RECOMMENDED FLUES FOR AUSTRALIA

ARCADIA:

Floate Metal - Flomet 5” Super Single with 180• polished stainless steel flue heat 
shield.
Shamic 1A with 900mm 180• polished stainless steel flue heat shield.

UTOPIA Ser 2: Acorn Metal Products - Special Insulated kit with 900mm 120• polished reflector and 

425 dia. ceiling plate.
Floate Metal - Flomet Super Single with full length decorative heat shield with 120• 
solid back.
Statewide Heating - Model M1 with 900mm enamelled flue shield.
Woodland Fireplaces - Woodland Standard Flat Ceiling Plate flue kit with 900mm 
enamelled flue shield.

WALL SHIELDING

The minimum distances between the heater and heat sensitive walls, (shown in the
Table on page 4), may be reduced significantly by fitting suitable heat shield(s) on the
adjacent wall(s). Shields must be made of heat resistant material (such as Harditherm or
Supalux) and they must be mounted on the wall on non-combustible spacers arranged
to not obstruct the vertical flow of cooling air behind them. Shields mounted against the
wall are virtually useless.
Ventilation slots must be provided at the top and bottom of each shield, each slot
having a cross-sectional area not less than half the width of the shield multiplied by the
spacing depth. The slots should, as far as possible, extend across the full width of the
shield.
EXAMPLE: A 1200mm wide shield spaced 25mm from the wall must have ventilation
slots, top and bottom, each of an area not less than  600 x 25 mm

2

,  i.e. 15,000mm

2

. So

if the effective length of each slot is 1m, it will need to be 15mm wide
Three types of shield are recommended:-

Type

Layers

Spacing

Clearance Factor

A

One

12mm

0.4 *

B

One

25mm

0.3 *

C

Two

12 & 12mm

0.2 *

* Valid only for shields within 45• of vertical.

To find the reduced minimum distances, multiply the figures in columns A, B and E
(from the Table on page 4) by the appropriate clearance factor.

EXAMPLE: An Arcadia in New Zealand, mounted parallel to the wall, has a normal
minimum rear clearance of 300mm and a side clearance of 512mm. The reduced
minimum clearances for type A shielding would be 300 x 0.4 (120mm) at the rear, and
512 x 0.4 (205mm) at the side.

NOTE: The original heater shields and flue heat shield must still be

fitted to the heater when the above factors are used.

WALL SHIELD SIZES
Shields must extend at least 600mm each side of the heater centreline on side and rear
walls, or in the case of a corner installation, 1200mm each way from the corner. They
must be at least 1200mm high (measured from the hearth top).

Because the reduced wall clearances will bring the flue close to the rear wall, (in the
case of a parallel installation), it will be necessary to extend the wall shield upwards to
protect the wall for at least 300mm each side of the flue centreline. The extended rear
wall shield will, of course, finish just clear of the ceiling to provide the top ventilation
slot described above.

WALL SHIELD FINISHES

Because the outer surface of the wall shield will become quite hot, any surface finish
must not be heat sensitive. Possibilities are high temperature paints or cladding with
ceramic tiles, slate etc.

                      5

Содержание ARCADIA

Страница 1: ...ARCADIA UTOPIA UTOPIA Series 2 GRAND UTOPIA SOLID FUEL HEATERS INSTALLING AND OPERATING INSTRUCTIONS 585877 ...

Страница 2: ...ou should approach your local Building Authority before commencing installation to establish whether you will require a Permit and whether you will need to meet extra requirements MASPORT radiant heaters have been tested to ensure that they will meet the appropriate safety Standard requirements if the instructions in this book are followed PLEASE ENSURE THAT ONLY COMPONENTS APPROVED BY MASPORT ARE...

Страница 3: ...lign with the back edge of the top of the heater and the extension should fit snugly against the top casting Raise the heater into its upright position again taking care not to damage the floor Before fitting the firebox ceiling baffle first locate the four support lugs which will support it near the top of the firebox Insert the baffle into the firebox ensuring that the curved centre section is a...

Страница 4: ...nts for a fireplace installation Finalise the installation position for your woodfire only after considering the necessary heater to wall distances see below and checking the practicability of installing the flue system through the ceiling and roof or wall As a guide the flue shielding and the 25mm clearance gap around it in the ceiling space will occupy a diameter of approximately 300mm and this ...

Страница 5: ... 25 mm2 i e 15 000mm2 So if the effective length of each slot is 1m it will need to be 15mm wide Three types of shield are recommended Type Layers Spacing Clearance Factor A One 12mm 0 4 B One 25mm 0 3 C Two 12 12mm 0 2 Valid only for shields within 45 of vertical To find the reduced minimum distances multiply the figures in columns A B and E from the Table on page 4 by the appropriate clearance f...

Страница 6: ...A G H J G l a ss W 360 min Wall Minimum dims for A are on page 4 See Notes below MINIMUM HEARTH EXTENSIONS mm WHEN THE REAR HEAT SHIELD IS FITTED Rear Heat Shield W B C D G H J Australia New Zealand New Zealand hearth flush hearth 50mm high Arcadia Utopia Arcadia Utopia Arcadia Utopia 855 635 300 165 150 335 525 1075 760 425 275 150 335 525 975 680 345 225 150 335 525 1165 980 550 275 155 430 615 ...

Страница 7: ...X Y NOTE YOUR SPECIFIC MEASUREMENT FOR E MUST BE ADDED TO X AND Y TO FIND THE APPROPRIATE MINIMUM HEARTH DIMENSIONS SEE PAGE 4 FOR MINIMUM VALUES OF E MINIMUM DIMENSIONS Millimetres Australia 750 430 New Zealand hearth 50mm high New Zealand hearth flush Arcadia Utopia Utopia Utopia Arcadia Arcadia 800 540 750 470 1050 730 1000 680 850 550 HEARTH CONSTRUCTION In Australia the minimum hearth constru...

Страница 8: ...Australia Not less than 18mm thickness of fibre cement board New Zealand Two sheets of MICORE160 or one sheet of WOODTEX 35 thick Ceramic tiles Trim moulding Recommended hearth constructions are FITTING A WATER COIL Water heating coils can be fitted to Arcadia and Utopia heaters The pipe attachment positions are shown below B Heater A B Arcadia Utopia 280 310 590 520 C Alternate flue position at r...

Страница 9: ...apter 7 1985 except that the specified separation between the outside of the chimney and timber construction need not be complied with A flue pipe must be fitted right up the chimney and the space between the flue pipe and chimney must be ventilated at the top In Australia the area of this vent must be not less than 10 000mm2 while in New Zealand it is 13 000mm2 The vent must be fitted with means ...

Страница 10: ...ing instructions will ensure satisfactory performance The use of wood with greater than 25 moisture is not permitted MAKE SURE THE MINIMUM HEATER TO WALL DISTANCES SHOWN ON PAGE 4 ARE ALWAYS MAINTAINED BETWEEN THE HEATER AND ANY HEAT SENSITIVE MATERIAL SUCH AS FURNITURE WINDOW DRAPES FUEL ETC DO NOT ATTEMPT TO BURN LIQUID FUELS OF ANY KIND LIGHTING UP Before lighting the first fire spread the sand...

Страница 11: ...LED YOU MAY HAVE TO LEAVE A DOOR SLIGHTLY OPEN AND PERHAPS A WINDOW ELSEWHERE IN THE HOUSE IF YOUR HOME IS OF MODERN AIRTIGHT CONSTRUCTION LEAVING THE DOOR OPEN WILL HELP SPREAD WARMTH THROUGH THE REST OF YOUR HOME SAFETY Always keep children well away from the heater when it is alight as surfaces on radiant heaters can become very hot If children or aged and infirm persons might accidentally touc...

Страница 12: ...sote and soot build up are inadequate draught smoking when the door is opened and a dull thud when the outside of the flue is tapped A blocked flue can be cleaned only by sweeping DO NOT USE CHEMICAL CHIMNEY CLEANERS To facilitate flue cleaning the firebox ceiling baffle should be lifted out See ASSEMBLY page 3 for instructions on re fitting the baffle correctly CLEANING THE HEATER Usually a wipe ...

Отзывы: