14

 

Lay the positive and negative cables next to each other to 

limit  the  electromagnetic  field  around  the  cables.  The 

negative  cable  should  be  connected  directly  to  the 

negative  post  of  the  battery  bank  or  the  ground  side  of  a 

current  shunt.  Do  not  use  the  chassis  frame  as  the 

negative conductor. Tighten securely. The positive battery 

cable must be fused and connected to the positive post of 

the battery bank.  

 

The recommended DC fuses for outputs 1, 2 and 3 are: 

 

ChargeMaster Plus model 

DC fuse 

12/75-3 

85A 

12/100-3 

125A 

24/40-3 

50A 

24/60-3 

80A 

 

The  fuse  with  the  fuse-holder  is  available  from  your  local 

Mastervolt distributor or Customer Service Representative. 

 

4.3.2 

AC-wiring  

 

WARNING! 

The  ground  wire  offers  protection  only  if  the 

enclosure  of  the  ChargeMaster  Plus  is 

connected  to  the  safety  ground.  Connect  the 

ground terminal (PE / GND) to the hull or the 

chassis. 

 

CAUTION! 

According to local regulations a RCD/Breaker 

must  be  placed  in  the  AC  input  circuit  of  the 

ChargeMaster Plus. 

 

For  a  safe  installation  the correct  wire  cross section  must 
be applied. Don’t use a cross section that is smaller than 
indicated. See table below to select the appropriate  cross 

section for the AC wiring (up to 6m / 20ft length): 

 

AC-Current 

Minimum cross section: 

 

in mm² 

AWG 

6-12 Amp 

1.5 mm² 

AWG 14 

12-20 Amp 

2.5 mm² 

AWG 12 

20-32 Amp 

4.0 mm² 

AWG 10 

 

Connection of AC-wiring and recommended wire colours:  

  230V/50Hz installations: 

Wire color 

Meaning 

Must be 

connected to:  

Brown or black 

Phase  

L1 

Blue 

Neutral 

Green/Yellow 

Earth 

PE / GND 

 

  120V/60Hz installations (single phase): 

Wire color 

Meaning 

Must be 

connected to:  

Black 

Hot or Line  

L1 

White 

Neutral 

Green 

Ground 

PE / GND 

 

4.3.3 

AC safety grounding  

 

WARNING! 

The  ground  wire  offers  protection  only  if  the 

enclosure  of  the  ChargeMaster  Plus  is 

connected  to  the  safety  ground.  Connect  the 

ground terminal (PE / GND) to the hull or the 

chassis.  

 

CAUTION! 

For safe installation it is necessary to insert a 

Residual  Current  Device  (earth  leakage 

switch)  in  the  AC  input  circuit  of  the 

ChargeMaster Plus. 

 

4.4 

BATTERIES 

Always  follow  the  instructions  published  by  battery 

manufacturer.  

ChargeMaster 

Plus model 

Recommended battery capacity 

12/75-3 

140Ah 

800Ah 

12/100-3 

200Ah 

1000Ah 

24/40-3 

80Ah 

400Ah 

24/60-3 

120Ah 

500Ah 

 

4.5 

THINGS YOU NEED 

Make  sure  you  have  all  the  parts  you  need  to  install  the 

ChargeMaster Plus: 

  ChargeMaster Plus (included) 

  Battery  temperature  sensor  with  cable  and  plug 

(included). 

  DC  cables  to  connect  the  ChargeMaster  Plus  to  the 

batteries  and  common  negative;  see  section  4.3.1  for 

specifications 

  DC-fuse holder with a DC-fuse, to be integrated in the 

positive DC-cable; see section 4.3.1 for specifications 

  Screws  /  bolts  (Ø  6mm)  (with  plugs)  to  mount  the 

enclosure  to  a  surface.  Use  mounting  materials  which 

are  suitable  to  carry  the  weight  of  the  ChargeMaster 

Plus 

  AC  cable  to  connect  the  AC  input  to  an  AC  power 

source. See section 4.3.2. 

  Batteries; see section 4.4 

  Appropriate  and  reliable  cable  terminals,  cable  lugs, 

battery terminals and cord end terminals 

 

We recommend as a minimum tool kit:  

  Socket wrench 13mm to fix the main DC-cables  

Содержание 44310750

Страница 1: ...ASTERVOLT Snijdersbergweg 93 1105 AN Amsterdam The Netherlands Tel 31 20 3422100 Fax 31 20 6971006 www mastervolt com Copyright 2017 Mastervolt 10000011898 09 ENGLISH NEDERLANDS See www mastervolt com...

Страница 2: ...WARNING REGARDING LIFE SUPPORT APPLICATIONS 7 2 12 GUARANTEE SPECIFICATIONS 7 2 13 CORRECT DISPOSAL OF THIS PRODUCT 7 3 OPERATING INSTRUCTIONS 8 3 1 FEATURES 8 3 2 LOCAL USER INTERFACE 9 3 2 1 SWITCH...

Страница 3: ...4 10 DECOMMISSIONING 20 4 11 STORAGE AND TRANSPORTATION 20 4 12 RE INSTALLATION 20 5 SETTINGS 21 5 1 DIP SWITCH SETTINGS 21 5 2 MASTERBUS FUNCTIONS 21 5 2 1 MASTERBUS COMMUNICATION 21 5 2 2 CURRENT CO...

Страница 4: ...for the following models with apparatus version A and higher see section 1 4 Part number Model 44310750 ChargeMaster Plus 12 75 3 44311000 ChargeMaster Plus 12 100 3 44320400 ChargeMaster Plus 24 40...

Страница 5: ...9 Except for the connection compartment see chapter 4 the ChargeMaster Plus may not be opened or disassembled There are no serviceable parts inside the cabinet Take it to a qualified authorized and t...

Страница 6: ...e handling equipment for transportation 2 5 CHARGER LOCATION 1 Locate charger as far away from battery as dc cables permit 2 Never place charger directly above battery being charged gases from battery...

Страница 7: ...STRUCTIONS This battery charger should be connected to a grounded metal permanent wiring system or an equipment grounding conductor should be run with circuit conductors and connected to equipment gro...

Страница 8: ...AFE CHARGE Quickly recognizes the State of Charge The ChargeMaster Plus will prevent unnecessary charging overcharge of your batteries The ChargeMaster Plus will detect previous charges and will reduc...

Страница 9: ...e MODE switch pressed again for approx 3 seconds the ChargeMaster Plus will switch back to stand by the ChargeMaster Plus stops and the MODE LED illuminates red WARNING Switching the ChargeMaster Plus...

Страница 10: ...age Blinking slow green Battery absorption stage Solid green Battery in float stage Battery III Blinking medium fast green Battery in bulk stage Blinking slow green Battery absorption stage Solid gree...

Страница 11: ...nsumption decreases the charger goes back to normal operation of the three step charge system As the ChargeMaster Plus is equipped with a three step plus charge system the batteries can also remain co...

Страница 12: ...ve Relay When there is no AC power available and the alternator is charging the starter battery the alternator can also be used to charge battery 1 2 The threshold voltage which is used to switch over...

Страница 13: ...us straight above the batteries because of possible corrosive sulphur fumes If the ChargeMaster Plus is installed in the immediate vicinity of living areas take into account that the fan of the Charge...

Страница 14: ...connected to Brown or black Phase L1 Blue Neutral N Green Yellow Earth PE GND 120V 60Hz installations single phase Wire color Meaning Must be connected to Black Hot or Line L1 White Neutral N Green G...

Страница 15: ...compartment 4 6 OVERVIEW CONNECTION COMPARTMENT 1 Screw terminals AC input 7 Common negative output terminal 2 Cable clip for AC wiring 8 Ventilation openings 3 Isolation walls for DC connections 9 DI...

Страница 16: ...revent damage caused by reversed polarity The damage as a result of reverse polarity is detectable by the service department and is not covered by the warranty CAUTION Too thin cables and or loose con...

Страница 17: ...matic is to illustrate the general placement of the Chargemaster Plus in a circuit It is not meant to provide detailed wiring instructions for any particular electrical installation Figure 6 installat...

Страница 18: ...is suspended from the mounting bracket 3 Open the connection compartment by loosening the two screws 4 Fix the enclosure to the wall by fastening two screws at the lower side of the enclosure as well...

Страница 19: ...other settings can only be made after commissioning 4 9 2 Commissioning step by step CAUTION Check the polarity of all wiring before commissioning positive connected to positive red cables negative c...

Страница 20: ...ontrol panel to change these settings 4 10 DECOMMISSIONING If it is necessary to put the ChargeMaster Plus out of operation follow the instructions in order of succession as described below 1 Switch t...

Страница 21: ...argeMaster Plus can be made via the MasterBus network by means of a remote control panel or an interface connected to a PC with MasterAdjust software Some settings can only be changed via the MasterBu...

Страница 22: ...e main battery bank in C read only Output 1 Output 1 Output state Off pre float on read only Output 1 Voltage of charge output 1 read only Output 1 Output current of charge output 1 read only Shunt de...

Страница 23: ...read only Smart terminal Highest voltage Highest detected DC voltage output 1 read only Lowest voltage Lowest detected DC voltage output 1 read only Total Ah s Total charged Ah s read only Total Ah s...

Страница 24: ...tion 3 4 13 25 26 50V 0 15 50 0 31 00V Return to bulk Return to bulk voltage If the battery voltage stays below this level for at least the Return to bulk delay time the charger will start the Bulk st...

Страница 25: ...e Event x 5 2 11 Events source The ChargeMaster Plus can be configured as an event source an event source can be used to initiate an event command and an event action by another device that is connect...

Страница 26: ...command and an event action to be performed by the ChargeMaster Plus Event command Description State Command to switch on the ChargeMaster Plus Bulk Command to start the Bulk state of charge Abs Comma...

Страница 27: ...voltages the charge current is reduced Check AC input voltage Batteries not fully charged Charge current too low See Charge current too low in this table Current to load is too high Reduce load taken...

Страница 28: ...r defined AGM GEL Flooded AGM Spiral Flooded traction Flooded calcium MLi Dimensions mm 383x250x126 383x250x126 Dimensions inch 15 0x9 8x5 0 15 0x9 8x5 0 Weight 7kg 16Lbs 7kg 16Lbs Recommended battery...

Страница 29: ...fined AGM GEL Flooded AGM Spiral Flooded traction Flooded calcium MLi Dimensions mm 383x250x126 383x250x126 Dimensions inch 15 0x9 8x5 0 15 0x9 8x5 0 Weight 7kg 16Lbs 7kg 16Lbs Recommended battery cap...

Страница 30: ...30 7 3 DIMENSIONS Dimensions in mm ChargeMaster Plus models 12 75 3 12 100 3 24 40 3 and 24 60 3 185 231 12 250 383 13 126...

Страница 31: ...nt 500 DC distribution module for exact readout of battery voltage charge discharge current and state of charge on the display of the ChargeMaster Plus continuous rating 250A peak current 500A 8 2 MIS...

Отзывы: