UNIVERSAL TRANSMITTER UT-94
REF NO: m98A/om/101
Issue NO: 15
User’s Manual Page 19 of 25
Note:
a)
Display on UT-94 will show
“over”
when process value is higher than 5 % of individual span, at that
time UT-
94 will send ‘32766’ to PC. (Not applicable for linear inputs)
b)
Same way when process value is lower than 5 % of individual zero UT-94 will show
“under”
on its
display but it will send
‘32765’ to PC. (Not applicable for linear inputs)
c)
If UT-94 process value is out of limit for particular I/P type then UT-
94 will show “Open” on display but
it will send ‘32767’ to PC
d)
The serial no of UT-94 Indicators must be within 001 to 247.
e)
Before starting the communication, match the Baud rate and Sr. no. of Master and Slave devices.
f)
When process value is lower than minimum value of input range, UT-94 will show value up to 5% of
input range for input type 1-5V,4-20mA,0.4-2V .
g)
When process value is greater than maximum value of input range, UT-94 will show value up to 5% of
input range for input type 1-5V,4-20mA,0.4-2V, 0-5V,0-20mA,0-10V,0-2V.
h)
When process value is lower than minimum value of input range, UT-94 will show zero value (lower
range) for input type 0-5V,0-20mA,0-10V,0-2V.