information, review active diagnostic error codes, observe system 

menu testing of all operational modes (heat / cool / fan)  directly 

from the phone. The phone application is also capable of directly 

updating the air handler software anytime updates are available. 

The application will automatically notify the user. 
NOTE: The software update may take up to 20 minutes to complete. 

16  Quick Start Guide for Communicating Outdoor Units

EXTREMELY IMPORTANT: For all cooling calls the system only re

-

quires a single Y input from the thermostat. For all heating calls 

(including applications with backup electric heater kits) the system 

only requires a single W input from the thermostat. Internal algo

-

rithms will control all available cooling and heating stages based 

on these inputs. Any single-stage 24VAC thermostat can be used. 

For proper operation, the thermostat must be setup to control a 

single stage AC outdoor unit and to control single stage electric 

heat operation. The control board does not accommodate an O 

wire thermostat input (reversing valve signal). If a heat pump is 

installed, the thermostat should be setup as stated above. Setting 

the thermostat for the heat pump control or multistage control 

may result in incorrect performance. 

1.  Connect all necessary thermostat wires to the thermostat 

connector on the air handler control as instructed by the 

applicable wiring diagrams shown in this section. 

2.  Connect the 1 & 2 wires between the indoor and outdoor 

unit for communicating operation. 

 

Note: Verify two stage outdoor units include a 24VAC 

transformer (for outdoor control board power). Two stage 

outdoor units may not behave properly without this 24 VAC 

transformer.  

 

Figure 15 

3.  Download the Cool Cloud HVAC phone application for 

charging and to configure /test system.

NOTE: When new versions of Bluetooth Communication Software 

and Air Handler Control Software are available, the phone appli

-

cation notifies the user. Software updates are classified as either 

optional or mandatory and installed by using the phone application. 

Ensure all mandatory software updates and install if necessary. 

16.1 Charging

1.  Two-stage outdoor units using the Cool Cloud HVAC appli

-

cation: 

a. Using the cooling icon after entering the outdoor 

unit menus, energize the outdoor unit at 49% 

capacity or lower.  

b. Charge the outdoor unit as required using the 

charging information provided with the outdoor 

equipment.

17  Quick Start Guide for Non-Communicating Outdoor 

Units

When setting up a ComfortBridge air handler for use with a 

Non-Communicating outdoor unit you must set airflow in the 

“ton” menu on the PCB or in the CoolCLoud HVAC APP.  Failure 

to do so will result in the air handler PCB displaying “IdL” and the 

blower will not operate with a call for cooling.   The Board does 

not need to be replaced, you MUST set the airflow first.

EXTREMELY IMPORTANT: For two stage electric heat kit control 

the system only needs a single W input. Internal algorithms will 

control staging automatically based on the single W input. For 

non-communicating outdoor unit wiring, see instructions below:

  1. Use  the wiring diagrams on the next page to connect low 

voltage thermostat wires. 

 

NOTE: When installing the air handler with a non-com

-

municating heat pump, wire directly to the “O” terminal 

on the non-communicating heat pump. See the following 

figures.  

Figure 16

Содержание Amana AVPTC 14 Series

Страница 1: ...nt The manufac turer will not be responsible for any injury or property dam age arising from improper service or servide procedures If you service this unit you assume responsibility for any injury or...

Страница 2: ...ards Institute ANSI National Fire Protection Association NFPA 70 and local state codes In Canada electrical grounding is to be in accordance with the Canadian Electric Code CSA C22 1 uninterrupted unb...

Страница 3: ...this document with the unit Carefully read all instruc tions for the installation prior to installing product Make sure each step or procedure is understood and any special consid erations are taken...

Страница 4: ...CMK0014 Condensate Kit AVPTC25B14 AVPTC29B14 AVPTC31C14 AVPTC49D14 AVPTC33C14 AVPTC49C14 AVPTC37B14 AVPTC37C14 AVPTC61D14 AVPTC39C14 AVPTC37D14 AVPTC59C14 AVPTC59D14 CONDENSATE KIT TABLE 1 6 3 Downflo...

Страница 5: ...follow the specification for the condenser heat pump 7 2 Tubing Preparation All cut ends are to be round burr free and clean Failure to follow this practice increases the chances for refrigerant leak...

Страница 6: ...so will result in improper condensate drainage COIL INSTALLATION FOR DOWNFLOW Figure 8 Upper Tie Plate Control Deck Downflow Bracket Center Support Filter Bracket Filter Access Panel ACCESS PANEL CONF...

Страница 7: ...e liquid line at the liquid line service valve and 4 6 from the compressor on the suction line Ensure the thermometer makes adequate contact and is insulated for best possible readings Use liquid line...

Страница 8: ...above a finished living space to prevent sweating Install a condensate trap to ensure proper drainage NOTE When units are installed above ceilings or in other locationswheredamagefromcondensateoverfl...

Страница 9: ...on the ONLY heat kits that are permitted to be used are the HKS series Refer to the air handler unit s Serial and Rating plate or the HKS specification sheets to determine the heat kits compatible wit...

Страница 10: ...ll after 20 minutes the system would allow for an additional 20 heat pump run 20 of the 20 minute target is an additional 4 minutes In this case the system would turn on back up electric heat after 24...

Страница 11: ...sconnect ALL power before servicing Multiple power sources may be present HIGH VOLTAGE To avoid property damage personal injury or death due to electrical shock this unit MUST have an electrical groun...

Страница 12: ...the female connections on the casing down If the motor is not oriented with the connections down water could collect in the motor and may cause premature failure FEMALE CONNECTIONS SIDE VIEW WARN ING...

Страница 13: ...outdoor control board power Two stage outdoor units may not behave properly without this 24 VAC transformer Figure 15 3 Download the Cool Cloud HVAC phone application for charging and to configure te...

Страница 14: ...stage Heat Pumps 4 Go to the Tonnage Units Menu and select the ton nage value that corresponds to the desired airflow for the outdoor unit See the following table NOTE For the two stage non communicat...

Страница 15: ...on 19 Auxiliary Alarm Switch The control is equipped with a 24VAC Aux Alarm to be used for a condensate switch install designated by CON DENSATE IN OUT on the control By default the connected AUX swit...

Страница 16: ...nce and increase comfort level Select the desired ramping profile using the Cool Cloud phone application or the push button menus Figure 22 23 Electric Air Cleaner Warning The control is equipped with...

Страница 17: ...rom any areas where there may be objectionable odors flammable vapors or products of combustion such ascarbon monoxide CO which may cause serious personal injury or death 25 Regular Maintenance HIGH V...

Страница 18: ...e or disconnected wiring connection at circulator motor power leads Open circuit in inductor or loose wiring connection at inductor 3 4 Hp and 1 Hp models only Failed circulator blower motor Tighten o...

Страница 19: ...otor if necessary No Air Handler operation Circulator blower motor shuts down for over or under voltage condition Circulator blower motor shuts down due to over temperature condition on power module H...

Страница 20: ...stage heat pumps Indoor Airflow for non communicating outdoor units values based on 400CFM per ton default 3 0 Ton Cooling Airflow Trim default 0 Cooling Airflow Profile setting default profile D sho...

Страница 21: ...ing the next heat call if the heat pump fails to satisfy the custom target time for this number of consecutive cycles default 20 cycles Menu is enabled if the menu is set to 6 if the addition of low s...

Страница 22: ...comm units Compressor Heat Low Stage Comm Units Compressor Heat High Stage Comm Units Electric Heat Single Stage Electric Heat Low Stage Electric Heat High Stage Defrost Single Stage Electric Heat non...

Страница 23: ...avigation and Selection Instructions Using Phone Application over Bluetooth Network 1 Connect to the air handler instructions provided by phone during connection process 2 Select desired settings menu...

Страница 24: ...24 29 Wiring Diagrams HIGH VOLTAGE DISCONNECT ALL POWER BEFORE SERVICING MULTIPLE POWER SOURCES MAY BE PRESENT FAILURE TO DO SO MAY CAUSE PROPERTY DAMAGE PERSONAL INJURY OR DEATH WARNING...

Страница 25: ...ng diagram on the unit for the most up to date wiring HIGH VOLTAGE DISCONNECT ALL POWER BEFORE SERVICING MULTIPLE POWER SOURCES MAY BE PRESENT FAILURE TO DO SO MAY CAUSE PROPERTY DAMAGE PERSONAL INJUR...

Страница 26: ...maintained filter will keep the indoor coil of your comfort system clean A dirty coil could cause poor operation and or severe equipment damage Your air filter or filters could be located in your fur...

Страница 27: ...27 THIS PAGE WAS LEFT BLANK INTENTIONALLY...

Страница 28: ...u purchased to be directed to the feedback page PRODUCT REGISTRATION Thank you for your recent purchase Though not required to get the protection of the standard warranty registering your product is a...

Отзывы: