INSTALLATION  

 

EN / Mass Sine C1 / October 2010 / Copyright © 2010 Mastervolt  

  

9

 

 

4 INSTALLATION 

 
During installation and commissioning of the Mass Sine, 
the Safety Guidelines & Measures are applicable at all 
times. See chapter 2 of this manual.  
 

4.1 UNPACKING 

 

The delivery consists of the following parts: 

  The Mass Sine inverter 

  This user’s manual 

 
After unpacking, check the contents for possible damage. 
Do not use the product if it is damaged. If in doubt, contact 
your supplier. 
Check from the identification label (see section 1.6) 
whether the battery voltage is the same as the DC-input 
voltage of the Mass Sine (e.g. 24V battery set for a 24V 
input voltage). Also check that the AC output voltage and 
output power of the Mass Sine satisfies loading 
requirements. 
 

4.2 ENVIRONMENT 

 

Obey the following stipulations during installation:  

  The Mass Sine is designed for indoor use only. 

  Ambient temperature: 0 ... 60°C / 32°F … 140°F; 

(power derating above 25°C / 104°F to decrease the 
internal heat sink temperature) 

  Humidity: 0-95% non condensing 

  Mount the Mass Sine on a solid surface, with the 

connecting cables downwards. 

  Make sure that the hot air produced during operation 

can be discharged. The Mass Sine must be mounted 
in such a way that obstruction of the airflow through 
the ventilation openings will be prevented. 

  No objects must be located within a distance of 10 cm / 

4 inch around the Mass Sine.  

  Do not locate the Mass Sine in the same compartment 

as the batteries. 

  Do not install the Mass Sine straight above the 

batteries because of possible corrosive sulphur fumes 

 

4.3 WIRING 

 

The wiring is connected inside the connection 
compartment. If necessary, the wiring can be fed from the 
top to the bottom side of the cabinet along the back of the 
cabinet.  
Always feed the wiring through the cable glands of the 
cabinet, and then connect the wiring to the terminals. Fix 
the phase line wire to terminal L, the neutral wire to 
terminal N and the ground wire to terminal PE. 
 

4.3.1 AC-wiring 

 

For a safe installation the correct wire cross section must 
be applied. Don’t use a cross section that is smaller than 
indicated. See table below to select the appropriate cross 
section for the AC wiring (up to 6m / 20ft length): 
 

 
Recommended wire colours (refer to local rules): 
 

  230V AC installations: 

Wire color 

Meaning 

Must be 

connected to:  

Brown or black 

Phase  

L1 

Blue Neutral 

Green/Yellow 

Earth 

PE / GND 

 
Recommended torques AC wiring: 
 

Model Mass Sine 

Recommended torque AC wiring: 

 

Nm 

In-Lbs  

12/800, 24/800 

1.5 – 1.8 Nm 

13 – 16 In-Lbs 

Model Mass Sine 

Minimum cross section: 

12/800, 24/800 

1.5 mm² 

AWG 14 

Содержание MASS SINE 12/800

Страница 1: ...SS SINE 12 800 24 800 SINE WAVE INVERTER MASTERVOLT Snijdersbergweg 93 1105 AN Amsterdam The Netherlands Tel 31 20 3422100 Fax 31 20 6971006 www mastervolt com Copyright 2010 Mastervolt v 5 0 October...

Страница 2: ...2 Copyright 2010 Mastervolt October 2010 Mass Sine C1 EN...

Страница 3: ...g regarding the use of batteries 6 3 OPERATION 7 3 1 Introduction 7 3 2 Switching On and Off 7 3 3 Indicators 7 3 4 Remote controlled operation 8 3 5 Maintenance 8 3 6 Problem solving 8 4 INSTALLATION...

Страница 4: ...ts for installation labor or shipping of the defective parts are not covered by this guarantee 1 3 VALIDITY OF THIS MANUAL Copyright 2010 Mastervolt All rights reserved Reproduction transfer distribut...

Страница 5: ...ANCE REPAIR 1 If the Mass Sine is switched off during maintenance and or repair activities it should be secured against unexpected and unintentional switching on remove the connection to the batteries...

Страница 6: ...d for use as a component of any life support system unless a specific written agreement pertaining to such intended use is executed between the manufacturer and Mastervolt Such agreement will require...

Страница 7: ...Mass Sine is switched on overload Mass Sine is overloaded overload inverter on blinking slow Overload in wait state overload inverter on blinking fast The Mass Sine is switched off due to overload low...

Страница 8: ...NOTE When the main switch is in the Off position it overrides the remote control panel interface In this off state it is not possible to start the Mass Sine remotely The meaning of the illuminated LE...

Страница 9: ...must be mounted in such a way that obstruction of the airflow through the ventilation openings will be prevented No objects must be located within a distance of 10 cm 4 inch around the Mass Sine Do no...

Страница 10: ...PE GND to the hull or the chassis CAUTION For safe installation it is necessary to connect the neutral conductor N of the AC output to the earth PE GND insert a Residual Current Device earth leakage s...

Страница 11: ...e Use mounting materials which are suitable to carry the weight of the Mass Sine Batteries Refer to chapter 6 Specifications for recommended capacity Appropriate and reliable cable terminals cable lug...

Страница 12: ...e Mass Sine in a circuit It is not meant to provide detailed wiring instructions for any particular electrical installation Figure 3 Installation drawing of the Mass Sine inverter DC distribution RCD...

Страница 13: ...Check with a suitable voltmeter whether the DC installation is voltage free 2 Connect the AC load to the AC output For safe installation it is necessary to Connect both the earth PE GND and the neutr...

Страница 14: ...V again if the connected load rises above 30W Small loads like a digital clock will function properly and still 10 energy can be saved The inverter can be set in this mode by placing jumper S2 Do not...

Страница 15: ...occur and avoid having flammable materials close by Now the Mass Sine is ready for operation 4 11 DECOMMISSIONING If it is necessary to put the Mass Sine out of operation follow the instructions in or...

Страница 16: ...load and charge batteries DC cables too thin Replace with cables of correct diameter Inverter goes on and off LED inverter on and LED low battery are blinking on turns Connections are corroded or bad...

Страница 17: ...d batteries 100Ah 50Ah DC No load power consumption Stand by mode 65mA 0 8W 35mA 0 8W Low power mode Economic mode 410mA 4 9W 200mA 4 9W High power mode 470mA 5 6W 240mA 5 6W AC output Nominal voltage...

Страница 18: ...TECHNICAL DATA 18 Copyright 2010 Mastervolt October 2010 Mass Sine C1 EN 6 2 DIMENSIONS Figure 5 Dimensions Mass Sine 12 800 230V and 24 800 230V...

Страница 19: ...ne 24 800 230V Is in conformity with the provisions of the following EC directives 2004 108 EC EMC directive the following harmonized standards have been applied o EN 61000 6 3 2007 Emission household...

Страница 20: ...Snijdersbergweg 93 1105 AN Amsterdam The Netherlands Tel 31 20 3422100 Fax 31 20 6971006 Email info mastervolt com...

Отзывы: