RECEIPT INSPECTION: 
 
Check material received against packing list.  Claims resulting from factory errors must be made within 2 weeks 
after receipt of goods.  

 

INSTALLATION: 

 
1.

 

Prior to installing damper in duct, check to make sure blades operate freely with no binding or restriction.  

2.

 

Screw or rivet damper to duct. Make sure that fasteners do not interfere with blade operation and that damper is 
not racked.  

3.

 

Adjust worm gear rotation so that set screws will be accessible when in position. Align square shafts so as to 
catch set screws directly on flats.  Set screws are 90’ opposed. See reverse side for RT-WGA mounting 
requirements when dampers are supplied by others. 

4.

 

Slip worm gear assembly over shaft. Tighten (2) set screws onto damper shaft with 1/8” Allen key, then secure 
to duct or mounting plate.  Assembly mounts horizontally or vertically as required for best cable run.  Test for 
free operation by rotating cable.  Do not attempt to rotate worm gear by pushing on damper blade.  

5.

 

Support cables as required at all changes in direction and at 3 foot intervals.  Use retaining clips 
furnished by MAT.  NO DRAPING – cables should be taut or nearly so.  4” minimum turn radius. Clips 
should be installed with a loose fit to allow cable rotation. The longer the cable and the larger the damper 
– the more attention should be paid to cable support. For longer cable runs (e.g. > 30 ft) it may be more 
convenient to support the cable in a conduit rather than installing cable clamps at 3’ intervals (field 
option)  

6.

 

Fasten ceiling / wall cup or other termination to framing. For RT-CCS, RT-CCR, and RT-CCM see instructions 
provided.     

7.

 

TEST individual damper operation to evaluate cable support scheme prior to ceiling close-up.  

8.

 

Install ceiling/wall cup cover plate after installation and air system balancing, but prior to painting.  

 
OPERATION:  
 
1.

 

Damper may be adjusted with a quality ¼’ nut driver or hex socket wrench.  (Thin blade screwdriver if 
ordered.)  Often cable end may be pulled out several inches to ease adjustment.  

2.

 

Worm gear has a 20-1 ratio; therefore a 90 degree blade rotation requires five (minimum) complete rotations.  

3.

 

Damper will hold set position.  Gear design will not allow reverse movement from the damper end.  

 
MAINTENANCE:   

 

Properly installed 

ROTO-TWIST®

 dampers and the RT-WGA damper drive require no maintenance.  

 
 