TROUBLESHOOTING
73
Push Button Menu Options
Name/Cloud/Phone App
7 Segment Display
User Modifiable Options
Comments
Cool Trim Factor
-10%, -8%,-6%, -4%, -2%, 0%, 2%, 4%, 6%, 8%,10% Trims the cooling airflow by the selected amount.
Cool Airflow Profile
A, B, C, D
Select cooling airflow profiles.
Cool On Delay
d
5, 10, 20, 30
Selects the cooling on delay.
Cool Off Delay
d
30, 60, 90, 120
Selects the cooling off delay.
Dehumidifcation Enable
d
ON, OFF
Enables the dehum function for OD operation.
Defrost Gas Heat Stage
d
1 or 2
Selects the gas heat stage for defrost operation.
Compressor Balance Points
Adjustable and defined in Shared Data
Selects the compressor balance point options for HP operation.
HP Trim Factor
-10%, -8%,-6%, -4%, -2%, 0%, 2%, 4%, 6%, 8%,10% Trims the heating airflow by the selcted amount
HP On Delay
d
5, 10, 15
Selects the HP heating on delay.
HP Off Delay
d
30, 50, 70, 90
Selects the HP heating off delay.
HP Defrost Interval
dI
30, 60, 90, 120
Provides the defrost options for compressor heating operation.
Compressor Delay
dL
0, 5, 15, 30
Provides the compressor delay options for heating operation.
History Fault and Clear
L
Yes or No.
Views the comm outdoor history and clear the outdoor unit
history fault.
Name/Cloud/Phone App
7 Segment Display
User Modifiable Options
Comments
Boost Mode
On or Off
Provides the options for inverter boot operation.
Boost Temp
On(Always), 70F, 75F, 80F, 85F, 90F, 95F, 100F, 105F Provides the 9 temperature options for boot operation.
Set Max Current
OFF, 40%, 50%, 60%, 70%, 80%, 90%
Selects Max Current options
Vertical Rise
SL (Same Level), OL (Outdoor Lower), IL (Indoor
Lower)
Selects the level of outdoor vas indoor equipment.
System Reset Menu
Yes or No.
Reset all outdoor unit settings to factory default.
System Verification Test
On or Off
Runs System Verification Test after Installation.
Pump Down
d
On or Off
Enters Pump Down mode.
Charge Mode
On or Off
Enters charge mode.
Cool-Trim Factor - High
-15, -12, -9, -6, -3, 0, 3, 6, 9, 12, 15
Trims the cooling airflow by the selected amount.
Cool-Trim Factor - Intermediate
I
-15, -12, -9, -6, -3, 0, 3, 6, 9, 12, 15
Trims the cooling airflow by the selected amount.
Cool-Trim Factor - Low
L
-15, -12, -9, -6, -3, 0, 3, 6, 9, 12, 15
Trims the cooling airflow by the selected amount.
Cool Airflow Profile
A, B, C, D
Select cooling airflow profiles.
Cool On Delay
d
5, 10, 20, 30
Selects the cooling on delay.
Cool Off Delay
d
30, 60, 90, 120
Selects the cooling off delay.
Dehum Enable
d
On or Off
Enables the dehum function for compressor operation.
Cool Reset Menu
L
Yes or No.
Resets all cooling settings to factory default.
Cool Max RPS Range
01(58 to 62.5 RPS), 02(63 to 67.5 RPS), 03(68RPS),
04(68.5 to 73 RPS), 05(73.5 to 78 RPS)
Selects the appropriate range for the installed system
configuration.
Cool Max RPS Selection
10 RPS values from inverter
Selects the appropriate compressor RPS for the installed system
configuration.
Defrost Gas Heat Stage
d
1 or 2
Selects the gas heat stage for defrost operation.
Compressor Balance Points
Adjustable and defined in Shared Data
Provides the compressor balance point options for HP operation.
Force Defrost
dd
On or Off
HP Trim Factor - High
-15, -12, -9, -6, -3, 0, 3, 6, 9, 12, 15
Trims the heating airflow by the selected amount.
HP Trim Factor - Intermediate
I
-15, -12, -9, -6, -3, 0, 3, 6, 9, 12, 15
Trims the heating airflow by the selected amount.
HP Trim Factor - Low
L
-15, -12, -9, -6, -3, 0, 3, 6, 9, 12, 15
Trims the heating airflow by the selected amount.
HP On Delay
d
5, 10, 20, 30
Selects the HP heating on delay.
HP Off Delay
d
30, 60, 90, 120
Selects the HP heating on delay.
HP Defrost Interval
dI
Maximum amount of compressor runtime before
defrost occurs.
Provides the defrost options for compressor heating operation.
HP Reset Menu
Yes or No.
Resets all heating settings to factory default.
HP Max RPS Range
01(58 to 62.5 RPS), 02(63 to 67.5 RPS), 03(68RPS),
04(68.5 to 73 RPS), 05(73.5 to 78 RPS)
Selects the appropriate range for the installed system
configuration.
HP Max RPS Selection
10 RPS values from inverter
Selects the appropriate compressor RPS for the installed system
configuration.
History Fault and Clear
L
Yes or No.
Views the comm outdoor history and clear the outdoor unit
history fault.
ClimateTalk Comm Outdoor 2-Stage AC/HP
ClimateTalk Comm Outdoor Inverter AC/HP