6/17 Rev. E 57-02410
7
MECHANICAL
Remove front grille and check refrigeration lines to see that they are free (not touching each other or compressor).
Spin condenser fan blade to see that it is free.
Check that all service valves (3) are open. Remove wooden shipping blocks under compressor. Check all
refrigeration lines and electrical conduit for rubbing or chaffing, paying particular attention to area where lines enter
the cabinet. Make sure the compressor switch is on before start up the cabinet.
After removering the wooden blocks, the compressor
should move freely on its mounting springs.
Remove cabinet from crate base and slide into location. Cabinet must be level from side to side and front to back for
correct draining of coil pan and for self-closing doors to operate correctly. Allow minimum of 4” between back of
cabinet and wall and between top of cabinet and ceiling for proper condensing unit air circulation.
To comply with Sanitation requirements the cabinet must be mounted on legs (6” high min.) or casters or the base
must be sealed to the floor with an N.S.F. listed silicone sealant.
To comply with UL requirements the cabinet must have a minimum clearance of 4” at the top, 6” at the rear and 0” at
each side.
ELECTRICAL
WARNING
Before servicing electrical components in the case or the doors or door frames make sure all power to case
is ff. Always use a qualified technician.
Check voltage and amps drawn on (Page 17) to determine proper line and fuse or circuit breaker size. Check power
supply for low voltage. If voltage reads “230” with no load, and it drops below “207” when the compressor tries to
start, it is an indication of too small supply wiring or too long to run.
It is recommended that a separate circuit be run for each cabinet to prevent another appliance blowing the fuse or
breaker, causing loss of product.
*
*The cabinet should be grounded.**
Содержание IHC-27
Страница 2: ...6 17 Rev E 57 02410 2 ...