Maytag Amana APCH32441 Скачать руководство пользователя страница 6

6

weatherproof flexible connectors on both supply and return 

connections at the unit to reduce noise transmission is 

recommended.

It is preferable to install the unit on the roof of the structure 

if the registers or diffusers are located in the wall or ceiling. 

A slab installation is recommended when the registers are 

low on the wall or in the floor.

Connecting the Return and Supply Flexible Duct in 

Manufactured or Modular Housing Application

The return and supply fittings are to be attached at 

the unit to a suitable square to round duct converter. 

Your distributor has a factory designed square to round 

converter transition. The model #’s of these kits are 

as follows: Small Chassis 27.5” SQRPCH102, Large 

and Extra Large Chassis 32.5:” and 36” SQRPCH103 

(See Specification Sheets for Dimension details). The 

SQRPCH101 has 14” duct collar on supply and 16” duct 

collar (equivalent diameter, opening is oval) on the return. 

The SQRPCH102 and SQRPCH103 have 14” duct collar 

on supply and 18” duct collar (equivalent diameter, opening 

is oval) on the return. The collars are to be slipped into the 

openings, and the flanges bent around the converter. The 

square to round converter is attached to the flanges of the 

square duct openings. The flexible duct is then clamped on 

to the collars. Once the duct is affixed to the unit, 

seal the 

collars and flanges with a proper waterproof sealant

 

(See Figure 4).

OUTER FLANGE

STARTER FLANGE

SQUARE TO ROUND

DUCT CONVERTER PANEL

Figure 4

It is strongly encouraged to use appropriately sized ducts 

based upon the CFM for your application (unit’s CFM). If 

duct sizing through industry manuals or air duct calculators 

require larger ducts than converter openings, run larger 

duct size up to unit converter openings and reduce with a 

reducer duct fitting or transition right at the unit.

Plenum Application

A suitable plenum or square duct must be constructed. The 

duct cross-sectional area should be determined by industry 

duct sizing manuals or air duct calculators.

On ductwork exposed to outside air conditions of 

temperature and humidity, use an insulation with a good 

K factor, and a vapor barrier. Industry practices should be 

followed. Balancing dampers are recommended for each 

branch duct in the supply system. Ductwork should be 

properly supported from the unit.

NOTE: Proper sealing of all duct work and air 

handling compartments is extremely important to 

overall unit efficiency.

Filters

Filters are not provided with unit, and must be supplied 

and installed in the return duct system by the installer. 

A field installed filter grille is recommended for easy and 

convenient access to the filters for periodic inspection 

and cleaning. Filters must have adequate face area 

for the rated quantity of the unit. See table below for 

recommended filter size. 

Unit

2 Ton

2 1/2 Ton

3 Ton

3 1/2 4 Ton

5 Ton

Min. Filter 

Size

(1)20 x 20 x 1 (1)20 x 25 x 1 (1)25 x 25 x 1 (2)20 x 20 x 1 2(20) x 25 x1

Recommended filter sizes

Table 1

PIPING

Condensate Drain

The condensate drain connection of the evaporator is a 

half coupling of ¾” N.P.T.  A trap must be provided to have 

Proper condensate drainage.

2" Minimum

3" Minimum

A Positive Liquid Seal

Is Required

Flexible

Tubing-Hose

Or Pipe

Drain

Connection

Unit

Figure 5

Install condensate drain trap as shown. Use ¾” drain 

connection size or larger. Do not operate without trap. Unit 

must be level or slightly inclined toward drain.

ELECTRICAL WIRING

CAUTION

To avoid property damage or personal injury due to fire, use 

only copper conductors.

All wiring should be made in accordance with the National 

Electrical Code. The local Power Company should 

be consulted to determine the availability of sufficient 

power to operate the unit. The voltage, frequency, and 

phase at the power supply should be checked to make 

sure it corresponds to the unit’s RATED VOLTAGE 

REQUIREMENT.

Содержание Amana APCH32441

Страница 1: ...or repair the equipment specified in this manual without proper training may result in product damage property damage personal injury or death WARNING RECOGNIZE THIS SYMBOL AS A SAFETY PRECAUTION All...

Страница 2: ...y look the location over both the inside and outside of home Note any potential obstacles or problems that might be encountered as noted in this manual Choose a more suitable location if necessary IMP...

Страница 3: ...inal tons of cooling Optional field installed heat kits are available in 5 8 10 15 and 20 KW The units can be easily installed in manufactured or modular homes with existing high static duct work The...

Страница 4: ...letely unobstructed If units are to be located under an overhang there should be a minimum of 48 clearance and provisions made to deflect the warm discharge air out from the overhang Location Consider...

Страница 5: ...ver the unit to prevent damage to the cabinet by the lift cables Spreader bars must be of sufficient length so that cables do not come in contact with the unit during transport Remove wood struts moun...

Страница 6: ...lenum Application A suitable plenum or square duct must be constructed The duct cross sectional area should be determined by industry duct sizing manuals or air duct calculators On ductwork exposed to...

Страница 7: ...NFPA NO 70 1984 or latest edition by using ground lug in the control box DO NOT EXCEED THE MAXIMUM OVERCURRENT DEVICE SIZE SHOWN ON UNIT DATA PLATE Fuses or HACR type circuit breakers may be used wher...

Страница 8: ...er when servicing the unit WARNING HIGH VOLTAGE Disconnect all power before servicing or in stalling this unit Multiple power sources may be present Failure to do so may cause proper ty damage persona...

Страница 9: ...upplemental heat Normally a Defrost cycle will take only 2 3 minutes unless system is low on charge or outdoor conditions are severe windy and cold The defrost control also provides for a 3 minute off...

Страница 10: ...e heating requirement should there be a component failure of the heat pump such as a compressor or refrigerant leak etc Since the temperature of the liquid refrigerant in the outdoor coil on the heati...

Страница 11: ...ple type temperature test lead on the tube adjacent to the defrost control Insulate the lead point of contact 2 Check the temperature at which the control closes its contacts by lowering the temperatu...

Страница 12: ...or with a electronic control board ECM Motor The ECM motor provides many features not available on the traditional PSC motor These features include Improved Efficiency Constant CFM Soft Start and Stop...

Страница 13: ...ltage power wire typically the black lead to the thermostat R Red wire in control box 5 Secure the dehumidistat ground wire typically the green lead to the ground screw to the unit s sheet metal contr...

Страница 14: ...running on low stage with TXV application should have a subcooling and superheat within the range listed on the chart a If subcooling and superheat are low adjust TXV superheat then check subcooling N...

Страница 15: ...to easily install the HKR HKP Series Electric Heat Kit Full Installation Instructions are included in this kit Please use this document for guidance in field equipping the package unit with electric h...

Страница 16: ...Do not allow air entering the indoor coil to drop below 65 F Air below this temperature will cause low discharge pressure thus low suction pressure and excessive defrost cycling resulting in low heati...

Страница 17: ...88 1022 989 Watts 179 190 203 210 225 243 249 268 CFM 1758 1715 1674 1637 1596 1557 1518 1474 Watts 394 406 418 430 443 455 466 474 CFM 2002 1935 1885 1827 1767 1732 1669 1618 Watts 498 521 516 534 55...

Страница 18: ...gs for Single Two Stage Thermostat Speed Tap Switch 5 Switch 6 A OFF OFF B ON OFF C OFF ON D ON ON Cooling HP DIP Switch Settings CFM Switch 7 Switch 8 Plus 10 ON OFF Normal OFF OFF Minus 10 OFF ON Sp...

Страница 19: ...81 294 305 318 330 CFM 1736 1679 1638 1598 1558 1520 1484 1441 Watts 356 372 382 395 408 422 433 442 CFM 1337 1297 1218 1155 1118 1088 1022 989 Watts 179 190 203 210 225 243 249 268 CFM 1758 1715 1674...

Страница 20: ...t be within 10 of nameplate volts when unit is operating d Capacitor weak open or shorted d Check capacitor If defective replace Low suction cool compressor a a Iced evaporator coil a Defective overlo...

Страница 21: ...A B PCH32441 66 34 27 30 Small PCH33041 66 34 27 30 Small PCH33641 66 34 27 30 Small PCH34241 66 34 32 35 Medium PCH34841 66 34 32 35 Medium PCH36041 66 34 32 35 Medium Model Duct Openings Supply Ret...

Страница 22: ...A B PHH32441 66 34 27 30 Small PHH33041 66 34 27 30 Small PHH33641 66 34 32 35 Medium PHH34241 66 34 32 35 Medium PHH34841 66 34 32 35 Medium PHH36041 66 34 36 38 Large Model Duct Openings Supply Ret...

Страница 23: ...minum Indoor Coil Cleaning Qualified Servicer Only This unit is equipped with an aluminum tube evaporator coil The safest way to clean the evaporator coil is to simply flush the coil with water This c...

Страница 24: ...Type NG Natural Gas LP Liquid Propane Residential Package Outdoor Section ELECTRICAL Supply Voltage Measure L1 and L2 Voltage L1 L2 Compressor Amps Condenser Fan Amps PRESSURES TEMPERATURES Suction Ci...

Страница 25: ...25 THIS PAGE IS LEFT INTENTIONALLY BLANK...

Страница 26: ...26 THIS PAGE IS LEFT INTENTIONALLY BLANK...

Страница 27: ...27 THIS PAGE IS LEFT INTENTIONALLY BLANK...

Страница 28: ...o the feedback page GOODMAN BRAND AMANA BRAND GOODMAN BRAND AMANA BRAND PRODUCT REGISTRATION Thank you for your recent purchase Though not required to get the protection of the standard warranty regis...

Отзывы: