductwork system.

To ensure correct system performance, the ductwork is to be sized 

to accommodate 350-450 CFM per ton of cooling with the static 

pressure not to exceed 0.5” in w.c. Refer to ACCA Manual D, Manual 

S and Manual RS for information on duct sizing and application.

  

Flame retardant ductwork is to be used and sealed to the unit in a 

manner that will prevent leakage.

NOTE:

 A downflow application with electric heat must have an 

L-shaped sheet metal supply duct without any outlets or registers 

located directly below the heater.

9.1  Return Ductwork

 

DO NOT LOCATE THE RETURN DUCTWORK IN AN AREA 

THAT CAN INTRODUCE TOXIC, OR OBJECTIONABLE FUMES/

ODORS INTO THE DUCTWORK.  The return ductwork is to be 

connected to the air handler bottom (upflow configuration).

10  Return Air Filters

Each installation must include a return air filter.  This filtering may 

be performed at the air handler using the factory filter rails or 

externally such as a return air filter grille.  

When using the factory 

filter rails, a nominal 16x20x1”, 20x20x1” or 24x20x1” (actual 

dimension must be less than 23-½”x20”) filter can be installed on 

a B, C and D cabinet respectively (the cabinet size is the seventh 

letter of the model number).

11  Achieving 1.4% and 2.0% Airflow Low Leakage Rate

Ensure all the gaskets remain intact on all surfaces as shipped with 

the unit. These surfaces are areas between the upper tie plate and 

coil access panel, blower access and coil access panels, and between 

the coil access and filter access panels. Ensure upon installation, 

that the plastic breaker cover is sitting flush on the blower access 

panel and all access panels are flush with each other and the 

cabinet.  With these requirements satisfied, the unit achieves less 

than 1.4% airflow leakage @ 0.5 inch wc static pressure and less 

than 2% airflow leakage @1inch wc static pressure when tested in 

accordance with ASHRAE Standard 193.

12  Electric Heat

Do not operate this product without all the ductwork 

attached.

Refer to the installation manual provided with the electric heat kit 

for the correct installation procedure.  All electric heat must be 

field installed. If installing this option, the ONLY heat kits that  are 

permitted to be used are the HKS series. Refer to the air handler 

unit’s Serial and Rating plate or the HKS specification sheets to 

determine the heat kits compatible with a given air handler. No 

other accessory heat kit besides the HKS series may be installed 

in these air handlers.
The heating mode temperature rise is dependent upon the system 

airflow, the supply voltage, and the heat kit size (kW) selected.  Use 

data provided in Tables 3, 4 and 5 to determine the temperature 

rise (°F).

3

5

6

8

1 0

1 5

1 9 /2 0

2 5

8 0 0

1 2

1 9

2 3

3 1

3 7

5 6

1 0 0 0

9

1 5

1 9

2 5

3 0

4 4

1 2 0 0

8

1 2

1 5

2 1

2 5

3 7

4 9

6 2

1 4 0 0

7

1 1

1 3

1 8

2 1

3 2

4 2

5 3

1 6 0 0

6

9

1 2

1 5

1 9

2 8

3 7

4 6

1 8 0 0

5

8

1 0

1 4

1 6

2 5

3 3

4 1

2 0 0 0

5

7

9

1 2

1 5

2 2

3 0

3 7

CFM  

HEAT KIT NO M INAL k W  

230/1/60 SUPPLY VOLTAGE - TEMP. RISE °F

Table 3

3

5

6

8

1 0

1 5

1 9 /2 0

2 5

8 0 0

1 1

1 8

2 2

3 0

3 5

5 4

1 0 0 0

9

1 4

1 8

2 4

2 8

4 2

1 2 0 0

7

1 2

1 5

2 0

2 4

3 5

4 7

5 9

1 4 0 0

6

1 0

1 3

1 7

2 0

3 0

4 0

5 1

1 6 0 0

6

9

1 1

1 5

1 8

2 7

3 5

4 4

1 8 0 0

5

8

1 0

1 3

1 6

2 4

3 1

3 9

2 0 0 0

4

7

9

1 2

1 4

2 1

2 8

3 5

CFM  

HEAT KIT NO M INAL k W  

220/1/60 SUPPLY VOLTAGE - TEMP. RISE °F

Table 4

3

5

6

8

10

15

19/20

25

80 0

10

17

21

28

3 3

1 000

8

13

17

22

2 7

4 0

1 200

7

11

14

19

2 2

3 3

45

56

1 400

6

10

12

16

1 9

2 9

38

48

1 600

5

8

10

14

1 7

2 5

33

42

1 800

5

7

9

12

1 5

2 2

30

37

2 000

4

7

8

11

1 3

2 0

27

33

CFM  

HEAT KIT NOM INAL kW  

208/1/60 SUPPLY VOLTAGE - TEMP. RISE °F

Table 5

3

5

6

8

10

15

19

20

25

AVPTC25B14

550

650

700

800

850

875

AVPTC29B14

550

650

700

800

875

875

AVPTC35B14

550

650

700

800

875

1050

AVPTC37B14

550

650

700

800

875

1050

AVPTC31C14

600

700

770

880

970

1090

1280

AVPTC33C14

600

700

750

850

920

950

AVPTC37C14

700

770

880

970

1090

1280

AVPTC39C14

700

770

880

970

1090

1280

AVPTC49C14

800

800

950

1090

1290

1345

AVPTC59C14

800

800

950

1090

1290

1345

AVPTC37D14

870

970

1060

1120

1220

1250

AVPTC49D14

950

1060

1150

1220

1520

AVPTC59D14

990

1110

1200

1240

1520

1520

AVPTC61D14

1030

1150

1250

1320

1650

1690

1750

HEATER (kW)

Model

MINIMUM CFM REQUIREMENTS FOR HEATER KITS

Table 6

NOTE:  

For installations not indicated above the following formula 

is to be used:

TR = (kW x 3412) x (Voltage Correction) / (1.08 x CFM)

Where:  

TR 

=   Temperature Rise

 

kW 

=   Heater Kit Actual kW

 

3412  =   Btu per kW

 

VC*  =  .96 (230 Supply Volts)

 

 

=  .92 (220 Supply Volts)

 

 

=  .87 (208 Supply Volts)

 

1.08  =   Constant

 

CFM  =   Measured Airflow

 

 

VC* (Voltage Correction)

Содержание Amana AVPTC 14 Series

Страница 1: ...nt The manufac turer will not be responsible for any injury or property dam age arising from improper service or servide procedures If you service this unit you assume responsibility for any injury or...

Страница 2: ...ards Institute ANSI National Fire Protection Association NFPA 70 and local state codes In Canada electrical grounding is to be in accordance with the Canadian Electric Code CSA C22 1 uninterrupted unb...

Страница 3: ...this document with the unit Carefully read all instruc tions for the installation prior to installing product Make sure each step or procedure is understood and any special consid erations are taken...

Страница 4: ...CMK0014 Condensate Kit AVPTC25B14 AVPTC29B14 AVPTC31C14 AVPTC49D14 AVPTC33C14 AVPTC49C14 AVPTC37B14 AVPTC37C14 AVPTC61D14 AVPTC39C14 AVPTC37D14 AVPTC59C14 AVPTC59D14 CONDENSATE KIT TABLE 1 6 3 Downflo...

Страница 5: ...follow the specification for the condenser heat pump 7 2 Tubing Preparation All cut ends are to be round burr free and clean Failure to follow this practice increases the chances for refrigerant leak...

Страница 6: ...so will result in improper condensate drainage COIL INSTALLATION FOR DOWNFLOW Figure 8 Upper Tie Plate Control Deck Downflow Bracket Center Support Filter Bracket Filter Access Panel ACCESS PANEL CONF...

Страница 7: ...e liquid line at the liquid line service valve and 4 6 from the compressor on the suction line Ensure the thermometer makes adequate contact and is insulated for best possible readings Use liquid line...

Страница 8: ...above a finished living space to prevent sweating Install a condensate trap to ensure proper drainage NOTE When units are installed above ceilings or in other locationswheredamagefromcondensateoverfl...

Страница 9: ...on the ONLY heat kits that are permitted to be used are the HKS series Refer to the air handler unit s Serial and Rating plate or the HKS specification sheets to determine the heat kits compatible wit...

Страница 10: ...ll after 20 minutes the system would allow for an additional 20 heat pump run 20 of the 20 minute target is an additional 4 minutes In this case the system would turn on back up electric heat after 24...

Страница 11: ...sconnect ALL power before servicing Multiple power sources may be present HIGH VOLTAGE To avoid property damage personal injury or death due to electrical shock this unit MUST have an electrical groun...

Страница 12: ...the female connections on the casing down If the motor is not oriented with the connections down water could collect in the motor and may cause premature failure FEMALE CONNECTIONS SIDE VIEW WARN ING...

Страница 13: ...outdoor control board power Two stage outdoor units may not behave properly without this 24 VAC transformer Figure 15 3 Download the Cool Cloud HVAC phone application for charging and to configure te...

Страница 14: ...stage Heat Pumps 4 Go to the Tonnage Units Menu and select the ton nage value that corresponds to the desired airflow for the outdoor unit See the following table NOTE For the two stage non communicat...

Страница 15: ...on 19 Auxiliary Alarm Switch The control is equipped with a 24VAC Aux Alarm to be used for a condensate switch install designated by CON DENSATE IN OUT on the control By default the connected AUX swit...

Страница 16: ...nce and increase comfort level Select the desired ramping profile using the Cool Cloud phone application or the push button menus Figure 22 23 Electric Air Cleaner Warning The control is equipped with...

Страница 17: ...rom any areas where there may be objectionable odors flammable vapors or products of combustion such ascarbon monoxide CO which may cause serious personal injury or death 25 Regular Maintenance HIGH V...

Страница 18: ...e or disconnected wiring connection at circulator motor power leads Open circuit in inductor or loose wiring connection at inductor 3 4 Hp and 1 Hp models only Failed circulator blower motor Tighten o...

Страница 19: ...otor if necessary No Air Handler operation Circulator blower motor shuts down for over or under voltage condition Circulator blower motor shuts down due to over temperature condition on power module H...

Страница 20: ...stage heat pumps Indoor Airflow for non communicating outdoor units values based on 400CFM per ton default 3 0 Ton Cooling Airflow Trim default 0 Cooling Airflow Profile setting default profile D sho...

Страница 21: ...ing the next heat call if the heat pump fails to satisfy the custom target time for this number of consecutive cycles default 20 cycles Menu is enabled if the menu is set to 6 if the addition of low s...

Страница 22: ...comm units Compressor Heat Low Stage Comm Units Compressor Heat High Stage Comm Units Electric Heat Single Stage Electric Heat Low Stage Electric Heat High Stage Defrost Single Stage Electric Heat non...

Страница 23: ...avigation and Selection Instructions Using Phone Application over Bluetooth Network 1 Connect to the air handler instructions provided by phone during connection process 2 Select desired settings menu...

Страница 24: ...24 29 Wiring Diagrams HIGH VOLTAGE DISCONNECT ALL POWER BEFORE SERVICING MULTIPLE POWER SOURCES MAY BE PRESENT FAILURE TO DO SO MAY CAUSE PROPERTY DAMAGE PERSONAL INJURY OR DEATH WARNING...

Страница 25: ...ng diagram on the unit for the most up to date wiring HIGH VOLTAGE DISCONNECT ALL POWER BEFORE SERVICING MULTIPLE POWER SOURCES MAY BE PRESENT FAILURE TO DO SO MAY CAUSE PROPERTY DAMAGE PERSONAL INJUR...

Страница 26: ...maintained filter will keep the indoor coil of your comfort system clean A dirty coil could cause poor operation and or severe equipment damage Your air filter or filters could be located in your fur...

Страница 27: ...27 THIS PAGE WAS LEFT BLANK INTENTIONALLY...

Страница 28: ...u purchased to be directed to the feedback page PRODUCT REGISTRATION Thank you for your recent purchase Though not required to get the protection of the standard warranty registering your product is a...

Отзывы: