background image

4

OPERATION

This controller can perform control functions for most Single Pump pumping applications. It is more than likely that the 

control parameters have already been set up for your particular application, however, hereunder you will find details 

of the setup and configuration options.

There are 6 DIP switches located on the lower side of the control module, which allows for selecting “mode” and

“feature”options, as per the following table:

DIP Switch

Position Function

1/2

Off/Off

Mode A: 

Standard typical float switch configuration (Start,Stop and High Level). No Low Level

Off/On

Mode B: 

Standard configuration plus low level (Start,Stop and High Level).

On/Off

Mode C: 

Standard configuration plus Prime Loss enabled, on Low Level (Input 1)

On/On

Mode D: 

Pressure Pumping configuration (Lead, Lag and Low Pressure)

3

Off

Operating Pump alternates each time a 

pu

mp start is triggered, or after 30 minutes continuous running.

On

Operating Pump alternates after 6 hours continuous running.

4

Off

Anti-seize Timer disabled

On

Anti-seize Timer 6 seconds every 7 days enabled

5

Off

When placed in Manual Mode, pump remains in Manual Mode

On

When placed in Manual Mode after 5 minutes the pump will revert to Auto

6

Off

High Level Alarm automatically resets upon open circuit of high level input. High Level alarm

has 15 minute delay.

On

High Level Alarm can only be reset manually. High Level Alarm has 5 minute delay.

Mode A: Standard Configuration

Start/Stop/High  Level  operation.  When  the  Pump  Start  input  is  closed  contact  (triggered),  the  Duty  Pump 

will  be  turned  on.  The  pump  will  remain  on  until  both  the  Pump  Start  and  Pump  Stop  Inputs  have  turned  off

(Open Circuited). Upon High Level, both pumps will run until the Pump Stop Input turns off.

Input

Function

Input 1

Not used

Input 2

Pump Stop

Input 3

Pump Start

Input 4

High Level

Input

Function

Input 1

Low Level

Input 2

Pump Stop

Input 3

Pump Start

Input 4

High Level

Mode B: Standard Configuration plus Low Level Alarm

As per Mode A, except it has an active Low Level input. The Low Level input must be closed, for Pump Start and 

Pump Stop inputs to function. The High Level input however, will still override the Low Level and run both pumps. 

Input functions are as follows:

In addition to this, there is a maximum idle timer, which will trigger a Pump Start condition, if either pump has not run 

for 4 hours, and the Stop Float Contacts are closed. The pump will continue to run until the Stop Float Contacts open. 

Input functions are as follows:

Содержание FPC-15007

Страница 1: ...MAIN ISOLATOR DOC FPC 15007 VER 2 0 P U M P C O N T R O L OWNER S OPERATION MANUAL Single Pump Controller Installation and Operating Instructions MODEL FPC 15007 ...

Страница 2: ...must be Circuit Breaker Protected Qualified Electrician to determine appropriate amp rating Electrical connection to the panel must be carried out in accordance with Connection Instructions see page 3 Addition or modifications to the control panel are not permitted and will void warranty The controller is not intended for use by children or infirm persons without supervision Repairs to the Control...

Страница 3: ... 415Vac Connections E P1 P2 P3 N E A1 A2 A3 Input 1 Low Level Input 2 Stop Level Input 3 Start Level Input 4 High Level INPUT SWITCHES T1 T2 THERMAL 12Vdc Connections COMMON FAULT BMS VOLT FREE PUMP REMOVE BRIDGE WIRE TO USE LOW LEVEL FLOAT ON STEADY A pump fault overload has occured FLASHING MOMENTARY PRESS To mute audible buzzer PRESS FOR 3 SECS To reset alarms and faults PRESS CONTINUOUS To tes...

Страница 4: ... in Manual Mode after 5 minutes the pump will revert to Auto 6 Off High Level Alarm automatically resets upon open circuit of high level input High Level alarm has 15 minute delay On High Level Alarm can only be reset manually High Level Alarm has 5 minute delay Mode A Standard Configuration Start Stop High Level operation When the Pump Start input is closed contact triggered the Duty Pump will be...

Страница 5: ...cts This run on occurs even if Pressure switch contacts open during this initial period If however run time exceeds 11 seconds the pump will stop immediately upon open circuit occurring If the Pressure Switch Input closes circuit as well as the Low Pressure Switch Input a low pressure timer will begin counting If this condition exists for a period of 60 seconds then both pumps are shut down and th...

Страница 6: ...Reset The controller will also use the alternate High Level Alarm Delay Typically used for Storm Water applications High Level Alarm delay in this mode is 15 minutes Setting this DIP Switch to On will cause the High level Alarm to remain active until the controller is reset The High Level Alarm will use the standard High Level Alarm activation delay Typically used for Sewerage applications High Le...

Страница 7: ...ACTOR COIL PUMP R O T C A T N O C MAIN ISOLATOR 2 Amp CIRCUIT BREAKER STROBE BUZZER TRANSFORMER 12Vac 415Vac 240Vac INPUT 1 SWITCH INPUT 2 SWITCH INPUT 3 SWITCH INPUT 4 SWITCH 12Vdc 12Vdc P1 P2 P3 E R1 COMMON FAULT BMS VOLT FREE R1 1 CIRCUIT DIAGRAM ...

Страница 8: ...ALARM ON A high level alarm has been present for the preset time FLASHING A low level alarm is present ON STEADY Pump switched on to run ON STEADY A pump fault overload has occurred FLASHING A prime loss fault has occurred Silences the siren and if held down for 3 seconds clears all faults If selected the LED indicator will confirm if on the particular pump is set to Automatic Pumping Mode Turns p...