CONSTANT CURRENT DISCHARGE
1.85V/cell – Discharge in A @ 20°C / 68°F
Type
Time (minutes) 5
10
20
30
60
180
300
480
600
MVG 12/25
41.1
36.2
24.8
20.5
13.1
5.80
3.90
2.50
2.10
MVG 12/55
99.2
83.1
59.1
46.4
32.7
13.6
9.00
6.00
4.90
MVG 12/85
168
141
100
78.0
53.0
22.0
14.2
9.40
7.70
MVG 12/120
257
201
135
104
65.5
27.8
18.1
11.9
9.80
MVG 12/140
275
220
151
118
75.1
32.5
21.3
14.0
11.5
MVG 12/200
329
274
196
160
104
46.6
31.0
20.4
16.7
1.80V/cell – Discharge in A @ 20°C / 68°F
Type
Time (minutes):
5
10
20
30
60
180
300
480
600
MVG 12/25
46.1
38.8
27.0
21.3
13.8
6.00
4.00
2.60
2.20
MVG 12/55
114
89.8
65.3
50.2
34.2
14.0
9.20
6.10
5.00
MVG 12/85
193
154
112
85.0
56.0
23.0
14.7
9.80
8.00
MVG 12/120
293
221
147
112
69.5
28.9
18.6
12.3
10.2
MVG 12/140
315
244
166
128
79.7
33.8
22.0
14.5
11.9
MVG 12/200
381
313
222
176
110
48.5
32.0
21.1
17.3
1.75V/cell – Discharge in A @ 20°C / 68°F
Type
Time (minutes):
5
10
20
30
60
180
300
480
600
MVG 12/25
54.2
41.4
28.6
21.9
14.2
6.10
4.00
2.70
2.20
MVG 12/55
139
99.0
69.5
52.5
35.0
14.2
9.30
6.20
5.10
MVG 12/85
226
169
120
90.0
58.0
23.0
15.0
9.90
8.10
MVG 12/120
330
235
155
116
71.6
29.5
19.0
12.6
10.5
MVG 12/140
357
264
176
133
82.3
34.5
22.3
14.8
12.2
MVG 12/200
437
349
237
183
115
49.7
32.3
21.5
17.7
1.70V/cell – Discharge in A @ 20°C / 68°F
Type
Time (minutes):
5
10
20
30
60
180
300
480
600
MVG 12/25
61.7
43.3
29.6
22.4
14.4
6.20
4.10
2.70
2.20
MVG 12/55
151
106
72.0
53.9
35.5
14.3
9.30
6.20
5.10
MVG 12/85
244
182
125
93.0
59.0
23.0
15.1
9.90
8.10
MVG 12/120
367
249
161
119
73.1
29.9
19.2
12.8
10.5
MVG 12/140
397
282
183
137
84.1
35.1
22.6
15.0
12.2
MVG 12/200
486
380
251
191
117
50.6
32.8
21.8
17.7
1.65V/cell – Discharge in A @ 20°C / 68°F
Type
Time (minutes):
5
10
20
30
60
180
300
480
600
MVG 12/25
67.5
45.4
30.2
22.7
14.4
6.20
4.10
2.70
2.20
MVG 12/55
161
112
73.6
54.7
35.7
14.4
9.30
6.20
5.10
MVG 12/85
259
192
128
94.0
59.0
24.0
15.1
9.90
8.10
MVG 12/120
387
260
165
122
74.0
30.1
19.2
12.8
10.5
MVG 12/140
423
294
189
141
85.4
35.4
22.6
15.0
12.2
MVG 12/200
531
395
262
198
120
51.0
32.8
21.8
17.7
1.60V/cell – Discharge in A @ 20°C / 68°F
Type
Time (minutes):
5
10
20
30
60
180
300
480
600
MVG 12/25
71.8
46.9
30.7
22.9
14.5
6.20
4.10
2.70
2.20
MVG 12/55
169
116
74.6
55.2
35.8
14.4
9.30
6.20
5.10
MVG 12/85
273
199
130
95.0
60.0
24.0
15.1
9.90
8.10
MVG 12/120
409
267
168
124
74.7
30.2
19.2
12.8
10.5
MVG 12/140
452
303
193
143
86.3
35.4
22.6
15.0
12.2
MVG 12/200
581
411
269
202
121
51.1
32.8
21.8
17.7
BATTERY STORAGE
The rate of self discharge is approximately 2% per month
@ 20ºC/68°F. Therefore batteries need supplementary
charge according to the table below to keep its capacity.
Storage temperature
Charging interval
< 20ºC / < 68 ºF
Every 24 months
20 to 30 ºC / 68 to 86 ºF
Every 12 months
30 to 40 ºC / 86 to 104 ºF
Every 6 months
40 to 50 ºC / 104 to 122 ºF
Every 3 months
100%
75%
20ºC (68ºF)
50%
30ºC (86ºF)
40ºC (104ºF)
25%
0%
0
4
8
12
16
20
24
Storage time (months)
Remaining capa
city