background image

Long Distance Combus Extensions

The length of Combus from a PC4204CX Combus Regenerator can
be  extended  beyond  1000ft  (305m),  providing  the  following
conditions are met:

• Combus must be regenerated and repowered at both ends of

the wire run using the PC4204CX.

• No other modules are to be connected along the long distance

wire run.

• A maximum distance of 4000ft (1220m) can be achieved between

two PC4204CX devices. To extend further, additional PC4204CX
devices should be used.

NOTE: The wiring used to connect this equipment must be insulated with
PVC, TFE, PTFE, FEP, neoprene or polymide.

When extending Combus long distances, use the following chart to
determine what gauge of wire is necessary:

Maximum Length

AWG

2000ft (600m)

22

3000ft (900m)

21

4000ft (1200m)

20

Line Loss

When current is drawn through a piece of wire, voltage will be lost
due to the wire’s resistance. This voltage loss must be considered
for all installations.
To ensure proper operation, at least 12.5V

DC

 must be applied to all

modules on the system (when AC is applied and the battery is fully
charged). If less than 12.5V

DC

 is applied, system operation will be

adversely affected.

To correct the problem, try any or all of the following:

1. Connect another PC4204CX power supply near the module to
provide power to the Combus.
2. Reduce the length of the Combus run to the module.
3. Increase the gauge of wire.

Capacitance Limits

An  increase  in  capacitance  on  the  Combus  will  affect  data
transmission and will cause the system to slow down. Capacitance
will  increase  for  every  foot  of  wire  added  to  the  Combus.  The
capacitance rating of the wire used will determine the maximum
length of the Combus, between two PC4204CX Combus Repower/
Regenerator modules.
For example, 22-gauge, non-shielded, 4-conductor wire has a typical
capacitance rating of 20 picofarads per foot (which is 20nF/1000’).
For every 1000' of wire added – regardless of where it is run – the
capacitance of the Combus will increase by 20nF.
The  following  chart  indicates  the  total  Combus  wire  allowed
depending on the capacitance rating of the wire used:

Wire Capacitance per

1000’(300m)

TOTAL Combus Wire

Length

15nF

5300’/1616m

20nF

4000’/1220m

25nF

3200’/976m

30nF

2666’/810m

35nF

2280’/693m

40nF

2000’/608m

Wires run in parallel also increase Combus capacitance. For example,
when  using  20nF  wire,  the  following  would  be  some  of  the
combinations allowed:

• Four wire runs at 1000'/305m each
• Six wire runs at 666'/203m each

• Eight wire runs at 500'/152m each
• 10 wire runs at 400'/122m each etc…

Contact  the  wire  manufacturer  for  the  capacitance  ratings  of  the
wire being used.

3.4 Regenerating Combus

This module will regenerate the Combus signal as it passes from
one  side  to  the  other.  The  LEDs  on  the  module  will  illuminate
whenever there is activity on either side of the input or output of
the module.

LED 1 

LED 1 

LED 1 

LED 1 

LED 1 illuminates when the module transmits data on ‘Combus In’

LED 2 

LED 2 

LED 2 

LED 2 

LED 2 illuminates when the module transmits data on ‘Combus Out’

The PC4204CX module will isolate ‘Combus In’ from any short
circuit problems on ‘Combus Out’. In the event of a problem, the
PC4204CX module will generate a module fault along with the
modules on the disabled Combus. This information can be used
to determine which section of Combus is disabled on the system.

When connecting the PC4204CX to the Combus, care must be taken
to  ensure  that  the  ‘Combus  In’    terminals  are  connected  to  the
wires originating from the control panel (or a module that may be
situated between the PC4204CX and the control panel).

3.5 Applying Power

NOTE: Do not connect power until all wiring is complete.

After all wiring is completed, apply power to the control panel.
Connect  the  battery  leads  to  the  battery,  then  connect  the AC
transformer. Then, connect power to the PC4204CX:  first connect
the battery leads, then the AC transformer.

For more information on control panel power specifications, see
the control panel 

Installation Manual

.

NOTE:  It is the installer’s responsibility to provide adequate protection
for the transformer used in the primary and secondary circuit according
to the rated current of the transformer. The transformer used must be Class2,
Fail  Safe  as  defined  within  EN61558-1  and  must  meet  the  applicable
requirements of the EN60950 Standard. A readily accessible disconnect
device  must  be  incorporated  into  the  fixed  wiring  and  must  disconnect
both poles simultaneously. The wiring connected to the PC4204CX must
be  mechanically  protected,  routed,  supported,  clamped  or  secured  in  a
manner that prevents excessive strain on wire and terminal connections,
loosening of terminal connections and conducter insulation damage.

NOTE:  Do  not  connect  fully  discharged  (less  than  10V)  or  damaged
batteries to the PC4204CX.

4. Enrolling the Module

Once  connected,  the  module  must  be  enrolled  on  the  system.  To
enroll the module, perform the following:

1. Enter installer’s programming by pressing [*] [8] [Installer’s Code].

2. Scroll to “Module Hardware” and press the [*] key.

3. Scroll to “Enroll Module” and press the [*] key.

4. Scroll through the different modules until “PC4204” is displayed.

Press the [*] key.

5. The message “Create Tamper on Desired Unit” will be displayed.

To create the required tamper, secure the tamper zone on the
module and then open it. The transition from secure to violated
enrolls the module. After this is done, the keypad will display
the module number and will confirm enrollment (e.g., “PC4204
Mod 01 Enrolled”).

For more information regarding module enrollment, see the control
panel 

Installation Manual

.

Содержание PC4204CX

Страница 1: ...tible cabinet mounted in a dry secure location NOTE The PC4204CX must be installed within a fire enclosure as defined in EN60950 The cabinet must comply with the battery manufacturer s installation instructions NOTE The cabinet should be mounted in a safe and reliable manner A safety factor of 4 or higher must be provided Perform the following steps to mount the unit 1 1 1 1 1 Press the five plast...

Страница 2: ...Module 35 PC4850 Telephone Entry Module 135 Calculating Total Current Requirement Once you have determined which modules will draw power from the main panel use the following chart to calculate the Combus current Combus Current Calculation Chart Item Current mA x Quantity Total mA Keypad 50 x PC4108A 30 x Current required for connected devices PC4116 30 x Current required for connected devices PC4...

Страница 3: ...nal as it passes from one side to the other The LEDs on the module will illuminate whenever there is activity on either side of the input or output of the module LED 1 LED 1 LED 1 LED 1 LED 1 illuminates when the module transmits data on Combus In LED 2 LED 2 LED 2 LED 2 LED2illuminateswhenthemoduletransmitsdataon CombusOut The PC4204CX module will isolate Combus In from any short circuit problems...

Страница 4: ...CC Rules which are designed to provide reasonable protection against such interference in any residential installation However there is no guarantee that interference will not occur in a particular installation If this equipment does cause interference to television or radio reception which can be determined by turning the equipment off and on the user is encouraged to try to correct the interfere...

Отзывы: