Mastervolt AGM SL Series Скачать руководство пользователя страница 2

ENGLISH 

 

 

Observe these instructions and keep them 
located near the battery for future reference. 
Work on the battery should only be carried out 
by qualified personnel. 

 

 

Explosion and fire hazard. Do not short circuit, 
use insulated tools. 

 

 

Do not smoke or introduce sparks in the 
vicinity of the battery. Explosion and fire 
hazards are present.

 

 

 

Electrolyte is strongly corrosive. Under normal 
conditions contact with electrolyte is impossible. 
If the housing is damaged the electrolyte can be 
available. 

 

While working on batteries wear protective 
eye-glassing and clothing. Observe accident 
protection rules. 

 

 

Batteries are heavy. Ensure adequate mounting 
security and always use suitable handling 
equipment for transportation. Batteries must be 
transported in an upright position. 

 

Any acid splashes on the skin or in the eyes 
must be flushed with plenty of water 
immediately. Then seek medical assistance. 
Spillages on clothing should be rinsed out with 
water. 

 

 

Metal parts of the battery are always alive. Do 
not place tools or other items on the battery. Do 
not wear any metallic items such as watches, 
bracelets, et cetera. 

 

 

 

 

 

General 

Mastervolt AGM batteries are immediate ready for use.  

Installation 

  Prior to installation check battery for mechanical 

damages.  

  Recommended torque for screw connections: 35 to 48 

InLbs / 3.9 to 5.4 Nm. 

  Installation angle of the battery: 180º. Installation in 

upright position is recommended. 

  Keep >0.5 inch / >1cm space between the batteries.  

  Keep away from heat sources.  

  Allowed operating temperature: 

–4 to 131ºF / –20 to 

55ºC; Nominal operating temperature: 41 to 95ºF / 5 to 
35ºC. Recommended at 77ºF / 25ºC. The battery life is 
halved for every 18 ºF / 10ºC of rise in temperature. 
Lower temperatures will reduce the available capacity 

  Under overcharging conditions lead acid batteries can 

vent an explosive mixture of hydrogen gas. If contained, 
assure adequate ventilation.  

  Clear the terminals before connection.  

  During installation all loads and chargers must be 

switched off.  

  Use properly sized and reliable cable lugs and battery 

terminals. Tighten all connections firmly.  

 

Connect the battery with correct polarity. The 
position of the battery poles may differ from previous 
installed batteries!  

  Connect the minus cable last of all.  

  Use protective battery terminal insulators.  

  Batteries in series or parallel must be of the same brand, 

type, capacity and state of charge. Do not mix old and 
new batteries. See figure 1 to 4 if batteries must be 
connected in parallel or in series.  

 

Charging 

Use only chargers with IUoUo characteristic.  
Voltage  settings:  float  charge  13.80V  @  77ºF  /  25ºC; 
absorption  charge  14.25V  @  77ºF  /  25ºC  (max  5  hrs). 
Temperature compensated charging is recommended  
(

–17mV/ºF or –30mV/ºC).  

Maximum charge current: 30% of rated capacity @ C10. 
Incomplete charges may damage the batteries. Therefore the 
batteries must be charged to the full 100% regularly, at least 
every month.  

Discharge 

Avoid deep discharges. Regular discharges beyond 50% of 
the nominal capacity are not recommended as they might 
shorten the lifetime of the battery.  
Recharge the battery immediately after a discharge. Never 
discharge below the final discharge voltage. The final 
discharge voltage is related to the discharge current. See 
table 

“Final discharge voltage”.  

Maintenance 

Check  batteries  and  connections  on  a  regular  base,  at  least 
every  three  months.  Defects  such  as  loose  or  corroded 
connections must be corrected immediately.  
Keep battery in charged condition.  
Elevated  environmental  temperatures  increase  the  self-
discharge rate of the batteries. 

See “Battery storage” 

Batteries should be recharged  when the open circuit voltage 
drops below 12.3 Volt.  
Keep  the  battery  dry  and  clean. Use  only  a  wet  soft  cloth  to 
clean  the  battery.  Never  use  any  additives,  acids  and/or 
scourers.  
Do not open the battery. Never add acid or distilled water.  

Disposal of batteries 

Spent batteries are harmful to health and the 
environment. Therefore batteries may not be 
mixed with domestic or industrial waste but must 
be collected and recycled separately. Contact 
your supplier for recollection and recycling of 
batteries or contact an authorized waste 
management company. 
 

Содержание AGM SL Series

Страница 1: ...ANUAL DE UTILIZACION AGM SL BATTERY Models AGM SL 12 150Ah 12 200Ah Mastervolt Inc N86 W12500 Westbrook Crossing Menomonee Falls WI 53051 USA Tel 1 443 459 5370 Fax 1 443 459 5367 www mastervolt com 1...

Страница 2: ...be switched off Use properly sized and reliable cable lugs and battery terminals Tighten all connections firmly Connect the battery with correct polarity The position of the battery poles may differ...

Страница 3: ...an fiables y del tama o adecuado Las conexiones se deben apretar firmemente Habr que conectar la bater a con la polaridad correcta La posici n de los polos de la bater a puede ser diferente a la de la...

Страница 4: ...be crosswise Las conexiones de los cables positivos y negativos deben ser del tipo de cruzamiento 12V 600Ah Figure 4 Figura 4 Maximum number of batteries 4 N mero m ximo de bater as 4 12V 300Ah Figur...

Страница 5: ...Ah 200 Ah Reserve capacity 250 min 420 min Number of cells per battery 6 6 Maximum charge current 43 Amps 53 Amps Approximate weight 97 Lbs 43 8 kg 113 Lbs 51 2 kg Terminal threaded insert stud M6 M6...

Страница 6: ...54 5 39 4 31 4 25 9 22 6 17 5 14 3 7 64 SL 12 200Ah 336 2 278 9 210 7 157 8 126 0 72 9 52 6 42 1 34 7 30 3 23 4 19 2 10 21 Final voltage V 10 5V Time minutes 10 15 20 30 45 60 120 180 240 300 360 480...

Страница 7: ...DIMENSIONS Dimensions in mm inch See www mastervolt com batteries for detailed drawings Battery casing material ABS 63001500 AGM SL 150Ah 63001851 AGM SL 200Ah...

Страница 8: ...ransfer distribution or storage of part or all of the contents in this document in any form without the prior written permission of Mastervolt is prohibited Mastervolt cannot be held liable for possib...

Отзывы: