August 20, 2012
eMAX-MR51e-Man Rev B
10 of 17
9.
Status LEDs:
At power up, LEDs 2 through 6 are turned ON then OFF in sequence.
After the above sequence has completed successfully, the eMAX-
MR51e goes to the “waiting for IP address”
mode:
LED
DESCRIPTION
1
Off-line: .2 second ON, .8 second OFF
2
Waiting for IP address: .5 second ON, .5 second OFF
3
Flashes when data is received from either reader
4
Input IN1 Status: OFF = Inactive, ON = Active, Flashing = Trouble
5
Input IN2 Status: OFF = Inactive, ON = Active, Flashing = Trouble
6
Input IN3 Status: OFF = Inactive, ON = Active, Flashing = Trouble
Note: There is no LED for IN4.
After the eMAX-MR51e has received its IP address, the following table describes the LEDs in the normal running
mode. If the communication is lost, the eMAX-
MR51e reverts back to the “waiting for IP address” mode:
LED
DESCRIPTION
1
On-line, encryption disabled = .8 second ON, .2 second OFF
On-line, encryption enabled = four pulses, .1 second ON, .1 second OFF per
second
2
Flashes when there is host communication
3
Flashes when data is received from either reader
4
Input IN1 Status: OFF = Inactive, ON = Active, Flashing = Trouble
5
Input IN2 Status: OFF = Inactive, ON = Active, Flashing = Trouble
6
Input IN3 Status: OFF = Inactive, ON = Active, Flashing = Trouble
Note: There is no LED for IN4.
10.
Configuring the eMAX-MR51e
The eMAX-MR51e is an IP Network connected device. Therefore, when adding the eMAX-MR51e to the
eAxxess or eFusion Access System, the hardware (MAC) address and the IP address will be required for the
device. The MAC address must be entered using a colon ( : ) as a separator between digits, not a dash ( - ).
{ i.e. 11:22:33:44:55:66 }
The device panel address may be 0
–
31.
It is recommended that the IP address be within the same subnet as the eMAX-EP controller that this eMAX-
MR51e is assigned to. The eMAX-MR51e must be no more than one hop from its eMAX-EP controller.