background image

 

 

4.0 

Operation  

 
ALWAYS connect the control cable to the actuator 
BEFORE installing the Chicken Switch®. 
 

4.1 

Connecting the control cable:

 

 

 

 

 

1.

 

Align the arrow on the cable end with the top of 
the receptacle.   

2.

 

Push in and engage the threads on the coupling 
nut and turn clockwise. 

3.

 

After one or two turns of the coupling nut, push 
in on the cable end.  Repeat this until the 
connector is fully seated. 

4.

 

Use a similar technique of turn-stop-and-pull to 
disengage the cable ends. 

 

4.2 

Sequence of Operation: 

 

1.

 

The breaker can be charged before or after 
installing the K20 actuator. 

2.

 

Connect the control cable to the actuator and to 
the hand-held controller.  

3.

 

Position the actuator on the breaker by 
completing the steps on the following pages. 

4.

 

Ensure you are at a safe distance from the circuit 
breaker that is to be operated. 

5.

 

Turn the Power Switch on top of the hand-held 
controller to the ON position.  The amber LED 
should illuminate indicating the unit is ready. 
 

 

 
 

6.

 

When ready to operate the actuator, press and 
HOLD the ENABLE button while depressing either 
then TRIP or CLOSE button for the desired 
operation.  Both buttons must be held depressed 
until the actuator had fully depressed the button.   

7.

 

Release the ENABLE and TRIP or CLOSE buttons 
and the actuator will retract. 

 

4.3 

Attaching and Removing the Actuator:

 

 

 

 

 

 

 

 

 

 

 

       

 

 

 

STEP #1

 – 

Before installing the actuator, 

verify that the plungers are fully retracted 
below the actuator frame surface.  If 
plungers are NOT fully retracted, DO NOT 
install the actuator. Doing so could cause the 
breaker to inadvertently trip or close.

 

Содержание Chicken Switch K-15

Страница 1: ... magnets 3 0 Battery Information 3 0 Battery Requirements 3 1 Battery Life 3 2 Battery Replacement 3 3 Connecting Disconnecting Batteries 3 4 Static Discharge Potential 4 0 Operation 4 1 Connecting the control cable 4 2 Sequence of operation 4 3 Attaching and removing the actuator 4 4 Indicator lights 5 0 Care and Storage 5 1 Cleaning debris from magnets 5 2 Storage 6 0 Warranty 7 0 Specifications...

Страница 2: ...eeded Electrical switching may present risk of serious injury or death This device should only be used by qualified persons after careful analysis of the hazards WARNING 2 0 Safety Information ALWAYS connect the control cable to the actuator BEFORE installing the Chicken Switch 2 1 Finger pinch points Keep fingers clear of the bottom of the actuator when the actuator is near a ferrous surface 2 2 ...

Страница 3: ...e control station upside down remove the endplate retaining knob Remove the endplate and slide the cover out as shown above 3 3 To connect disconnect batteries 3 4 CAUTION Static Discharge Potential To avoid possible damage to electronic components disconnect the control cable before replacing batteries WARNING To avoid possible damage to electronic components disconnect control cable before repla...

Страница 4: ... breaker by completing the steps on the following pages 4 Ensure you are at a safe distance from the circuit breaker that is to be operated 5 Turn the Power Switch on top of the hand held controller to the ON position The amber LED should illuminate indicating the unit is ready 6 When ready to operate the actuator press and HOLD the ENABLE button while depressing either then TRIP or CLOSE button f...

Страница 5: ...r shown by BLUE arrows STEP 4 While continuing to hold the actuator frame against the top edge of the breaker flip the magnet levers shown by RED arrows so the magnets engage the switchgear door NOTE The actuator frame must be against the top breaker edge or the actuator plungers will not align properly with the breaker TRIP and CLOSE buttons ...

Страница 6: ...idly blinking YELLOW indicates the battery voltage with zero load has fallen to an unacceptable level Operation is inhibited until batteries with an acceptable voltage level are installed The ENABLE button The Enable button must be continuously depressed in order to command the actuator Releasing the enable button has the same affect as releasing either the ON or OFF buttons both actuators will mo...

Страница 7: ...this does occur use a paper towel or nylon bristle brush to clean the face of the magnets Keeping the magnet faces clean ensures that maximum holding power is maintained 5 2 Storage Remove all batteries from the control station if the device will not be used for longer than 6 months Never store the batteries where the ambient temperature might exceed 110º F Avoid getting the unit wet or storing it...

Страница 8: ... INCLUDING WITHOUT LIMITATION LOST PROFITS EVEN IF ADVISED OF THE POSSIBILITY OF SUCH DAMAGES MarTek Ltd reserves the right to disallow warranty repairs if the unit has been disassembled or misused as determined by MarTek Ltd in good faith Please contact us at 800 248 4958 for a return authorization MarTek Ltd 4782 Chimney Drive Charleston WV 25302 1 304 965 9220 1 800 248 4958 7 0 Specifications ...

Страница 9: ...Registered Trademark of MarTek Ltd US Patent 7 623 011 Copyright 2004 2016 MarTek Ltd All rights reserved MarTek Ltd 4782 Chimney Drive Charleston WV 25302 1 800 248 4958 www chickenswitch com User Manual K 15 Version 1 1 ...

Отзывы: