6 CONFIGURATION
The Mass Sine Ultra is provided with a group of DIP-
switches to adjust the Mass Sine Ultra according to the
specifications of the electrical installation, see figure 6-1.
DIP-switch settings are 0 for default values. The Mass Sine
Ultra also features the more sophisticated MasterBus
configuration.
Previously done MasterBus settings are overruled by the
DIP-switch settings and they are greyed out in the menu.
When a DIP-switch is set to 0, the corresponding MasterBus
setting becomes default too, regardless the previous setting.
6.1
Configuration via dip-switches
The DIP-switches are located in the connection
compartment. Figure 6-1 shows the location of the DIP-
switches and the print on the inside of the front cover plate.
Figure 6-1: DIP-switches and cover print
DIP
switch
Function
A1-A2
Parallel mode
0-0: Stand alone
1-0: Master 0
0-1: Slave
1-1: NA
A3
Output frequency inverter
0: 50 Hz
1: 60 Hz
A4
Energy saving mode
0: off
1: on (scan mode)
A5-A6
N.A.
A7-A8
Main battery type
0-0: Flooded
1-0: Gel
0-1: AGM
1-1: Flooded
traction