INITIAL SET UP
Once the control wires are connected to the MPVSR and a power source,
the device is ready to be programmed to the user’s desired settings. It is
worth keeping in mind that you may not need to alter the factory settings,
which are listed in the table below.
12 Volt DC
Upper Voltage Limit
13.7 Volts
Upper Time Delay
5 Seconds
Lower Voltage Limit
12.8 Volts
Lower Time Delay
5 Seconds
Alarm Voltage Limit
12.0 Volts
Alarm Time Delay
10 Seconds
State of Contacts
Normally Open (n - o)