OPERATION

This controller can perform control functions for most Single Pump pumping applications. It is more than likely that the 

control parameters have already been set up for your particular application, however, hereunder you will find details 

of the setup and configuration options.

There are 6 DIP switches located on the lower side of the control module, which allows for selecting “mode” and

“feature”options, as per the following table:

DIP Switch

Position Function

1/2

Off/On

Mode A: 

Standard typical float switch configuration (Start,Stop and High Level). No Low Level

Mode B: 

Standard configuration plus low level (Start,Stop and High Level).

Mode C: 

Standard configuration plus Prime Loss enabled, on Low Level (Input 1)

Mode D: 

Pressure Pumping configuration (Lead, Lag and Low Pressure)

3

Off

Operating Pump alternates each time a 

pu

mp start is triggered, or after 30 minutes continuous running.

On

Operating Pump alternates after 6 hours continuous running.

4

Off

Anti-seize Timer disabled

On

Anti-seize Timer 6 seconds every 7 days enabled

5

Off

When placed in Manual Mode, pump remains in Manual Mode

On

When placed in Manual Mode after 5 minutes the pump will revert to Auto

6

Off

High Level Alarm automatically resets upon open circuit of high level input. High Level alarm

has 15 minute delay.

High Level Alarm can only be reset manually. High Level Alarm has 5 minute delay.

Mode A: Standard Configuration

Start/Stop/High  Level  operation.  When  the  Pump  Start  input  is  closed  contact  (triggered),  the  Duty  Pump 

will  be  turned  on.  The  pump  will  remain  on  until  both  the  Pump  Start  and  Pump  Stop  Inputs  have  turned  off

(Open Circuited). Upon High Level, both pumps will run until the Pump Stop Input turns off.

Input

Function

Input 3

Pump Start/Stop

Input 4

High Level

In addition to this, there is a maximum idle timer, which will trigger a Pump Start condition, if either pump has not run 

for 4 hours, and the Stop Float Contacts are closed. The pump will continue to run until the Stop Float Contacts open. 

Input functions are as follows:

Содержание FPC-15007-INT

Страница 1: ...MAIN ISOLATOR DOC FPC 15007 INT VER 1 0 P U M P C O N T R O L OWNER S OPERATION MANUAL Single Pump Controller Installation and Operating Instructions MODEL FPC 15007 INT...

Страница 2: ...ician to determine appropriate amp rating Electrical connection to the panel must be carried out in accordance with Connection Instructions see page 3 Addition or modifications to the control panel ar...

Страница 3: ...H CONNECTED TO INPUT 1 415Vac MAINS POWER SUPPLY PUMP 415Vac BRIDGE IF NOT REQUIRED SUPPLY 415Vac Connections E P1 P2 P3 N E A1 A2 A3 WORKING LEVEL FLOAT COMMON N O CLOSE ON RISE BLUE NOT REQUIRED HIG...

Страница 4: ...ternates after 6 hours continuous running 4 Off Anti seize Timer disabled On Anti seize Timer 6 seconds every 7 days enabled 5 Off When placed in Manual Mode pump remains in Manual Mode On When placed...

Страница 5: ...for Sewerage applications High Level Alarm delay in this mode is 5 minutes Audible and Visual Alarm Test Setting this DIP Switch to On will cause the High level Alarm to remain active until the contro...

Страница 6: ...0Vac Contactor 1 L1 T1 L2 T2 L3 T3 Contactor 3P C1 240V 240N 12V 0V Transformer 12Vac T1 12 Vac 0Vac 95 96 NC Contact TOL 1 Strobe Light Buzzer 415VAC Pump P1 Thermal Overload TOL1 1 2 3 4 5 6 ON Work...

Страница 7: ...LARM ON A high level alarm has been present for the preset time FLASHING A low level alarm is present ON STEADY Pump switched on to run ON STEADY A pump fault overload has occurred FLASHING A prime lo...