4
P: 1800 281 282
|
F: 1300 281 282
|
|
W: www.matelecaustralia.com.au
User Commands
SMS commands are sent to the phone number of the SIM card installed. This phone number should be supplied with the SIM card.
Commands sent ending with ‘?’ are a query of the command setting, commands sent without this are used to configure the setting.
The symbols < > are used to reference user information to be sent in the commands, and should not be send in the command
message.
Step 4 - SMS Programming
#title?
4.1 - Set the SMS alarm sender title
Use this command to add the SMS alarm sender title (max 50 characters).
Example SMS command:
#title ME-Link SMS Alarm Sender
The title will be set to ‘ME-Link SMS Alarm Sender’. This will be sent with each alarm message sent from the SMS alarm sender.
#num add <slot> <number>
Use this command to add the phone numbers.
Example SMS Command:
#num add 3 0406446XXX
The phone number 0406446XXX will be added to phone number slot 3.
#num del <slot>
#msg <input> on <message>
#msg <input> off <message>
#title <new title>
4.2 - Set the numbers to receive alarm messages
Use this command to delete a phone number
Example SMS command:
#num del 3
The phone number 0406446XXX is deleted from slot 3.
4.3 - Set the digital input alarm messages to be received
Each digital input will send a message when the input turns on (goes high) and when it turns off (goes low). Inputs 7 and 8 are pre-
programmed for power fail and battery voltage low alarms.
<input>
is the digital input number from 1 to 8 that will trigger the SMS alarm messages.
<message>
Is the text message you want to send to the phone number based on the input state.
Use this command to set alarm on messages for specific inputs.
Example SMS command:
#msg 3 on High Pressure Fault
The Input 3 on message will be set to ‘High Pressure Fault’.
Use this command to set alarm off messages for specific inputs.
Example SMS command:
#msg 3 off High Pressure Cleared
The Input 3 off message will be set to ‘High Pressure Cleared’.
<slot>
is the phone book slot from 1 to 10 which phone numbers can be added and deleted from.
<number>
is the phone number assigned to the phone book slot that will receive the alarm messages.
#num?
Use this command to request the phone number list. Empty slots are reported as ----------.
Use this command to enquire the current SMS alarm sender title.