PowerCombi MasterBus Interface 

 User and Installation Manual 

 

 

3

 

 

 

 

 

The following table shows the PowerCombi configuration settings. 

Configuration 

Description 

Default 

Adjustable range 

Device 

 

 

 

Language 

Language displayed on monitoring 
device connected to PowerCombi 

English 

Read-only 

Name 

Name of the PowerCombi in 
MasterBus 

PowerCombi 

Free text with a max. of 12 
characters 

Type 

PowerCombi type 

12V/1200W-50A or  
12V/2000W-100A 

Read-only 

Inverter 

 

 

 

Energy save mode  Option to enable Energy save mode 

Off (not checked) 

Off. On 

Frequency 

Output frequency 

60Hz 

60Hz 

Voltage 

AC voltage 

115V 

100 - 120 

DC low off 

Low battery voltage at which the 
inverter switches off 

10.0V /  
20.0V  

10.00-11.50 (12V) 
20.00-23.00 (24V) 

DC low on 

Low battery inverter switch on 
voltage at DC Low off alarm 

11.5V /  
23.0V 

10.00-14.50 (12V) 
20.00-29.00 (24V) 

DC high off 

High battery voltage for inverter 
switch off 

15.5V /  
31.0V 

15.00-16.50 (12V) 
30.00-33.00 (24V) 

DC high on 

High battery voltage for inverter 
switch to DC High Off alarm 

15.0V /  
30.0V 

13.00-16.50 (12V) 
26.00-33.00 (24V) 

Charger 

 

 

 

Max charge cur. 

Maximum charging current 
adjustable.  

50A /  
100A 

13-50 (12V/1200W-50A) 
25-100 (12V/2000W-100A) 
6-25 (24V/1200W-25A) 
13-50 (24V/2000W-50A)

 

Battery type 

Select the main battery type. 

Flooded (Lead acid) 

Flooded, Gel, AGM, User defined 

Bulk 

 

 

 

Voltage 

Maximum Bulk voltage (adjustable if 
User Defined). 

Flooded: 14.40 / 28.80  
Gel: 14.40 / 28.80 
AGM: 14.40 / 28.80 
User defined: 14.40 / 28.80 

12.00-16.00 (12V) 
24.00-32.00 (24V) 
Read-only when battery type is 
not User defined 

Maximum time 

Maximum time the bulk phase lasts 
before the charger changes to 
absorption. 

480min 

30-1200 
Read-only when battery type is 
not User defined 

Absorption 

 

 

 

Voltage 

Absorption voltage (adjustable if User 
Defined is selected.  

14.25V /  
28.50V 

12.00-16.00 (12V) 
24.00-32.00 (24V) 
Read-only when battery type is 
not User defined 

Maximum time 

Maximum time that the charger stays 
in absorption mode. 

240min 

30-600 

Float settings 

 

 

 

Voltage 

Float voltage (adjustable if User 
Defined). 

Flooded: 13.25/26.50 
Gel: 13.80/27.60  
AGM: 13.80/27.60 
User defined: 13.25/26.50

 

12.00-16.00 (12V) 
24.00-32.00 (24V) 
Read-only when battery type is 
not User defined 

AC IN 

 

 

 

AC IN support 

Allow AC support mode option 

Off (not checked) 

Off. On 

DIP Switches 

Position of the DIP switches 

Not applicable 

Read-only 

A MasterBus device can be programmed to initiate an action at another connected device. This is very helpful in automation of 

your system. In MasterBus this is done by means of event-based commands. In the Events tab you can program the 

PowerCombi

 to act as an event source. Events which occur during the operation of the 

PowerCombi

 will then trigger actions 

from other products. The following tables list the parameters as shown in MasterAdjust. 

 

 

Содержание MasterBus PowerCombi Interface

Страница 1: ...consequential damage due to use of the PowerCombi MasterBus Interface possible errors in the manuals and the results thereof use that is inconsistent with the purpose of the product Disclaimer Our products are subject to continual development and improvement Therefore additions or modifications to the products may cause changes to the technical data and functional specifications No rights can be d...

Страница 2: ...he PowerCombi 4 CONFIGURATION The following table lists the MasterBus monitoring functions as shown in MasterAdjust Monitoring Description Default Adjustable range General Device state The operation mode Off Charging Inverting Alarm Power saving Supporting Not applicable read only AC IN Limit Fuse setting of the AC input 15 3 30 Power button Button to switch off on the PowerCombi On On Off DC IN O...

Страница 3: ...l AGM User defined Bulk Voltage Maximum Bulk voltage adjustable if User Defined Flooded 14 40 28 80 Gel 14 40 28 80 AGM 14 40 28 80 User defined 14 40 28 80 12 00 16 00 12V 24 00 32 00 24V Read only when battery type is not User defined Maximum time Maximum time the bulk phase lasts before the charger changes to absorption 480min 30 1200 Read only when battery type is not User defined Absorption V...

Страница 4: ...witch to position remote No display function Display is switched off Switch on display refer to display manual Error in the wiring Check the MasterBus cables No powering device available on the MasterBus With AC power disconnected the PowerCombi MasterBus Interface gets no power from the MasterBus network At least one connected MasterBus device should have powering capabilities Problem Possible ca...

Отзывы: