  ChargeMaster Plus 24/80-2, 24/110-2 

 User and Installation Manual 

 

 

 

 

 

 

 

 

3.9

 

Commissioning after installation 

Check  the  wiring

;  positive  connected  to 

positive (red cables), negative connected to 
negative (black cables). 

When all wiring is OK, place the 

DC fuse

(s) 

to connect the batteries to the ChargeMaster 
Plus.  

 

WARNING! 

When  placing  this  fuse,  a  spark 
might  occur,  caused  by  the 
capacitors 

used 

in 

the 

ChargeMaster  Plus.  This  is 
particularly  dangerous  in  places 
with  insufficient  ventilation.  Due 
to the gassing of the batteries, an 
explosion  can  occur.  Avoid 

having flammable materials close 
by. 

Switch on the 

AC power

 supply. 

Note:

 when new, the ChargeMaster Plus will 

not start charging batteries before activated 
with the ON/OFF button. See step 6. 

Check the 

DIP switches

.  

See chapter DIP switch settings on page 15. 

Check  and  adjust  the  settings  of  the 
ChargeMaster  Plus  with 

MasterAdjust

 

(MasterBus  network)  or  with  the 

CZone 

Configuration Tool

 (CZone network). 

See chapter SETTINGS on page 15. 

When the settings meet the power system's 
needs, press and hold the 

ON/OFF

 button for 

3  seconds  to  switch  the  charger  on  and 
initiate the charging process. 

 

If required, use a small screwdriver to 
change DIP switch settings. See 
section 4.1. 

10 

Check all wiring; see also Figure 3 
for wiring details. If all wiring is OK: 
Place the DC fuses. 

11 

Close the connection compartment 
by fixing the screws. 

12 

Continue with section 3.9 for 
commissioning of the ChargeMaster 
Plus. 

Содержание CHARGEMASTER PLUS 24/110-2

Страница 1: ...te downloaden naar onze website Um diese Anleitung in anderen Sprachen herunterzuladen besuchen Sie bitte unsere Website Pour t l charger ce manuel dans d autres langues consultez notre site Web Para...

Страница 2: ...AC safety grounding 8 3 3 4 Network wiring CZone MasterBus 8 3 4 Batteries 9 3 5 Things you need 9 3 6 Overview of the connection compartment 10 3 7 Connection example 11 3 8 Installation step by step...

Страница 3: ...of the product Costs of labor or shipping are not covered by this warranty 1 4 Disclaimer Our products are subject to continual development and improvement Therefore additions or modifications to the...

Страница 4: ...be carried out only by qualified and trained personnel consistent with the locally applicable standards and regulations 9 Make sure that all wiring is properly installed in good electrical condition...

Страница 5: ...ay burst and cause injury to persons and damage to property Make sure lithium ion batteries used for this charger are certified to IEC standards 2 NEVER charge non rechargeable batteries 3 NEVER charg...

Страница 6: ...area around battery is well ventilated while battery is being charged 3 Clean battery terminals Be careful to keep corrosion from coming in contact with eyes 4 Add distilled water in each cell until...

Страница 7: ...clearance on every side If added to a CZone or MasterBus network take the network powering into consideration Never place the ChargeMaster Plus directly above the battery being charged as gases from b...

Страница 8: ...n of AC wiring and recommended wire colors 240VAC 50 60Hz installations Wire color Meaning Must be connected to Brown or black Phase L1 Blue Neutral N Green Yellow Earth PE GND 120VAC 50 60Hz installa...

Страница 9: ...ake sure the manufacturer s recommendations are met 3 5 Things you need Make sure you have all the parts you need to install the ChargeMaster Plus ChargeMaster Plus included Battery temperature sensor...

Страница 10: ...on negative output terminal 7 Safety ground connection 2 M6 Positive terminal charge output 2 DC 2 OUT 8 Network connection CZone MasterBus 3 Isolation walls for DC connections 9 Temperature sensor co...

Страница 11: ...ion Figure 3 Installation drawing of the ChargeMaster Plus Notes If the battery temperature remains within 15 25 C connection of the battery temperature sensor is optional Lithium ion batteries requir...

Страница 12: ...polarity may lead to serious damage to the batteries the ChargeMaster Plus the cabling and or the terminal connections Fuses between the batteries and the ChargeMaster Plus cannot prevent damage caus...

Страница 13: ...mp sense jack 7 Option Connect the ChargeMaster to the CZone or MasterBus network 8 Adding to a CZone network 1 Disconnect the backbone at the closest backbone connection and add in a tee connector 2...

Страница 14: ...n new the ChargeMaster Plus will not start charging batteries before activated with the ON OFF button See step 6 4 Check the DIP switches See chapter DIP switch settings on page 15 5 Check and adjust...

Страница 15: ...e CZone Configuration Tool Instructions manual for more information In a MasterBus network DIP switch 1 must always be set to the ON position 1 DIP switch 2 is MasterBus Powering ON 1 or OFF 0 DIP swi...

Страница 16: ...he main battery bank in C read only DC 1 OUT Output 1 Output state pre float on read only Output 1 V Voltage of charge output 1 read only Output 1 A Output current of charge output 1 read only Shunt d...

Страница 17: ...terBus DIP switch 1 must be in the ON position Parameter Meaning Factory setting Value range Device Language Menu language of this device English EN NL DE FR ES IT NO SV FI DA Name Name of this device...

Страница 18: ...0 240min Float Voltage Float voltage 25 C see section 5 4 26 50V 16 32V Return to bulk V Return to bulk voltage If the battery voltage stays below this level for at least the Return to bulk delay tim...

Страница 19: ...s as an event source Bulk Bulk state of charge serves as an event source Abs Absorption state of charge serves as an event source Float Float state of charge serves as an event source Failure Any faul...

Страница 20: ...ne network Either do the configuration while connected to the network or use a prepared configuration file zcf Ensure that a DIP Switch is assigned Also see section 4 2 4 for a detailed description of...

Страница 21: ...den or grayed out 9 NMEA2000 Instances are used to differentiate between multiple monitoring sources 10 Press OK to return to the Module Modification window and press the Alarm Switch Settings button...

Страница 22: ...nds the ChargeMaster Plus will switch off the ChargeMaster Plus stops and the MODE LED illuminates red When the ChargeMaster Plus was switched off it can only be activated by pressing the ON OFF butto...

Страница 23: ...gure 6 3 step charge process The BULK phase is followed by the ABSORPTION phase Absorption charging starts when the voltage on the batteries has reached the BULK voltage and ends when the battery is c...

Страница 24: ...0V 100 of Imax 28 50 Limited by Pmax 5 5 DC Output 2 The ChargeMaster Plus is equipped with one full output DC 1 OUT and one secondary output DC 2 OUT The total output current is divided over these tw...

Страница 25: ...batteries 4 Switch the RCD Breaker of the AC input to the OFF position and if required disconnect the AC mains 5 Open the connection compartment of the ChargeMaster Plus 6 Check with a suitable volta...

Страница 26: ...r some time this will be higher Wrong setting of the charge voltage Check settings see chapter 4 Charge current too low Batteries almost fully charged Nothing this is normal when the battery is almost...

Страница 27: ...g network Ring networks are not allowed Check the connections of the network ChargeMaster Plus is not configured in CZone configuration file Open CZone Configuration Tool and check ChargeMaster Plus D...

Страница 28: ...ded Lithium ion Dimensions mm 383 252 126 383 252 126 Dimensions inch 15 1 9 9 5 0 15 1 9 9 5 0 Weight 6 3 kg 13 9 lbs 6 3 kg 13 9 lbs Recommended battery capacity 280 700Ah 400 1000Ah Power factor re...

Страница 29: ...User and Installation Manual 29 7 2 Dimensions Dimensions in mm inches ChargeMaster Plus models 24 80 2 24 110 2 7 3 Characteristics Output power versus input voltage Output power AC voltage V Figure...

Страница 30: ...30 ChargeMaster Plus 24 80 2 24 110 2 User and Installation Manual 3 step charging characteristics of flooded batteries Figure 9 3 step charging characteristics of flooded batteries...

Страница 31: ...ChargeMaster Plus 24 80 2 24 110 2 User and Installation Manual 31...

Страница 32: ...rvolt com Location Shipping Power Products LLC N85 W12545 Westbrook Crossing Menomonee Falls Wisconsin 53051 United States Asia Pacific Customer Service T 64 9 415 7261 Option 1 E enquiries bepmarine...

Отзывы: