MARTINDALE MM34 Скачать руководство пользователя страница 3

CONTENTS

1

Introduction

1.1

Description

1.2

Unpacking And Inspection

1.3

Battery Installation

2

Technical Specification

3

Operation

3.1

Precautions

3.2

Voltage Measurement

3.3

Current Measurement

3.4

Resistance Measurement

3.5

Diode Test

3.6

Battery Test

4

Maintenance

4.1

Cleaning

4.2

Battery Replacement

4.3

Fuse Replacement

4.4

Calibration

4.5

Repair & Service

4.6

Storage Conditions

4.7

Warranty

4. MAINTENANCE

4.1 Cleaning

Maintenance consists of periodic cleaning and battery replacement. The
exterior of the instrument can be cleaned with a dry clean cloth to remove
any oil, grease or grime. Never use liquid solvents or detergents.

Repairs or servicing not covered in this manual should only be performed
by qualified personnel.

4.2 Battery Replacement
WARNING - To avoid electrical shock, disconnect the test leads and
any input signals before replacing the battery. Replace only with the
same type of battery.

This meter is powered by NEDA type 1604 or equivalent 9V battery. When
the meter displays the “     ” symbol, the battery must be replaced to
maintain proper operation. To replace the battery, remove the three screws
from the back of the meter and open the bottom case, remove the battery
from battery compartment and replace it with a new one.

4.3 Fuse Replacement 

If no current measurements are possible, check for a blown overload
protection fuse. There are two fuses: F1 for the µA/mA socket and F2 for
the 10A socket. For access to fuses, remove the three screws from the
back of the meter and open the bottom case. Replace F1 only with the
original type 0.5A/250V, fast acting fuse (part no: FUSE500250). Replace
F2 only with the original type 10A/600V, fast acting ceramic fuse (part no:
FUSE10600).

3

10

Содержание MM34

Страница 1: ...ase rotation G Proving units G Socket Testers G Thermometers Probes G Test Leads G Voltage Indicators and G Specialist Metrohm testers 4 5kV G Specialist Drummond testers Martindale Electric Company Limited Metrohm House Penfold Trading Estate Watford WD24 4YY UK Tel 44 0 1923 441717 Fax 44 0 1923 446900 E mail sales martindale electric co uk Website www martindale electric co uk Martindale Electr...

Страница 2: ...re available at www martindale electric co uk instruct html SYMBOLS Equipment complies with relevant EU Directives AC Alternating Current Ground Direct Current Equipment protected by Double Insulation Class II Caution refer to accompanying documents Caution risk of electric shock 4 4 Calibration The recommended calibration interval is 12 months Martindale Electric will carry out routine calibratio...

Страница 3: ...placement WARNING To avoid electrical shock disconnect the test leads and any input signals before replacing the battery Replace only with the same type of battery This meter is powered by NEDA type 1604 or equivalent 9V battery When the meter displays the symbol the battery must be replaced to maintain proper operation To replace the battery remove the three screws from the back of the meter and ...

Страница 4: ... both directions indicates open circuit a reading lower than 0 5 in either direction indicates a shorted diode 3 6 Battery test 1 Connect the red test lead to the µA mA socket and black lead to COM 2 Select either the 1 5V or the 9V Batt switch position 3 Connect the test probes across the battery a satisfactory reading for a 1 5V battery is 1 25V and for a 9V battery is 8 1V Further information r...

Страница 5: ...irt grease etc Check the test leads for any evidence of cracked or frayed insulation If any abnormal conditions exist do not use the meter Warning When using probes keep your fingers behind the guards Warning Measuring voltages which exceed the limits of the meter may damage it and expose the operator to a shock hazard Always work within the meter voltage limits indicated on it s front panel Warni...

Страница 6: ...ccuracy 3 rdg 1 digit Open circuit voltage 3V DC typical Overload protection 500V DC or AC rms BATTERY TEST Ranges 1 5V 9V Resolution 1mV 10mV Accuracy 3 5 rdg 2 digits Load current 150mA for 1 5V range typical 6mA for 9V range typical NOTE This instrument complies with class ll overvoltage CAT lll 600V of the IEC1010 1 EN61010 1 standard and pollution degree 2 in accordance with IEC 664 indoor us...

Отзывы: