Max Machinery, Inc. G-Series User Manual © Copyright 2018
Rev2018A
9
WARNING
Installation and removal should only be facilitated by trained personnel
Verify transmitter output type (ANALOG or FREQUENCY) before wiring, inappropriate wiring could
result in damaging the circuit.
Removal note: The transmitter does not need to be removed from the flow meter for any field servicing or adjustments.
Normally, the flow meter and transmitter are shipped back to the factory for calibration or service as a unit. If the
transmitter needs to be removed from the flow meter for installation, be sure to retighten the transmitter snugly in
order to ensure proper sensor alignment.
Mechanical Installation
1. The transmitter is attached to the flow meter’s threaded magnet shield. Hand tighten only. (~ 3 ft-lb)
2. The transmitter lid has four thread paths. To realign the cable, remove the lid and rotate up to 180° and retighten
using an alternate starting point. Tighten to compress the O-ring seal.
Removal
1. Remove electrical connections
2. Unscrew transmitter, using a wrench if necessary.
Moisture Seal Protection
On all models, the housing is designed as a liquid and vapor-tight enclosure. There is an O—ring seal at the lid of the
housing — these need to be fully seated. A properly sealed transmitter will prevent the formation of damaging moisture
inside the housing.
Turck connector model: The connector is sealed to the lid at the factory and is ready for use.
NPT Model: To ensure a moisture-tight seal, apply appropriate sealant to the threads at installation.
Electrical Installation - Wiring