Operating Instructions SG-EFS 1X4 ZK2/1 8k2 

Page 13/15

Polymer Electric

Troubleshooting and remedies

Prerequisite: the Control Unit is connected to the supply voltage and sensor. No 
sensor is activated.

Fault display

Possible cause

Remedy

yellow LEDs “K1 ON“ 
and “K2 ON“ are out

No or incorrect supply voltage

1.  Check supply voltage, compare with 

type plate

2.  Check terminal connections

Incorrect monitoring resistor on sensor

 

Ä

Connect sensor with monitoring  
resistor 8k2

If monitoring resistor is correct: sensor is 
faulty

 

Ä

Replace sensor

No sensor connected

 

Ä

Connect sensor

Sensor incorrectly connected

 

Ä

Check terminal connections

Cable break

 

Ä

Replace sensor

Manual reset: reset switch not actuated

 

Ä

Actuate reset switch

Manual reset: reset switch sticks

 

Ä

Replace switches on terminals 5 and 6

Automatic reset: bridge missing

 

Ä

Connect bridge between terminals 7 
and 8

Control Unit is faulty

 

Ä

Replace Control Unit

Only one LED is on

Incorrect supply voltage

 

Ä

Check supply voltage, compare with 
type plate

Control Unit is faulty

 

Ä

Replace Control Unit

Fault can still not be detected?

 

Ä

Contact Mayser-Support: Tel. +49 731 2061-0.

Disposal

The devices produced by Mayser are professional electronic tools exclusively in-
tended for commercial use (so-called B2B devices). Unlike devices mainly used in 
private households (B2C), they may not be disposed of at the collection centres of 
public sector disposal organisations (e.g. municipal recycling depots). At the end of 
their useful life, the devices may be returned to us for disposal.
WEEE reg. no. DE 39141253 

Replacement parts

Overall safety endangered

If the sensor and Control Unit are not replaced with original parts from Mayser, 
operation of the protective device may be impaired.

 

Ä

Only use original parts from Mayser.

CAUTION

Содержание 1003100

Страница 1: ...89073 Ulm GERMANY Tel 49 731 2061 0 Fax 49 731 2061 222 E Mail info ulm mayser com Internet www mayser com Control Unit SG EFS 1X4 ZK2 1 8k2 1003100 SG EFS 104 ZK2 1 8k2 24 V 7500354 SG EFS 134 ZK2 1...

Страница 2: ...4 Parts supplied 5 Transport and storage 6 Packaging and transport 6 Storage 6 Product overview 6 Connections 6 LEDs information 6 Function installation and commissioning 7 Function 7 Installation 7...

Страница 3: ...n to every subsequent owner or user of the prod uct Add any supplement received from the manufacturer to the operating instruc tions In addition to the operating instructions observe the following doc...

Страница 4: ...r 8k2 The integrated output signal switching device OSSD transmits the evaluated safety signals directly to the downstream control Safety instructions Maintain distance When installing in the switch c...

Страница 5: ...ct relay contacts Risk of welding Protect the relay contacts externally Do not overload Control Unit Ensure that the specified switching current is not exceeded Observe pin assignment Observe pin assi...

Страница 6: ...LED K1 ON Sensor not activated yellow LED K2 ON Sensor not activated Storage Store the Control Units in the original packaging in a dry place Observe the storage temperatures given in the technical sp...

Страница 7: ...and K2 are de energised The yellow LEDs K1 ON and K2 ON go out the switching channels 1 and 2 are open and the sig nal circuit is closed The signal circuit works opposed to the switch channels 1 and...

Страница 8: ...ered The quality and reliability of the interface between the protective device and the machine influences the overall safety Install the interface very carefully CAUTION 2 Wire the sensors switching...

Страница 9: ...nnels 1 and 2 open signal circuit closed Manual reset For manual reset with reset a switch must be connected between cable terminals 5 and 6 The control unit reacts when the switch changes from not ac...

Страница 10: ...eat steps 1 and 2 5 Disconnect the sensor yellow LEDs K1 ON and K2 ON go off contacts of switching channels 1 and 2 open signal circuit closed Test function manual reset Recommissioning Check for prop...

Страница 11: ...ymer Electric Switching channel 2 Switching channel 1 Switching channel 2 Switching channel 1 Switching channel 2 Switching channel 1 Connection examples Contacts continued in two channel mode Contact...

Страница 12: ...onthly Cleaning Clean the outside of the enclosure with a dry cloth Danger of injury due to electrocution Disconnect the Control Unit as well as all devices and live parts in the im mediate environmen...

Страница 13: ...rminals 5 and 6 Automatic reset bridge missing Connect bridge between terminals 7 and 8 Control Unit is faulty Replace Control Unit Only one LED is on Incorrect supply voltage Check supply voltage com...

Страница 14: ...ep distance and air gap with without Category 3 PL e 313 years 4 29 10 8 1 h 90 2 106 52560 per year Requirements fulfilled soiling degree 2 overvoltage category II 230 V basic insulation with without...

Страница 15: ...Contact fuse protection external 13 14 23 24 AC 12 250 V 2 A DC 12 24 V 2 A AC 250 V DC 24 V 2 A 2 A 10 mA 10 mA 500 VA 48 W 5 107 3 105 AC 250 V 2 A 2 A quick acting 31 32 AC 42 V DC 42 V 100 mA 100...

Отзывы: