- 4 -
4. Installation
The dust switch must be installed horizontally or vertically.
・
A: The Isolation must protrude at least 10 mm from the side wall of the duct.
・
B: The distance between the probe tip and the side wall of the duct must be at least 10 mm.
Fig. 2 Installation 1
The dust switch might malfunction if not installed under appropriate operating conditions. Do not install
the dust switch under the following conditions or in an environment.
・
Close to a very narrow section.
・
A nonconductive pipe, short pipe, or duct is used.
・
Environment and conditions do not comply with the Specification.
・
There is a chance that dust may accumulate between the pipe wall and the probe when the base
pipe is extended with a short pipe.
・
The space between the probe tip and the side wall is less than 10 mm.
Fig. 3 Installation 2