OPERATION
18
Copyright © 2009 Mastervolt / December 2009 / WHISPER 3.5 / EN
3 OPERATION
3.1 GENERAL
The generating set is operational after full installation and
filling up with: fuel, engine lubricating oil and cooling liquid,
filling the starter battery with acid, connecting the battery
to earth and connecting the MasterView Easy remote
panel.
1 Filling
cap
2
Minimum oil level
3
Maximum oil level
Figure 9
3.2
OPERATING INSTRUCTIONS
3.2.1
Summarised operating instructions (daily
use)
Routine "pre-start" checks:
1
Check oil level (refer to figure 9).
2
Engine cooling system (all valves open).
3 Power source selector switch (off/shore
power/generator power). Switch power source switch
to "OFF", or switch off all consumers in the usual way.
If a
Mass SystemSwitch
is installed, this operates
automatically.
4
Switch on battery switch (when installed).
5
Fuel valve: open.
Starting:
To initiate the full automatic starting procedure, push
the Start / Stop button on the Local control panel or
give a start command by means of the MasterView
Easy. You can monitor the procedure on the display
of the MasterView Easy
In operation checks:
1
Check for abnormal noise or vibration;
2
Check the voltage;
3
Check sea water flow at exhaust outlet;
4 Power source selector switch (off/shore
power/generator power). Switch to power source
Generator
. If a
Mass SystemSwitch
is installed, this
operates automatically;
5 Before loading the generating set up to maximum,
have it run warm. Continuous load should be
restricted to 70 % of maximum load.
Stopping generator:
1 Switch off all electrical devices (consumers). If the
generating set has been running under full load for a
longer period, do not shut it down abruptly. Reduce
the electrical load to about 30% of the rated load (i.e.
30% of 3 kW is approx. 1000W) and let it run for
approx. 5 minutes.
2
Push the Start / Stop button on the Local control panel
or give a stop command by means of the MasterView
Easy.
3
Close the inlet sea water cock.
4 Switch to an other 230V power source, if available. If
a
Mass SystemSwitch
is installed, this is done
automatically.
1
2
3
Содержание WHISPER 3.5M3000 RPM
Страница 35: ...SPARE PARTS LIST EN WHISPER 3 5 December 2009 Copyright 2009 Mastervolt 35 Figure 18 Waterpump type K...
Страница 37: ...NOTES EN WHISPER 3 5 December 2009 Copyright 2009 Mastervolt 37 NOTES...
Страница 38: ...NOTES 38 Copyright 2009 Mastervolt December 2009 WHISPER 3 5 EN NOTES...
Страница 39: ...NOTES EN WHISPER 3 5 December 2009 Copyright 2009 Mastervolt 39 NOTES...