#msg all on?

Step 4 - SMS Programming (Continued)

 

 

#msg all off?

4.3 (Continued)

Quick Start Complete

The SMS alarm sender is now configured and has begun operation. 

Refer to ME-Link Operation Manual for more information on the 

operation of the ME-Link SMS module.

#info?

Use this command to request the status information of the device.

Example response:

<title>
Ver: <firmware revision>
RSSI: <signal strength>
Power: <supply voltage>
Time: <network current time>
Reminder: <on or off>
Test msg: <on or off>

#inputs?

#reset

Use this command to reset all settings back to defaults, including the PIN.

Example SMS Command:
Response:
SMS Command:
Response:

#reset

Are you sure you want to factory reset? Enter #reset again within 1 minute to confirm

#reset

Device has been reset back to factory defaults.

4.4 - Additional Informative Commands

#help?

Use this command to request help on what commands are available and get more detailed information about different commands. 

Refer to the ME-Link Operation Manual for more detailed information on all the SMS commands.

Use this command to request status of all inputs.

Example response (input 1 only):

Input 1 OFF: ALARM ACTIVE

   Input state as ON/OFF and corresponding alarm direction: ‘Alarm Active’ or ‘Alarm Inactive’

Activated:  

 

 

Alarm state: ‘Last Active’ if inactive or ‘Activated’ if active

Mon 07/12/2020 16:42 

 

Time at which the alarm was last activated

Notified once 

 

 

Alarm notification state: ‘Notified Once’, ‘Not Recorded’, ‘Not Accepted Yet’ or ‘Accepted’

Use this command to request alarm messages for all inputs in 
ON state.

Example response:

Input on messages:
1: Power On/Restored
2: High Level Fault
3: Pump 1 Fault
4: Pump 2 Fault
5: -----------
6: -----------
7: ME-Link Mains Power Failure
8: ME-Link Battery Voltage Healthy

Use this command to request alarm messages for all inputs in 
OFF state. 

Example response:

Input on messages:
1: Power Off/Failure
2: High Level Fault Cleared
3: Pump 1 Fault Cleared
4: Pump 2 Fault Cleared
5: -----------
6: -----------
7: ME-Link Mains Power Restored
8: ME-Link Battery Voltage Low