Model: TC5396
masibus
Doc. Ref. no. : - m105/om/101
Issue no. 00
User’s Manual
Page 20 of 40
6.6 LEVEL 4 ALARM MODE
ALARM PARAMETERS
Parameter
(PV display)
Setting Name & Description
Default
Value
Show if
Only
Reg.
No.
Symbol
Name
A1TP
(
a1tp
)
Alarm Type
–
1
6
(PVAL)
Output Type
is LIN(Linear)
34
A1HY
(
a1HY
)
Alarm 1
Hysteresis
Set Hysteresis(in °C) for Alarm-1
1 to 250
TC & RTD Input
0.1 to 25.0
RTD.1 Input
1 to 250
Linear Input with DP=0
0.1 to 25.0
Linear Input with DP=1
0.01 to 2.50
Linear Input with DP=2
0.001 to 0.250
Linear Input with DP=3
1
Output Type
is LIN(Linear)
35
A1LC
(
a1lC
)
Alarm 1 Logic
Set Logic for Alarm-1
norm
/
flsf
0 : NORM (Normal)
1 : FLSF (Fail-Safe)
Operation diagram of different
for Alarm Logic NORM (Normal). For Fail-Safe Logic
Alarm will work completely opposite to Normal
behavior. (i.e. for any particular condition when Relay
is ON for Normal logic, for that condition relay will
OFF for Fail-Safe Logic & vice-versa)
0
(Normal)
Output Type
is LIN(Linear)
36
A1DY
(
a1dy
)
Alarm 1
Delay
Alarm Delay is amount of time (in sec), that
Relay-1 will wait before getting ON after the
alarm condition occurs.
1 to 99 sec
1
Output Type
is LIN(Linear)
37
A2TP
(
a2tp
)
Alarm Type
–
2
6
(
PV.A.L.))
Output Type
is not VPFN
38
A2HY
(
a2Hy
)
Alarm 2
Hysteresis
Set Hysteresis(in °C) for Alarm-2
1
Output Type
is not VPFN
39
A2LC
(
a2lC
)
Alarm 2 Logic
Set Logic for Alarm-2
norm
/
flsf
0 : NORM (Normal)
1 : FLSF (Fail-Safe)
0
(Normal)
Output Type
is not VPFN
40
A2DY
(
a2.Dy
)
Alarm 2
Delay
Alarm Delay is amount of time (in sec), that
Relay-2 will wait before getting ON after the
alarm condition occurs.
1 to 99 sec
1
Output Type
is not VPFN
41
A3TP
(
a3tp
)
Alarm Type
–
3
6
(PV.A.L.)
Output Type
is LIN(Linear)
42
A3HY
(
a3HY
)
Alarm 3
Hysteresis
Set Hysteresis(in °C) for Alarm-3
1
Output Type
is LIN(Linear)
43
A3LC
(
a3lC
)
Alarm 3 Logic
Set Logic for Alarm-3
norm
/
flsf
0 : NORM (Normal)
1 : FLSF (Fail-Safe)
0
(Normal)
Output Type
is LIN(Linear)
44