12.  Status LEDs: 

Power-up: 

All LED's 

OFF

Initialization: 

After power is applied or reset switch pushed, LED 1 is ON for about 15 seconds, then 

LED’s 2, 3, 4, 5, 6, 

R1, R2, IN1, IN2, IN3, IN4, IN5, IN6, IN7 and IN8 are flashed once at the beginning 

of initialization.  LEDs 3 and 4 is turned ON for approximately 1 second after the hardware initialization 
has completed, then the application code is initialized.  The amount of time the application takes to 
initialize depends on the size of the database, about 1 second without a card database.  Each 10,000 
cards will add about 2 seconds to the application initialization.  When LED's 1, 2, 3 and 4 flash at the 
same time, data is being read from or written to flash memory, do not cycle power when in this state. 

 

If the sequence stops or repeats, perform the bulk erase procedure, see section 4

.

 

Running: 

After initialization is complete, the LEDs have the following meanings: 

LED 

DESCRIPTION 

Off-Line / On-Line and Battery Status 

  

Off-Line = 20% ON, On-Line = 80% ON 

  

Double Flash if Battery is Low 

Host Communication Activity (Ethernet or Micro USB port) 

Internal SIO Communication Activity 

External SIO Communication Activity 

Unassigned 

R1 

Reader 1:  

Clock/Data or D1/D0 Mode:  Flashes when Data is Received, Either Input 

F/2F Mode:  Flashes when Data/Acknowledgment is Received 

RS-485 Mode:  Flashes when Transmitting Data 

R2 

Reader 2:  

Clock/Data or D1/D0 Mode:  Flashes when Data is Received, Either Input 

F/2F Mode:  Flashes when Data/Acknowledgment is Received 

RS-485 Mode = Flashes when Transmitting Data 

D16 

Flashes with Ethernet Traffic 

YEL 

Ethernet Speed: OFF = 10Mb/S, ON = 100Mb/S 

GRN 

OFF = No Link, ON = Good Link, Flashing = Ethernet Activity 

IN1 

Input IN1 Status: OFF = Inactive, ON = Active, Flash = Fault.  See Note 3. 

IN2 

Input IN2 Status: OFF = Inactive, ON = Active, Flash = Fault.  See Note 3. 

IN3 

Input IN3 Status: OFF = Inactive, ON = Active, Flash = Fault.  See Note 3. 

IN4 

Input IN4 Status: OFF = Inactive, ON = Active, Flash = Fault.  See Note 3. 

IN5 

Input IN5 Status: OFF = Inactive, ON = Active, Flash = Fault.  See Note 3. 

IN6 

Input IN6 Status: OFF = Inactive, ON = Active, Flash = Fault.  See Note 3. 

IN7 

Input IN7 Status: OFF = Inactive, ON = Active, Flash = Fault.  See Note 3. 

IN8 

Input IN8 Status: OFF = Inactive, ON = Active, Flash = Fault.  See Note 3. 

K1 

Relay K1: ON = Energized 

K2 

Relay K2: ON = Energized 

K3 

Relay K3: ON = Energized 

K4 

Relay K4: ON = Energized 

 

Note

:  If this input is defined, every three seconds the LED is pulsed to its opposite state for 0.1 

seconds, otherwise, the LED is off. 

Содержание eMAX-LP1502

Страница 1: ...GENT CONTROLLER Installation Guide and Specifications This device complies with FCC Part 15 Class A Specifications The device meets CE Specifications and is RoHS Certified This device is UL 294 Recogn...

Страница 2: ...tion Memory 7 5 Input Power Cabinet Tamper UPS Fault Wiring 8 6 Communication Wiring 8 7 Reader Wiring 8 8 Input Circuit Wiring 10 9 Relay Circuit Wiring 11 10 Memory Backup Battery 11 11 IT Security...

Страница 3: ...Stripe Clock Data F 2F Protocol standard or supervised or 2 wire RS 485 device signaling such as OSDP and also provides tri state LED control and buzzer control one wire LED mode only Each Reader Port...

Страница 4: ...4 5 R1 R2 J8 TR TR GND IN1 IN2 TB3 TB4 TB5 TB6 IN3 IN4 IN5 IN6 IN7 IN8 TB7 K 1 K 2 K 3 K 4 J7 TB10 TB11 3V BR CR2330 RESET S2 BT1 50 12 70 2 00 50 80 3 00 76 20 2 00 50 80 50 12 70 8 00 203 20 5 50 13...

Страница 5: ...D1 Clock Data 1 TR B See note 1 TB3 3 TR A See note 1 TB9 4 BZR Reader Buzzer TB4 1 Input 2 IN2 TB9 5 LED Reader LED TB4 2 IN2 TB9 6 VO Reader Power TB4 3 Input 1 IN1 TB10 1 Out 1 NO Normally Open Co...

Страница 6: ...10 Base T 100Base Tx Ethernet Connection Port 0 J3 N A Factory Use Only J4 N A N A J5 OFF RS 485 EOL Terminator is Off ON RS 485 EOL Terminator is On J6 N A Micro USB Port 2 0 J7 Reader Power Select S...

Страница 7: ...communication address 0 Alternate Host Port Disabled Refer to online HELP in the Maxxess host software for important details on encryption NOTE See Appendix A for details on configuring the eMAX LP co...

Страница 8: ...ANT NOTE Install the termination jumper ONLY on the panel at each end of the RS 485 bus Failure to do so will compromise the proper operation of the communication channel 7 Reader Wiring Each Reader P...

Страница 9: ...GREEN LED 1 TB8 or TB9 1 VO LED BZR D1 CLK TR D0 DAT TR GND 12 Vdc D1 GROUND DO GREEN LED NORMALLY CLOSED CONTACT DOOR MONITOR SWITCH REQUEST TO EXIT SWITCH NORMALLY OPEN CONTACT 1K 1 1K 1 1K 1 1K 1...

Страница 10: ...wo resistors be added to the circuit to facilitate proper reporting The standard supervised circuit requires 1k ohm 1 resistors and should be located as close to the sensor as possible Custom end of l...

Страница 11: ...and the real time clock are backed up by a lithium battery when input power is removed This battery should be replaced annually If data in the static RAM is determined to be corrupt after power up al...

Страница 12: ...unication Activity 4 External SIO Communication Activity 5 Unassigned R1 Reader 1 Clock Data or D1 D0 Mode Flashes when Data is Received Either Input F 2F Mode Flashes when Data Acknowledgment is Rece...

Страница 13: ...ght unsupervised supervised standard EOL 1k 1k ohm 1 watt Two unsupervised dedicated for cabinet tamper and UPS fault monitoring Outputs Four relays Form C with dry contacts Normally open contact NO c...

Страница 14: ...nvironmental Temperature 55 to 85 C storage 0 to 70 C operating Humidity 5 to 95 RHNC Mechanical Dimension 8 in 203 2 mm W x 6 in 152 4 mm L x 1 in 25 mm H Weight 9 oz 255 g nominal board only UL294 6...

Страница 15: ...anties implied or otherwise and expressly excludes and disclaims all implied warranties of merchantability or fitness for a particular purpose Returned units are repaired or replaced from a stock of r...

Страница 16: ...___ _____ Gateway IP _____ ______ ______ _____ Connecting to the eMAX LP controller 1 Connect the device to a computer using a standard network cable 2 Set the computer s IP to a Statis IP Address of...

Страница 17: ...n will then appear Click on the Click Here to Login the following screens appears Login using username admin and password password The following message will appear if you FAILED to turn Switch 1 to O...

Страница 18: ...he controller will post a message suggesting a new user be added click OK When a new user is added it disables the default admin user It is strongly recommended that a new user account be added during...

Страница 19: ...k Default Gateway as applicable for the eMAX LP1502 If using Redundant host communication you will need to configure the Interface 2 NIC2 parameters To SAVE Click on Accept button then select the Appl...

Страница 20: ...at the Dip Switch settings must be reset to off The 2nd check box is telling you that no special User Accounts were defined If you wish to proceed check both of the check boxes then click on the Yes b...

Отзывы: