Smoke detector
7,5m
7,5m
7,5m
Max. 15m
Max. 15m
< 2m
Heat detector
5m
5m
5m
Max. 10m
Max. 10m
If corridors have less than 2 m width, smoke detectors can be mounted
max. 15 m gap.
There is no need to overlap the coverage area of the detectors. If corridors have more
than 2 m width, smoke detectors are mounted in 10 m gaps according to the Table A.
If corridors have less than 2 m width, heat detectors can be mounted with
max. 10 m gap.
There is no need to overlap the coverage area of the detectors. If corridors have more
than 2 m width, heat detectors are mounted with 7 m gaps according the Table A.
< 2m