STEPS TO REMOVE THE ACTUATOR
To remove the actuator, perform the above
steps in the reverse order.
STEP #5
–
Actuator shown installed and
ready to use.
4.4
The indicator lights & controls:
NOTE: Red and Green indicator lights only work
when the ENABLE button is depressed.
GREEN
: indicates the actuator is being
commanded to extend the ON actuator.
RED
: indicates the actuator is being commanded
to extend the OFF actuator.
YELLOW
: indicates the hand-held controller is
powered and is ready.
Rapidly blinking YELLOW
indicates the battery
voltage with zero load has fallen to an
unacceptable level. Operation is inhibited until
batteries with an acceptable voltage level are
installed.
The ENABLE button:
The Enable button must be continuously depressed
in order to command the actuator.
Releasing the enable button has the same affect as
releasing either the ON or OFF buttons – both
actuators will move to the retracted position.
Note:
If either of the actuators are held in the extended
position for longer than approximately 2 seconds
the actuator will de-energize and will remain in
extended position. When the pushbutton or the
enable button is released, the actuator will retract.