INSTALLATION
EN / Mass Sine C1 / October 2010 / Copyright © 2010 Mastervolt
9
4 INSTALLATION
During installation and commissioning of the Mass Sine,
the Safety Guidelines & Measures are applicable at all
times. See chapter 2 of this manual.
4.1 UNPACKING
The delivery consists of the following parts:
•
The Mass Sine inverter
•
This user’s manual
After unpacking, check the contents for possible damage.
Do not use the product if it is damaged. If in doubt, contact
your supplier.
Check from the identification label (see section 1.6)
whether the battery voltage is the same as the DC-input
voltage of the Mass Sine (e.g. 24V battery set for a 24V
input voltage). Also check that the AC output voltage and
output power of the Mass Sine satisfies loading
requirements.
4.2 ENVIRONMENT
Obey the following stipulations during installation:
•
The Mass Sine is designed for indoor use only.
•
Ambient temperature: 0 ... 60°C / 32°F … 140°F;
(power derating above 25°C / 104°F to decrease the
internal heat sink temperature)
•
Humidity: 0-95% non condensing
•
Mount the Mass Sine on a solid surface, with the
connecting cables downwards.
•
Make sure that the hot air produced during operation
can be discharged. The Mass Sine must be mounted
in such a way that obstruction of the airflow through
the ventilation openings will be prevented.
•
No objects must be located within a distance of 10 cm /
4 inch around the Mass Sine.
•
Do not locate the Mass Sine in the same compartment
as the batteries.
•
Do not install the Mass Sine straight above the
batteries because of possible corrosive sulphur fumes
4.3 WIRING
The wiring is connected inside the connection
compartment. If necessary, the wiring can be fed from the
top to the bottom side of the cabinet along the back of the
cabinet.
Always feed the wiring through the cable glands of the
cabinet, and then connect the wiring to the terminals. Fix
the phase line wire to terminal L, the neutral wire to
terminal N and the ground wire to terminal PE.
4.3.1 AC-wiring
For a safe installation the correct wire cross section must
be applied. Don’t use a cross section that is smaller than
indicated. See table below to select the appropriate cross
section for the AC wiring (up to 6m / 20ft length):
Recommended wire colours (refer to local rules):
•
230V AC installations:
Wire color
Meaning
Must be
connected to:
Brown or black
Phase
L1
Blue Neutral
N
Green/Yellow
Earth
PE / GND
Recommended torques AC wiring:
Model Mass Sine
Recommended torque AC wiring:
Nm
In-Lbs
12/800, 24/800
1.5 – 1.8 Nm
13 – 16 In-Lbs
Model Mass Sine
Minimum cross section:
12/800, 24/800
1.5 mm²
AWG 14