Page 2 of 12
2.0
INSTALLATION
2.1
Unpacking
Please inspect the shipping boxes for any obvious damage.
Unpack the unit from all packaging and boxes.
Inspect the appearance of the unit for any shipping damage.
Document and inform the shipping company and your local representative, if
any damage was observed.
NOTE: If returning the product to the Maxcom, please use original packaging,
Maxcom disclaims all responsibility for damage caused by non-use of original
packaging.
2.2
EDFA Mounting and Power Connection
1.
Place the unit into a 19-inch wide rack or cabinet. Make sure to leave a
1.75-inch (about 4.5cm) space above and below the unit.
2.
Per design requirements,
the MX-T5400 series 1550nm EDFA can operate
between 0°C~50°C
(
32°F~122°F
)
temperature range. We recommend 25°C
(
77°F
)
environment temperature.
Humidity should be not more than 95%
(
under non-coagulation condition
)
.
It is recommended installing this unit in a dust free environment.
3.
The equipment can be powered by AC or steady voltage DC. If using both
AC & DC, AC is the primary operational power supply.
Request of power supply:
AC input
94-245VAC, 50-60Hz
DC input
36-60VDC, floating
Power consumption
Maximum 50W
4.
The DC power supply for this equipment must comply with a SELV circuit
stipulated as in the CAN/CSA C22.2 No.950-95 standard.
5.
The unit should be grounded with grounding resistance
<
4Ω. According
to the international standard, 120V plug-in adopts a tri-wire rule and
the
center wire is the ground wire.
Before connecting circuit, please use (#20AWG and larger) electric wire to
connect the grounding screw on the bottom and the grounding frame. When
using DC input power supply, the equipment chassis must be grounded.
2.3
Optic connection
1.
Insure all fiber patch cords are clean before connecting to the
transmitter.