Marvair 8AA1024A-1060A & 8AA2036A-2060A I&O Manual
03/2021 Rev.1
7
MODEL
0.10
0.15
0.20
0.25
0.30
0.40
0.50
8AA1024A
800
785
770
725
680
600
500
8AA1030A
1200
1150
1100
1050
1000
900
800
8AA1036A
1290
1230
1170
1115
1060
1000
920
8AA1042A
1500
1430
1360
1295
1230
1160
1070
8AA1048A
1900
1850
1800
1700
1600
1500
1350
8AA1060A
1900
1850
1800
1700
1600
1500
1350
8AA2036A
1290
1230
1170
1115
1060
1000
920
8AA2042A
1500
1430
1360
1295
1230
1160
1070
8AA2048A
1900
1850
1800
1700
1600
1500
1350
8AA2060A
1900
1850
1800
1700
1600
1500
1350
Values in bold are the minimum air flow.
Air flow ratings of 208-230 volt units are at 230v. Air flow ratings of 460 volt units are at 460 volts. Operation of units at a voltage
different from the rating point will affect air flow.
Table 1. CFM @ External Static Pressure (Wet Coil) (IWG)
MODEL
INCHES
MILLIMETERS
PART
NUMBER
FILTERS PER
UNIT
MERV
RATING
8AA1024A
30 x 16 x 2
762 x 406 x 52
80138
1
8
8AA1030A/1036A/1042A & 8AA2030A/2036A/2042A 36½ x 22 x 2
927 x 559 x 52
80162
1
8
8AA1048A/1060A & 8AA2048A/2060A
18 x 24 x 2
457 x 610 x 52
81257
2
8
Table 2. Return Air Filter Sizes
MODEL
LBS
KG
Non-Economizer
8AA1024A
395
179
8AA1030A/1036A & 8AA2036A/2042A
451
205
8AA1048A/1060A & 8AA2048A/2060A
599
272
With Economizer
8AA1024A
415
188
8AA1030A/1036A & 8AA2036A/2042A
471
214
8AA1048A/1060A & 8AA2048A/2060A
619
281
Table 3. Shipping Weights for Marvair Wall Mount AC Units
1.5 General Operation
Model
Ventilation Configuration
Temperature Range
Non-Economizer
Standard ("N")
20ºF – 120ºF (-7ºC – 48.9ºC)
Desert Duty ("ND")
32ºF – 130ºF (-0ºC – 54ºC)
Extreme Duty ("NE"), 60 Hz Only
0ºF – 130ºF (-18ºC – 54ºC)
With Economizer
Standard ("CE")
-40ºF – 120ºF (-40ºC – 48.9ºC)
Desert Duty ("CD")
-40ºF – 130ºF (-40ºC – 54ºC)
Extreme Duty ("CE"), 60 Hz Only
-40ºF – 130ºF (-40ºC – 54ºC)
Table 4. Ambient Temperature Operating Range
Refrigerant Cycle (Cooling Mode)
Marvair air conditioners use R-410A refrigerant in a conventional vapor-compression refrigeration cycle
to transfer heat from air in an enclosed space to the outside. A double blower assembly blows indoor
air across the evaporator. Cold liquid refrigerant passing through the evaporator is boiled into gas by
heat removed from the air. The warmed refrigerant gas enters the compressor where its temperature
and pressure are increased. The hot refrigerant gas condenses to liquid as heat is transferred to outdoor
air drawn across the condenser by the condenser fan. Liquid refrigerant is metered into the evaporator