  ChargeMaster Plus 24/80-2, 24/110-2 

 User and Installation Manual 

 

 

 

 

5.4.1

 

Charge voltages 

 

Bulk  Absorption 

Float 

AGM or 
GEL 

28.5 

28.5 

27.6 

Flooded  

28.5 

28.5 

26.5 

Lithium-ion  28.5 

28.5 

27.0 

5.4.2

 

Pre-float 

The ChargeMaster Plus can automatically switch 
each  individual  output  from  absorption  to  pre-
float  stage.  Pre-float  ensures  batteries  that  are 
nearly  full  do  not  receive  the  higher  charge 
voltage  needed  in  the  absorption  stage.  This 
prevents over-charging, extending the lifespan of 
the batteries

.

 

5.4.3

 

Temperature compensated charging  

By installing the battery temperature sensor, the 
charge  voltages  are  automatically  adapted  for 
deviating temperatures. 

 

Ch
ar

ge

 volt
age
 (V

Battery temperature (°C) 

Figure 7: Temperature compensated charging 

When the battery temperature is low, the charge 
voltage increases. When the battery temperature 
is  high,  the  charge  voltage  is  decreased. 
Overcharge and gassing are prevented this way. 
This will extend the life of your batteries. 

5.4.4

 

Flat battery support 

The ChargeMaster Plus automatically detects a 
flat battery and will initiate the flat battery charge 
curve described in the following table. 

Voltage 

Output power 

0.00V 

 5.00V 

15%-30% of I

max

 

5.00V 

 16.00V 

25% of I

max

 

16.00V 

 20.00V  linear from 25% - 100% of I

max

 

20.00V 

 28.50V  100% of I

max

 

>28.50 

Limited by P

max

 

5.5

 

DC Output 2 

The ChargeMaster Plus is equipped with one full 
output  (DC  1  OUT)  and  one  secondary  output 
(DC 2 OUT). The total output current is divided 
over  these  two  outputs.  See  section  3.6  for 
connections.  
DC  2  OUT  is  current  limited  at  20A  and  can 
operate in the following modes: 

 

12V battery

 (DIP switch 6)

 

If DIP switch 6 is in the on position, then DC 2 
OUT  is  current  limited  and  set  to  12V.  All 
batteries are charged with the same settings. 

 

Current limit 10A

 (DIP switch 7)

 

 

DC 2 OUT is current limited to 10A to safely 
charge a small starter battery. 

 

12V constant voltage 

DC  2  OUT  is  current  limited  (configurable) 
and set to 13,25V constant voltage. 

 

24V constant voltage 

DC  2  OUT  is  current  limited  (configurable) 
and set to 26,5V constant voltage. 

 

12V 3 step+ 

DC 2 OUT can charge a 12V battery with its 
own  charging  profile.  Settings  can  be 
configured. 

The  charge  method  can  be  selected  in  the 
configuration  tool.  The  first  two  can  also  be 
selected via DIP switches. 

5.6

 

Maintenance 

No  specific  maintenance  to  the  ChargeMaster 
Plus  is  required.  Examine  your  electrical 
installation  on  a  regular  basis,  at  least  once  a 
year.  Defects  such  as  loose  connections,  old 
wiring etc. must be corrected immediately. 
If  necessary,  use  a  soft  clean  cloth  to  clean 
enclosure of the ChargeMaster Plus. Do not use 
any  liquids  or  corrosive  substances,  such  as 
solvents, alcohol, petrol or abrasive components. 

30

28

26

24

22

-30

-20 -10

0

10

20

30

40

50

60

Содержание CHARGEMASTER PLUS 24/110-2

Страница 1: ...te downloaden naar onze website Um diese Anleitung in anderen Sprachen herunterzuladen besuchen Sie bitte unsere Website Pour t l charger ce manuel dans d autres langues consultez notre site Web Para...

Страница 2: ...AC safety grounding 8 3 3 4 Network wiring CZone MasterBus 8 3 4 Batteries 9 3 5 Things you need 9 3 6 Overview of the connection compartment 10 3 7 Connection example 11 3 8 Installation step by step...

Страница 3: ...of the product Costs of labor or shipping are not covered by this warranty 1 4 Disclaimer Our products are subject to continual development and improvement Therefore additions or modifications to the...

Страница 4: ...be carried out only by qualified and trained personnel consistent with the locally applicable standards and regulations 9 Make sure that all wiring is properly installed in good electrical condition...

Страница 5: ...ay burst and cause injury to persons and damage to property Make sure lithium ion batteries used for this charger are certified to IEC standards 2 NEVER charge non rechargeable batteries 3 NEVER charg...

Страница 6: ...area around battery is well ventilated while battery is being charged 3 Clean battery terminals Be careful to keep corrosion from coming in contact with eyes 4 Add distilled water in each cell until...

Страница 7: ...clearance on every side If added to a CZone or MasterBus network take the network powering into consideration Never place the ChargeMaster Plus directly above the battery being charged as gases from b...

Страница 8: ...n of AC wiring and recommended wire colors 240VAC 50 60Hz installations Wire color Meaning Must be connected to Brown or black Phase L1 Blue Neutral N Green Yellow Earth PE GND 120VAC 50 60Hz installa...

Страница 9: ...ake sure the manufacturer s recommendations are met 3 5 Things you need Make sure you have all the parts you need to install the ChargeMaster Plus ChargeMaster Plus included Battery temperature sensor...

Страница 10: ...on negative output terminal 7 Safety ground connection 2 M6 Positive terminal charge output 2 DC 2 OUT 8 Network connection CZone MasterBus 3 Isolation walls for DC connections 9 Temperature sensor co...

Страница 11: ...ion Figure 3 Installation drawing of the ChargeMaster Plus Notes If the battery temperature remains within 15 25 C connection of the battery temperature sensor is optional Lithium ion batteries requir...

Страница 12: ...polarity may lead to serious damage to the batteries the ChargeMaster Plus the cabling and or the terminal connections Fuses between the batteries and the ChargeMaster Plus cannot prevent damage caus...

Страница 13: ...mp sense jack 7 Option Connect the ChargeMaster to the CZone or MasterBus network 8 Adding to a CZone network 1 Disconnect the backbone at the closest backbone connection and add in a tee connector 2...

Страница 14: ...n new the ChargeMaster Plus will not start charging batteries before activated with the ON OFF button See step 6 4 Check the DIP switches See chapter DIP switch settings on page 15 5 Check and adjust...

Страница 15: ...e CZone Configuration Tool Instructions manual for more information In a MasterBus network DIP switch 1 must always be set to the ON position 1 DIP switch 2 is MasterBus Powering ON 1 or OFF 0 DIP swi...

Страница 16: ...he main battery bank in C read only DC 1 OUT Output 1 Output state pre float on read only Output 1 V Voltage of charge output 1 read only Output 1 A Output current of charge output 1 read only Shunt d...

Страница 17: ...terBus DIP switch 1 must be in the ON position Parameter Meaning Factory setting Value range Device Language Menu language of this device English EN NL DE FR ES IT NO SV FI DA Name Name of this device...

Страница 18: ...0 240min Float Voltage Float voltage 25 C see section 5 4 26 50V 16 32V Return to bulk V Return to bulk voltage If the battery voltage stays below this level for at least the Return to bulk delay tim...

Страница 19: ...s as an event source Bulk Bulk state of charge serves as an event source Abs Absorption state of charge serves as an event source Float Float state of charge serves as an event source Failure Any faul...

Страница 20: ...ne network Either do the configuration while connected to the network or use a prepared configuration file zcf Ensure that a DIP Switch is assigned Also see section 4 2 4 for a detailed description of...

Страница 21: ...den or grayed out 9 NMEA2000 Instances are used to differentiate between multiple monitoring sources 10 Press OK to return to the Module Modification window and press the Alarm Switch Settings button...

Страница 22: ...nds the ChargeMaster Plus will switch off the ChargeMaster Plus stops and the MODE LED illuminates red When the ChargeMaster Plus was switched off it can only be activated by pressing the ON OFF butto...

Страница 23: ...gure 6 3 step charge process The BULK phase is followed by the ABSORPTION phase Absorption charging starts when the voltage on the batteries has reached the BULK voltage and ends when the battery is c...

Страница 24: ...0V 100 of Imax 28 50 Limited by Pmax 5 5 DC Output 2 The ChargeMaster Plus is equipped with one full output DC 1 OUT and one secondary output DC 2 OUT The total output current is divided over these tw...

Страница 25: ...batteries 4 Switch the RCD Breaker of the AC input to the OFF position and if required disconnect the AC mains 5 Open the connection compartment of the ChargeMaster Plus 6 Check with a suitable volta...

Страница 26: ...r some time this will be higher Wrong setting of the charge voltage Check settings see chapter 4 Charge current too low Batteries almost fully charged Nothing this is normal when the battery is almost...

Страница 27: ...g network Ring networks are not allowed Check the connections of the network ChargeMaster Plus is not configured in CZone configuration file Open CZone Configuration Tool and check ChargeMaster Plus D...

Страница 28: ...ded Lithium ion Dimensions mm 383 252 126 383 252 126 Dimensions inch 15 1 9 9 5 0 15 1 9 9 5 0 Weight 6 3 kg 13 9 lbs 6 3 kg 13 9 lbs Recommended battery capacity 280 700Ah 400 1000Ah Power factor re...

Страница 29: ...User and Installation Manual 29 7 2 Dimensions Dimensions in mm inches ChargeMaster Plus models 24 80 2 24 110 2 7 3 Characteristics Output power versus input voltage Output power AC voltage V Figure...

Страница 30: ...30 ChargeMaster Plus 24 80 2 24 110 2 User and Installation Manual 3 step charging characteristics of flooded batteries Figure 9 3 step charging characteristics of flooded batteries...

Страница 31: ...ChargeMaster Plus 24 80 2 24 110 2 User and Installation Manual 31...

Страница 32: ...rvolt com Location Shipping Power Products LLC N85 W12545 Westbrook Crossing Menomonee Falls Wisconsin 53051 United States Asia Pacific Customer Service T 64 9 415 7261 Option 1 E enquiries bepmarine...

Отзывы: