Power sharing mode:

 The CombiMaster automatically reduces its battery charger output when the load connected to AC 

OUT increases while the available power at AC IN is limited. This avoids the external AC circuit breaker from tripping. The 
power sharing level, i.e. AC IN Limit setting (adjustable from a display), should be set to match the value of the external 
circuit breaker.  

 

 

Load on AC OUT < AC IN Limit 

Load on AC OUT ≥ AC IN Limit 

 

 

AC input support mode:

 If the demand for AC power still 

increases, the external AC circuit breaker may still trip if 
nothing is done. This problem can be solved by the AC IN 
support mode. If the total demand for energy exceeds the 
maximum external power supply, energy can be added to 
AC OUT by means of the inverter. This means that the 
inverter adds energy from the batteries, in parallel with the 
external power source. 

 

Note:

  Different countries have different regulations regarding AC sources operating in parallel with the AC grid. This may 

mean that in some situations AC IN support mode is not allowed! Familiarize yourself with local regulations on this 
issue. AC power from the inverter will never be fed back into the AC grid. 

See chapter 5 on page 16 for the required settings. 

3.3 

Remote control 

The CombiMaster can be monitored from a remote panel like the SmartRemote or a Touch 5 (in a CZone network). Some 
settings can only be adjusted from a laptop/notebook or PC connected to the CombiMaster via a USB Interface.  

3.4 

Protection 

 

Overload or short circuit:

 while in the inverter mode, the CombiMaster will shut down after 5 seconds of 200% overload 

or after 10 seconds 150%. 

 

Transfer switch overload:

 the transfer switch of the CombiMaster is protected against overload and short circuit. When 

the current through the transfer switch of the CombiMaster is too high, the thermal fuse (item 8 on page 6) will disconnect 
the AC input. 

 

High temperature:

 if the ambient temperature of the CombiMaster exceeds 40°C, it will reduce power. If it exceeds 60°C, 

it will shut down, trigger the status LEDs and optionally a remote alarm. 

High temperature is most likely caused by heavy loads operating for a longer period, high ambient temperature or 
disrupted air flow (dust or too little space). 

As soon as the temperature drops below the factory default threshold, the inverter is powered up automatically or the 
charger resumes its charge current. 

 

Battery low/high:

 the CombiMaster can warn for low or high battery voltages by triggering status LEDs and 

CZone/MasterBus alarms. 

 

CAUTION! 

The CombiMaster is not protected against reversed polarity of the DC input or serious over voltage (>280V

AC

) on 

the AC in- and output. 

See section 6.2 on page 20 for an overview of the status LED. See chapter 5 on page 16 for the required settings. 

AC

DC

AC IN

6A

4A

AC OUT

BATTERIES

2A

AC

DC

AC IN

6A

6A

AC OUT

BATTERIES

0A

AC

DC

AC IN

AC OUT

BATTERIES

6A

9A

3A

Содержание COMBIMASTER 12V/2000VA-60A

Страница 1: ...OMBIMASTER 230V Series INVERTER CHARGER COMBINATION WITH AC IN SUPPORT USER AND INSTALLATION MANUAL 10000015079 03 To download this manual in other languages please visit our website www mastervolt co...

Страница 2: ...5 3 AC Safety grounding 10 4 5 4 Network wiring CZone MasterBus 10 4 6 Things you need 10 4 7 Installation step by step 11 4 8 Accessories connector dry contacts 14 4 8 1 Remote switch 14 4 8 2 Alarm...

Страница 3: ...ular base at least once a year Do not use the CombiMaster when the wiring is undersized or damaged 6 Do not operate the CombiMaster if it has received a sharp blow been dropped or otherwise damaged in...

Страница 4: ...nded limits of discharge level of your batteries 5 If it is necessary to remove a battery always remove grounded terminal from battery first Make sure all accessories are off so as not to cause an arc...

Страница 5: ...ply with these instructions may result in under performance damage or failure of the product and may void this warranty The warranty is limited to the cost of repair and or replacement of the product...

Страница 6: ...Ground stud 11 CZone MasterBus connection 12 Accessories connector 13 Temperature sensor connection 3 2 Operating modes Inverter mode When there is no external AC power available the inverter provide...

Страница 7: ...mote or a Touch 5 in a CZone network Some settings can only be adjusted from a laptop notebook or PC connected to the CombiMaster via a USB Interface 3 4 Protection Overload or short circuit while in...

Страница 8: ...ventilation in any way The CombiMaster requires a minimum of 100mm 4 of clearance on every side to ensure safety and proper ventilation If the CombiMaster is installed in the immediate vicinity of liv...

Страница 9: ...eline only Always comply with all local rules and regulations WARNING On first connecting to power make sure the CombiMaster is in a well ventilated area as it might spark 4 5 1 DC wiring Always keep...

Страница 10: ...Recommended cross section for the AC wiring AC Current Minimum cross section 0 20 A 2 5 mm 20 32 A 4 mm Recommended wire colors refer to local rules Wire color Meaning Must be connected to Europe USA...

Страница 11: ...ns Appropriate and reliable cable terminals cable lugs battery terminals and cord end terminals We recommend as a minimum tool kit Socket wrench to fix the main DC cables 13mm Socket wrench to fix the...

Страница 12: ...the two screws at the bottom and then lifting the front cover plate Step 7 Connect the AC wiring to the screw terminals Fasten the cables with a strain relief Step 8 Integrate a fuse holder in the po...

Страница 13: ...nnect to the CombiMaster Adding the CombiMaster to a MasterBus network 1 Disconnect a MasterBus cable or Terminator from the closest MasterBus device and connect it to the CombiMaster 2 Connect the ne...

Страница 14: ...Remote contacts to use the ignition lock In this case the CombiMaster s main switch must be in the off position Closed On Open Charge only Use both contacts to connect an external switch In this case...

Страница 15: ...h the DIP switch settings This is done in the CZone Configuration Tool MasterBus network Use an RJ45 MasterBus cable not included and daisy chain the CombiMaster to the other MasterBus devices forming...

Страница 16: ...to the ON position 1 DIP switch 2 is MasterBus Powering ON 1 or OFF 0 By default this is OFF DIP switches 3 to 5 are used for battery type selection DIP switch 3 4 5 MasterBus settings Flooded 1 0 0...

Страница 17: ...ters as shown in MasterAdjust Menu Description Temperature high Internal temperature of the CombiMaster is too high Fan error An error has been detected in the fan DC high voltage Battery voltage is t...

Страница 18: ...Maximum time that the charger stays in absorption phase 240 min 0 600 min Return Amps Return amps of maximum charge current 6 0 100 Float Voltage Float voltage 13 25 26 50V 12 15 24 30V Return to Bul...

Страница 19: ...arge phase Absorption Float Charge phase Float AC IN Limit A AC input is set to 6A AC IN Limit B AC input is set to 10A AC IN Limit C AC input is set to 16A Table 2 CombiMaster 230V Series MasterBus E...

Страница 20: ...k phase Charger in absorption phase Charger in float phase AC IN support mode Green blinking Inverter power save mode active Red on AC input out of range battery voltage low warning shutdown battery v...

Страница 21: ...lk phase Once consumption decreases the charger goes back to normal operation of the 3 step charge system Connected to the CombiMaster the batteries can be left unattended for weeks or months One hour...

Страница 22: ...ust be corrected immediately If necessary use a soft clean cloth to clean the CombiMaster Do not use any liquids or corrosive substances such as solvents alcohol petrol or abrasive components 6 6 1 De...

Страница 23: ...s the charge current is reduced Check AC input voltage Batteries not fully charged Charge current too low See Charge current too low in this table Current to load is too high Reduce load taken from th...

Страница 24: ...0V 16 0V 16 0V 16 0V Switch on voltage high battery 15 0V 15 0V 15 0V 15 0V Max ripple on DC full load 15 15 15 15 Nominal DC current at full load 160A 100A 260A 130A Recommended battery capacity 120...

Страница 25: ...ulk time at 13 25 26 50 V 13 25 26 50 V 13 25 26 50 V 13 25 26 50 V Return to bulk voltage 12 80 25 60 V 12 80 25 60 V 12 80 25 60 V 13 25 26 50 V Bulk return time 30 s 30 s 30 s 240 s Absorption volt...

Страница 26: ...ty not condensing Standards approvals listings CE E mark Front panel display Yes LEDs show AC input state Inverter state charger state Battery temperature sensor Yes Cooling Maintenance free vario fan...

Страница 27: ...allation Manual 27 8 5 Dimensions 12V 2000VA 60A and 24V 2000VA 40A 12V 3000VA 100A and 24V 3000VA 60A Figure 8 Dimensions in mm inches 240 9 5 262 10 3 150 5 9 153 6 0 378 14 9 284 11 2 240 9 5 327 1...

Страница 28: ...1 USA 1 800 307 6702 Option 1 technical marinco com ASIA PACIFIC 42 Apollo Drive Rosedale AUCKLAND 0632 New Zealand 64 9 415 7261 enquiries bepmarine com Copyright 2019 Mastervolt All rights reserved...

Отзывы: