background image

PC4204CX

 Power Supply / Relay Output / Combus Repeater Module

v 3.0 • Installation Instructions

Please refer to the System 

Installation Manual

 for information on limitations regarding product use

and function and information on the limitations as to liability of the manufacturer.

®

1.0 Introduction

The PC4204CX is a Power Supply/Relay Output/ Combus Repeater
Module. The PC4204CX provides a power output for system devices,
4  programmable  relay  outputs  and  an  output  to  regenerate  the
Combus data signal to allow for longer wire runs.

NOTE: Do not use any power supply other than the PC4204CX to repower
the  Combus.  If  a  power  supply  other  than  the  PC4204CX  is  used,  the
Combus  repower  function  will  not  operate  as  intended.  See  the  control
panel Installation Manual for details regarding this feature.

2.0 Specifications

• Transformer 16V

AC

- 40V

A

 to 80V

A

 may be used to power the

PC4204CX

• Backup battery 4Ah to 38Ah (not provided)

• Connects to control panel via 4-wire Combus

• Current draw from Combus: 30mA

• Four programmable relay contacts rated 2A, 30V

DC

• Selectable battery charging current (800mA or 1.2A)

• AUX  current:  2.2A  max.,  with  800mA  battery  charge  current

and 80VA transformer

• Tamper connection

3.0 Installing the PC4204CX

The  PC4204CX  should  be  located  inside  a  compatible  cabinet,
mounted in a dry, secure location.

NOTE:  The  PC4204CX  must  be  installed  within  a  fire  enclosure,  as
defined  in  EN60950.  The  cabinet  must  comply  with  the  battery
manufacturer’s installation instructions.

NOTE: The cabinet should be mounted in a safe and reliable manner. A
safety factor of 4 or higher must be provided.

Perform the following steps to mount the unit:

1.

1.

1.

1.

1. Press the five plastic standoffs through the mounting holes

at the back of the cabinet.

2.

2.

2.

2.

2. Secure the cabinet to the wall in the desired location. Use

appropriate  wall  anchors  when  securing  the  cabinet  to
drywall, plaster, concrete, brick or other surfaces.

3.

3.

3.

3.

3. Press the circuit board onto the plastic standoffs to secure

the module to the cabinet.

Once the unit is mounted, wiring may be completed.

3.3 Installation and Wiring

NOTE: The PC4204CX is intended to be PERMANENTLY CONNECTED
and should be installed by service personnel only.

Before  beginning  to  wire  the  unit,  ensure  that  all  power  (AC
transformer and battery) is disconnected from the control panel.
Perform the following steps to complete wiring:

1.

1.

1.

1.

1. Connect the four panel-originating Combus wires to the

PC4204CX.  Connect  the  red,  black,  yellow  and  green
Combus wires to the RED, BLK, YEL and GRN Combus In
terminals, respectively.

If  Relay  1  is  being  used  for  Combus  power,  connect  the
Combus wires according to the diagram below. Note that
for this option, jumper Con3 must also be set for “Repower
Relay 1.”

Содержание PC4204CX

Страница 1: ...tible cabinet mounted in a dry secure location NOTE The PC4204CX must be installed within a fire enclosure as defined in EN60950 The cabinet must comply with the battery manufacturer s installation instructions NOTE The cabinet should be mounted in a safe and reliable manner A safety factor of 4 or higher must be provided Perform the following steps to mount the unit 1 1 1 1 1 Press the five plast...

Страница 2: ...Module 35 PC4850 Telephone Entry Module 135 Calculating Total Current Requirement Once you have determined which modules will draw power from the main panel use the following chart to calculate the Combus current Combus Current Calculation Chart Item Current mA x Quantity Total mA Keypad 50 x PC4108A 30 x Current required for connected devices PC4116 30 x Current required for connected devices PC4...

Страница 3: ...nal as it passes from one side to the other The LEDs on the module will illuminate whenever there is activity on either side of the input or output of the module LED 1 LED 1 LED 1 LED 1 LED 1 illuminates when the module transmits data on Combus In LED 2 LED 2 LED 2 LED 2 LED2illuminateswhenthemoduletransmitsdataon CombusOut The PC4204CX module will isolate Combus In from any short circuit problems...

Страница 4: ...CC Rules which are designed to provide reasonable protection against such interference in any residential installation However there is no guarantee that interference will not occur in a particular installation If this equipment does cause interference to television or radio reception which can be determined by turning the equipment off and on the user is encouraged to try to correct the interfere...

Отзывы: