Marstair DCU+ 15 Скачать руководство пользователя страница 8

 

54208003-13 

 

 

4. 

If a manual HP cutout is fitted, ensure that the reset button is depressed. 

 

5. 

Additional refrigerant and polyolester oil should be introduced through the Schrader valve on the indoor 
unit, or the service port on the suction service valve on the outdoor unit. 

Ensure the refrigerant is the 

correct type, as shown on the rating plate

. R407C must always be added in the liquid state. 

 

6. 

Run the system for a few minutes to allow it to stabilize. Where possible, charge to a sweat line on the 
evaporator. Typical suction pressures on short lines at UK conditions, with high speed evaporator fan, 
high speed condenser fan, should be; electromechanical comfort system approx 4.4 bar (65 psig); 
electronic comfort system approx 3.8 bar (55 psig); heat pump system approx (58 psig). 

Systems 

should not be overcharged, to avoid liquid return to the compressor

 
 

7. 

  

DCU+/DHPUL: HEAD PRESSURE CONTROL SAGINOMIYA (RGE 

– ZIN4 – SH)

 

The head pressure controller is factory set to suit the refrigerant. It may be necessary to adjust this to suit 
site conditions, to raise or lower the nominal head pressure. 

 
 
 
 
 
 
 
 
 
 

a.  With the system switched off, connect a high pressure gauge to the liquid line service valve. 

 

b.  Switch on the system, indoor fan set to high speed, and run for a few minutes to stabilise. 

 

c.  The head pressure should be approximately: 

E

le

c

tric

sb

o

x

H

e

a

dp

re

ss

u

re

a

d

ju

s

tm

e

n

tsc

re

w

F

a

nc

a

p

a

cito

r

 

 

R407C: 275-280 psig (18.9-19.6barg) 

to achieve this adjust the screw clockwise to increase pressure or 

anticlockwise to decrease. Each ½ turn will alter the pressure by approx 5 psig (0.5 barg) 
 
Min fan speed (0 rpm) and fan cut in pressure 200 psig (13.8 barg) are factory set and not adjustable. 
 

NOTE: 

The condenser fan may stop if the operating pressure drops below 200 psig (13.8 barg) 

 
 
 
 

8.  DCU+/DHPUL: HEAD PRESSURE CONTROL ALCO (FSY-42S)

 

The head pressure controller is factory set to suit the refrigerant. It may be necessary to adjust this to suit 
site conditions, to raise or lower the nominal head pressure. 

 
 
 
 
 

 

 

 

 

 
a.  With the system switched off, connect a high pressure gauge to the liquid line service valve. 

Содержание DCU+ 15

Страница 1: ...g parts and refrigerant under pressure Always site out of reach of children and protect from vandalism 3 The units have fan speed control start delay timer HP and LP switches and a contactor fitted as...

Страница 2: ...560 1174 490 65 65 240 392 865 404 81 DCU 60 1100 510 560 1174 490 65 65 240 392 865 404 81 DCU 80 1100 510 560 1174 490 65 65 240 392 865 404 84 DHPU L 15 930 510 495 1004 490 65 120 210 317 757 354...

Страница 3: ...ers to suit IMPORTANT The stabilizing brackets provided MUST be used when suspending a unit Fit the stabilizing brackets to the top corners of the backpanel and front face using the No 10 screws provi...

Страница 4: ...n thickness of at least 45mm is recommended 1 To maximise performance pipe runs should be kept as short as possible However individual pipe runs to a maximum of 80m 50m on sizes 15 20 including 20m li...

Страница 5: ...Use the shortest possible route avoiding sharp bends 5 Fully insulate both the suction and expansion lines including the expansion device since both lines may sweat FITTING LOSSES in equivalent strai...

Страница 6: ...check valve is needed The expansion assembly and line must be fully insulated Note The indoor units listed below are fitted with heating capillarys WM60H WM80H WM100H CC875 80H CC875 110H CC875 140H H...

Страница 7: ...le charge to a sweat line on the evaporator Typical suction pressures on short lines at UK conditions with maximum evaporator and condenser fan speeds i e during commissioning will be 55 60 psig Take...

Страница 8: ...t to suit the refrigerant It may be necessary to adjust this to suit site conditions to raise or lower the nominal head pressure a With the system switched off connect a high pressure gauge to the liq...

Страница 9: ...hanges per turn of adjusting screw Pressure change 1 4 0 12 5 bar Clockwise 1 2 bar counter clockwise 1 2 bar Pressure change 2 9 2 21 2 bar Clockwise 2 5 bar counter clockwise 2 5 bar Pressure change...

Страница 10: ...hed cables ElectromechanicalSystems Systems including an electromechanical indoor unit require a supply to the condensing unit with connecting cables run to the indoor unit Electronic Systems It is re...

Страница 11: ...400V 3 50Hz disjoncteur a fournir 400 3 N 50 abgesicherts versorgung 400V 3 50Hz S S 1 3 7 S S Signal Ansteurung 230V 50Hz 1 3 7 S S SIGNAL 1 230V 50Hz 7 POWER TO SUIT SUPPLY FUSE PUISSANCE FOURNIR U...

Страница 12: ...characteristics that allow starting of the compressor yet still afford close overcurrent protection under running conditions The ratings shown are for HRC motor rated fuses DUCTED UNITS DCU 15 DCU 20...

Отзывы: